ABB 1SDA123498R1 Moulded Case Circuit Breaker - IEC 60947-2

Part Number: 1SDA123498R1
Manufacturer
ABB
Part number
1SDA123498R1

Quick Summary

ABB 1SDA123498R1 Moulded Case Circuit Breaker is a DC protection device for distribution panels and control cabinets. Engineers often struggle with reliable DC protection in tight panel spaces and front-terminal access. This solution aligns with IEC 60947-2, CE conformity, and RoHS/REACH, supporting compliant, sustainable operation. In addition, its compact footprint and fixed front-terminal design speed wiring and reduce installation time, improving maintenance efficiency for 3P 20A DC circuits.

Product Information

Extended Description

1SDA123498R1 ABB: C.BREAKER TMAX XT2N 160 DC FIXED THREE-POLE WITH FRONT TERMINALS AND THERMOMAGNETIC RELEASE TMD R 20
ABB EcoSolutions
Yes
ABB Site Meeting Group Waste To Landfill Target
UL 2799 Zero Waste To Landfill Validation available
End Of Life Disassembling Instructions
Disassembly instructions Tmax XT XT2 TM
Environmental Product Declaration - EPD
EPD Tmax XT XT2 TM (CN)
Recyclability Rate of the Product acc. to EN45555
Design for Closing Resource Loops - Standard EN45555 - 55.7 %
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
Document availability on demand
Customs Tariff Number
85362000
Product Net Width
90 mm
Product Net Height
130 mm
Product Net Depth / Length
82.5 mm
Product Net Weight
1.2 kg
Product Name
Moulded Case Circuit Breaker
Product Type
CB
Version
F
Current Type
DC
Mechanical Durability
25000 cycle | ;240 cycles per hour
Number of Poles
3P
Power Loss
at Rated Operating Conditions per Pole 1.62 W
Rated Current (In)
20 A
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
500 V DC
Rated Service Short-Circuit Breaking Capacity (Ics)
(250 V DC) 2 Poles in Series 36 kA | (500 V DC) 3 Poles in Series 36 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(250 V DC) 2 Poles in Series 36 kA | (500 V DC) 3 Poles in Series 36 kA
Rated Uninterrupted Current (Iu)
160 A
Release
TMD
Release Type
TM
Short-Circuit Performance Level
N
Standards
IEC 60947-2 | GB/T 14028.2
Sub-type
XT2
Terminal Connection Type
Fixed Circuit-Breakers
Declaration of Conformity - CE
EC Declaration of Conformity Tmax XT2
Instructions and Manuals
Installation instructions XT2 DC IEC
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
Feature: 3P DC protection with rated current of 20 A and rated operational voltage of 500 V DC. Business Impact: Delivers reliable overcurrent protection for DC power rails while minimizing voltage drops and thermal stress. Application: Ideal for DC distribution in control panels and motor control centers. Feature: High short-circuit performance with Ics and Icu of 36 kA at 500 V DC. Business Impact: Enhances system safety by ensuring rapid, clean disconnection under fault conditions, reducing arc energy and downstream damage. Application: Suitable for demanding DC bus protection in critical applications. Feature: Front-terminal, fixed-circuit-breaker design. Business Impact: Speeds installation and simplifies maintenance, cutting wiring time and cabinet depth requirements. Application: Preferred in compact control panels where service access is limited. Feature: Low power loss of 1.62 W per pole. Business Impact: Improves energy efficiency and reduces heat generation, improving reliability in warm environments. Application: Beneficial for continuous-duty installations and densely packed enclosures. Feature: ABB EcoSolutions compatibility with documented end-of-life guidance and recyclability (55.7% EN45555). Business Impact: Supports sustainability targets and compliant disposal without compromising protection. Application: Fits manufacturers pursuing responsible lifecycle management and regulatory alignment.

Get a Quick Quote for a ABB 1SDA123498R1

Chat with us on WhatsApp - fast responses guaranteed

Need to speak with someone? We'll call you back within 2 hours during business hours

Interested in ABB 1SDA123498R1? Enquire Now

FAQs

For starters, use the fixed front-terminal connection to simplify wiring and service access in tight spaces. The 3P design fits standard 90 mm width enclosures with front-access terminals, and the device supports 500 V DC operation. Ensure proper rail mounting, verify clearance for heat dissipation, and follow installation instructions XT2 DC IEC for reliable protection.
The unit is rated for 20 A continuous current, 500 V DC operational voltage, and a short-circuit current rating of 36 kA (Ics and Icu) for 3P configurations. It withstands 8 kV impulse without breakdown and remains reliable under fault conditions, making it suitable for DC distribution in demanding environments.
Yes. With 3P configuration, front-terminal access, and a robust 36 kA fault current capability at 500 V DC, it is well-suited for DC distribution in motor control centers and control panels. Its compact XT2 design ensures easy integration into standard MCCs and panelboards while maintaining protection integrity.
It complies with IEC 60947-2 and GB/T 14028.2 standards, carries a CE declaration of conformity, and adheres to RoHS/REACH requirements. End-of-life documentation and ABB EcoSolutions support sustainable practices, including recyclability targets and disassembly guidance.
Ownership offers reduced wiring time thanks to front-terminal design, lower energy loss at 1.62 W per pole, and high mechanical durability (up to 25,000 cycles). These factors translate to faster commissioning, longer intervals between maintenance, and lower total cost of ownership in DC power protection applications.