ABB 1SDA123509R1 Moulded Case Circuit Breaker - IEC 60947-2

Part Number: 1SDA123509R1
Manufacturer
ABB
Part number
1SDA123509R1

Quick Summary

ABB 1SDA123509R1 is a four-pole DC moulded case circuit breaker for reliable DC protection in industrial power networks. Engineers often contend with tight panel spaces, complex wiring, and the need for rapid, fail-safe disconnections during fault conditions. This device aligns with IEC 60947-2, CE conformity, and RoHS compliance, with additional End-of-Life guidance and an Environment Product Declaration option. Its fixed-terminal design and 20 A rating at 500 V DC support efficient protection for control panels, drives, and energy systems, while reducing installation time, maintenance, and lifecycle costs. In short, it blends compact practicality with robust electrical protection for modern automation environments.

Product Information

Extended Description

1SDA123509R1 ABB: C.BREAKER TMAX XT2N 160 DC FIXED FOUR-POLE WITH FRONT TERMINALS AND THERMOMAGNETIC RELEASE TMD R 20
ABB EcoSolutions
Yes
ABB Site Meeting Group Waste To Landfill Target
UL 2799 Zero Waste To Landfill Validation available
End Of Life Disassembling Instructions
Disassembly instructions Tmax XT XT2 TM
Environmental Product Declaration - EPD
EPD Tmax XT XT2 TM (CN)
Recyclability Rate of the Product acc. to EN45555
Design for Closing Resource Loops - Standard EN45555 - 55.7 %
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
Document availability on demand
Customs Tariff Number
85362000
Product Net Width
120 mm
Product Net Height
130 mm
Product Net Depth / Length
82.5 mm
Product Net Weight
1.6 kg
Product Name
Moulded Case Circuit Breaker
Product Type
CB
Version
F
Current Type
DC
Mechanical Durability
25000 cycle | ;240 cycles per hour
Number of Poles
4P
Power Loss
at Rated Operating Conditions per Pole 1.62 W
Rated Current (In)
20 A
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
500 V DC
Rated Service Short-Circuit Breaking Capacity (Ics)
(250 V DC) 2 Poles in Series 36 kA | (500 V DC) 3 Poles in Series 36 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(250 V DC) 2 Poles in Series 36 kA | (500 V DC) 3 Poles in Series 36 kA
Rated Uninterrupted Current (Iu)
160 A
Release
TMD
Release Type
TM
Short-Circuit Performance Level
N
Standards
IEC 60947-2 | GB/T 14028.2
Sub-type
XT2
Terminal Connection Type
Fixed Circuit-Breakers
Declaration of Conformity - CE
EC Declaration of Conformity Tmax XT2
Instructions and Manuals
Installation instructions XT2 DC IEC
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
Feature → Business Impact → Application: Front-terminal, fixed 4P configuration simplifies wiring and reduces installation time in DC distribution panels, improving site safety and reliability for automation drives. Feature → Business Impact → Application: Thermal-magnetic TMD release delivers reliable trip performance under DC fault currents, minimizing unplanned downtime in manufacturing lines and process controls. Feature → Business Impact → Application: Rated In 20 A and 500 V DC capability supports compact, high-integrity protection for intelligent control panels, with a wide insulation margin up to 1000 V, enabling safer, denser installations. Feature → Business Impact → Application: Short-circuit ratings (Ics/Icu up to 36 kA in series) provide strong protection for feeders and drives, reducing damage and maintenance costs in high-energy DC systems. Feature → Business Impact → Application: 25,000 mechanical cycles and 1.62 W per pole power loss translate to longer service life and cooler operation, lowering replacement and cooling costs in continuous production environments. Feature → Business Impact → Application: Compact footprint (120 × 130 × 82.5 mm) and 1.6 kg weight enable easy replacement in existing panels, compatible with standard mounting and wiring practices. Feature → Business Impact → Application: RoHS, REACH, EPD, and End-of-Life instructions support sustainability programs and recycling targets, improving total cost of ownership and compliance in regulated markets. Feature → Business Impact → Application: Clear documentation for disassembly and recycling reduces maintenance time and supports closed-loop waste reduction in industrial facilities.

Get a Quick Quote for a ABB 1SDA123509R1

Chat with us on WhatsApp - fast responses guaranteed

Need to speak with someone? We'll call you back within 2 hours during business hours

Interested in ABB 1SDA123509R1? Enquire Now

FAQs

Install the 4P fixed-mount breaker in a compatible DC panel, connect conductors to the front terminals using appropriate terminal torque per the panel spec, and verify insulation between live parts. Confirm the device is correctly seated, the release mechanism engages reliably, and the wiring matches the 20 A rating and 500 V DC operating range to ensure proper protection.
Rated Current In is 20 A, rated operational voltage is 500 V DC, and rated insulation voltage Ui is 1000 V. It provides a rated impulse withstand voltage Uimp of 8 kV. Short-circuit performance is up to 36 kA (Ics/Icu) under specified conditions, with a rated uninterrupted current of 160 A, supporting reliable protection for DC feeders and drives.
The 4P XT2N DC MCCB with TM/TMD release is suitable for protective switching in DC distribution to protect drives and panels, particularly where front-terminal wiring and compact form-factor are beneficial. It offers robust short-circuit protection (Ics/Icu up to 36 kA) and 500 V DC capability, but ensure the continuous operating current and duty cycle align with your motor drive's load profile.
It complies with IEC 60947-2 standards and CE declarations, with RoHS compliance and REACH declarations. End-of-Life guidance, disassembly instructions, and an Environmental Product Declaration (EPD) option are available, along with recyclability data under EN45555, supporting sustainability and regulatory requirements.
With a mechanical durability rating of 25,000 cycles and a low power loss of 1.62 W per pole, the unit reduces wear, thermal stress, and cooling needs, lowering maintenance and energy costs. Its recyclability rating (55.7%) and disassembly guidance facilitate end-of-life recycling, supporting corporate sustainability targets and potentially lowering total cost of ownership over the product lifecycle.