ABB 1SDA123514R1 Moulded Case Circuit Breaker - 60947-2

Part Number: 1SDA123514R1
Manufacturer
ABB
Part number
1SDA123514R1

Quick Summary

Moulded Case Circuit Breaker protects DC power circuits in industrial automation panels. Engineers face challenges with reliable arc interruption, compact wiring, and serviceability in crowded control enclosures. This ABB device meets IEC 60947-2 and CE conformity, backed by a full environmental profile (EPD) and recyclability data per EN45555. It also aligns with GB/T 14028.2 for broader regional compliance. With front-terminal wiring, a four-pole configuration, and a TM release, it simplifies installation and maintenance while fitting tightly spaced cabinets. The combination of reliability, compliance, and sustainability translates to lower lifecycle costs and improved uptime for critical DC applications in manufacturing and process automation.

Product Information

Extended Description

1SDA123514R1 ABB: C.BREAKER TMAX XT2N 160 DC FIXED FOUR-POLE WITH FRONT TERMINALS AND THERMOMAGNETIC RELEASE TMA R 63
ABB EcoSolutions
Yes
ABB Site Meeting Group Waste To Landfill Target
UL 2799 Zero Waste To Landfill Validation available
End Of Life Disassembling Instructions
Disassembly instructions Tmax XT XT2 TM
Environmental Product Declaration - EPD
EPD Tmax XT XT2 TM (CN)
Recyclability Rate of the Product acc. to EN45555
Design for Closing Resource Loops - Standard EN45555 - 55.7 %
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
Document availability on demand
Customs Tariff Number
85362000
Product Net Width
120 mm
Product Net Height
130 mm
Product Net Depth / Length
82.5 mm
Product Net Weight
1.6 kg
Product Name
Moulded Case Circuit Breaker
Product Type
CB
Version
F
Current Type
DC
Mechanical Durability
25000 cycle | ;240 cycles per hour
Number of Poles
4P
Power Loss
at Rated Operating Conditions per Pole 4.85 W
Rated Current (In)
63 A
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
500 V DC
Rated Service Short-Circuit Breaking Capacity (Ics)
(250 V DC) 2 Poles in Series 36 kA | (500 V DC) 3 Poles in Series 36 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(250 V DC) 2 Poles in Series 36 kA | (500 V DC) 3 Poles in Series 36 kA
Rated Uninterrupted Current (Iu)
160 A
Release
TMA
Release Type
TM
Short-Circuit Performance Level
N
Standards
IEC 60947-2 | GB/T 14028.2
Sub-type
XT2
Terminal Connection Type
Fixed Circuit-Breakers
Declaration of Conformity - CE
EC Declaration of Conformity Tmax XT2
Instructions and Manuals
Installation instructions XT2 DC IEC
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
DC protection with a 63 A rated current and 4P configuration delivers robust safeguarding of DC distribution in automation panels, while front-terminal wiring simplifies installation and future maintenance, reducing cabinet complexity. The thermomagnetic release (TMA TM) provides fast, reliable tripping for short-circuit events, supporting up to 36 kA breaking capacity in the specified configurations, which translates to minimized downtime and protection for sensitive drives and power buses. With 25,000 mechanical cycles durability, the device is built for frequent operation in dynamic manufacturing environments, delivering consistent performance and extended service life. Low power loss of 4.85 W per pole improves overall system energy efficiency, contributing to lower operating costs in high-availability plants. Sustainability features include an EPD (CN), 55.7% recyclability per EN45555, RoHS/REACH compliance, and end-of-life disassembly guidance, aligning with modern corporate responsibility programs. The MCCB adheres to IEC 60947-2 and GB/T 14028.2 standards, ensuring compatibility with global panels and a wide range of ABB EcoSolutions initiatives. Built as part of the Tmax XT2 family, it offers reliable protection for DC buses in servo drives, battery storage interfaces, and other critical loads, while streamlining commissioning thanks to standardized mounting and wiring practices.

Get a Quick Quote for a ABB 1SDA123514R1

Chat with us on WhatsApp - fast responses guaranteed

Need to speak with someone? We'll call you back within 2 hours during business hours

Interested in ABB 1SDA123514R1? Enquire Now

FAQs

Ensure correct mounting clearance and panel space for a 4P MCCB. Connect each of the four front terminals with appropriate torque as specified in the XT2 DC installation instructions. Verify polarity and ensure the device is fully seated in its fixed-circuit-breaker enclosure. Use the TM release to confirm proper tripping behavior during a test.
The device provides a rated service short-circuit breaking capacity (Ics) of 36 kA for 250 V DC when configured as two poles in series, and 36 kA for 500 V DC when configured as three poles in series. The rated ultimate short-circuit breaking capacity (Icu) matches these values, ensuring strong protection for high-energy DC systems.
Yes. With 4P configuration, DC operation up to 500 V, 63 A nominal current, and TM/TMA thermomagnetic release, this MCCB is well-suited for DC buses in servo drives, motor drives, and energy storage interfaces where fast interruption and reliable protection are critical for uptime and equipment longevity.
It complies with IEC 60947-2 and GB/T 14028.2, and carries CE conformity (EC Declaration of Conformity). Supporting documentation includes installation instructions XT2 DC IEC and environmental declarations like EPD (CN), RoHS, REACH, and end-of-life information under EN45555.
With a mechanical durability rating of 25,000 cycles and a modest 4.85 W power loss per pole, it reduces wear and energy costs in frequent switching scenarios. Front-terminal design and fixed mounting simplify maintenance and replacement, lowering downtime and contributing to lower total cost of ownership in high-availability DC networks.