ABB 1SDA123502R1 Moulded Case Circuit Breaker - IEC 60947-2

Part Number: 1SDA123502R1
Manufacturer
ABB
Part number
1SDA123502R1

Quick Summary

Moulded Case Circuit Breaker ABB 1SDA123502R1 provides precise DC protection for 3P power distribution in demanding industrial environments. This compact solution addresses space constraints and challenging maintenance by offering front-terminal access and a fixed connection design that speeds installation and reduces wiring errors. It is engineered to IEC 60947-2 standards with CE conformity and RoHS compliance, supporting safe, compliant operation across global facilities. For OEMs and panel builders, the combination of reliable protection, straightforward sourcing, and scalable performance translates to lower total cost of ownership and faster project rollout.

Product Information

Extended Description

1SDA123502R1 ABB: C.BREAKER TMAX XT2N 160 DC FIXED THREE-POLE WITH FRONT TERMINALS AND THERMOMAGNETIC RELEASE TMA R 50
ABB EcoSolutions
Yes
ABB Site Meeting Group Waste To Landfill Target
UL 2799 Zero Waste To Landfill Validation available
End Of Life Disassembling Instructions
Disassembly instructions Tmax XT XT2 TM
Environmental Product Declaration - EPD
EPD Tmax XT XT2 TM (CN)
Recyclability Rate of the Product acc. to EN45555
Design for Closing Resource Loops - Standard EN45555 - 55.7 %
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
Document availability on demand
Customs Tariff Number
85362000
Product Net Width
90 mm
Product Net Height
130 mm
Product Net Depth / Length
82.5 mm
Product Net Weight
1.2 kg
Product Name
Moulded Case Circuit Breaker
Product Type
CB
Version
F
Current Type
DC
Mechanical Durability
25000 cycle | ;240 cycles per hour
Number of Poles
3P
Power Loss
at Rated Operating Conditions per Pole 4.09 W
Rated Current (In)
50 A
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
500 V DC
Rated Service Short-Circuit Breaking Capacity (Ics)
(250 V DC) 2 Poles in Series 36 kA | (500 V DC) 3 Poles in Series 36 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(250 V DC) 2 Poles in Series 36 kA | (500 V DC) 3 Poles in Series 36 kA
Rated Uninterrupted Current (Iu)
160 A
Release
TMA
Release Type
TM
Short-Circuit Performance Level
N
Standards
IEC 60947-2 | GB/T 14028.2
Sub-type
XT2
Terminal Connection Type
Fixed Circuit-Breakers
Declaration of Conformity - CE
EC Declaration of Conformity Tmax XT2
Instructions and Manuals
Installation instructions XT2 DC IEC
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
DC rated current and voltage: 50 A at 500 V DC with three poles provides dedicated protection for critical DC buses. This specification ensures the system remains protected under normal operation while allowing selective disconnection during faults, reducing downtime and equipment damage in drive and DC bus applications. In practice, engineers gain predictable fault isolation in automation cabinets and data-center DC rails, supporting reliable uptime and easier fault tracing. Front-terminal fixed connections: the design simplifies wiring during panel assembly and maintenance, speeding commissioning and reducing the chance of loose connections that can cause nuisance trips. In real-world installations, this translates to shorter installation windows and improved long-term reliability in crowded control cabinets. High impulse withstand and fault capacity: with an 8 kV rated impulse withstand and 36 kA short-circuit capacity, the device handles transients common in welding, drives, and renewable energy interfaces. This capability minimizes arc energy risk and enhances safety for operators and technicians during fault events. RoHS and REACH compliance with EPD support: the ABB EcoSolutions framework ensures sustainable procurement and regulatory compliance across global supply chains, reducing lifecycle risk for buyers. In practice, this means easier supplier qualification and a lower overall environmental impact while maintaining high protection standards. Mechanical durability and compact footprint: rated for 25,000 operating cycles with a compact 90 mm x 130 mm x 82.5 mm enclosure and a 1.2 kg weight, it fits modern control cabinets and retrofit projects without sacrificing protection quality. This longevity reduces maintenance intervals and lifecycle costs in high-usage environments such as packaging lines or machine trolleys.

Get a Quick Quote for a ABB 1SDA123502R1

Chat with us on WhatsApp - fast responses guaranteed

Need to speak with someone? We'll call you back within 2 hours during business hours

Interested in ABB 1SDA123502R1? Enquire Now

FAQs

For optimum performance, mount the MCCB with fixed front terminals to simplify wiring and inspection. Ensure adequate clearance for cooling, secure terminal connections to prevent looseness, and follow the IEC 60947-2 installation instructions to maintain safety clearances and reliable tripping.
The device is a 3P MCCB rated for 50 A, with a rated operating voltage of 500 V DC and insulation voltage of 1000 V. It provides 8 kV impulse withstand, Ics/Icu up to 36 kA, and a rated service current of 160 A, suitable for demanding DC power protection.
Yes. Its 500 V DC rating, 3P configuration, and robust short-circuit capacity make it appropriate for PV DC circuits and battery interfaces, where reliable protection and ease of maintenance are critical. Ensure compatibility with the system’s fault current levels and wiring practices.
It conforms to IEC 60947-2 and carries CE conformity and RoHS compliance. ABB’s EC Declaration of Conformity and related documentation support regulatory alignment, while its EPD and recyclability data aid sustainability reporting.
The device supports up to 25,000 mechanical operating cycles, delivering long life in high-throughput environments. Regular inspection of terminals and release mechanism, together with adherence to installation manuals, helps maintain performance and reduces the risk of unexpected trips.