ABB 1SDA123519R1 Moulded Case Circuit Breaker - IEC 60947-2

Part Number: 1SDA123519R1
Manufacturer
ABB
Part number
1SDA123519R1

Quick Summary

The ABB 1SDA123519R1 DC Moulded Case Circuit Breaker is designed for DC distribution panels in harsh industrial environments. Engineers struggle with reliable DC fault interruption and predictable performance under high fault currents and frequent maintenance. It complies with IEC 60947-2 and GB/T 14028.2, carries the CE Declaration of Conformity, and supports end-to-end safety requirements. The compact, fixed-terminal design and DC operating characteristics enable robust short-circuit protection, while easy installation lowers commissioning costs. For procurement and maintenance teams, traceable compliance data (RoHS/REACH) and EcoSolutions guidance help streamline sourcing and end-of-life planning. Overall, this XT2 family device delivers reliable DC performance, supports waste-reduction goals, and reduces total cost of ownership through longer service intervals.

Product Information

Extended Description

1SDA123519R1 ABB: XT2S160 DC TMD16 FF 3P
ABB EcoSolutions
Yes
ABB Site Meeting Group Waste To Landfill Target
UL 2799 Zero Waste To Landfill Validation available
End Of Life Disassembling Instructions
Disassembly instructions Tmax XT XT2 TM
Environmental Product Declaration - EPD
EPD Tmax XT XT2 TM (CN)
Recyclability Rate of the Product acc. to EN45555
Design for Closing Resource Loops - Standard EN45555 - 55.7 %
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
Document availability on demand
Customs Tariff Number
85362000
Product Net Width
90 mm
Product Net Height
130 mm
Product Net Depth / Length
82.5 mm
Product Net Weight
1.2 kg
Product Name
Moulded Case Circuit Breaker
Product Type
CB
Version
F
Current Type
DC
Mechanical Durability
25000 cycle | ;240 cycles per hour
Number of Poles
3P
Power Loss
at Rated Operating Conditions per Pole 1.33 W
Rated Current (In)
16 A
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
500 V DC
Rated Service Short-Circuit Breaking Capacity (Ics)
(250 V DC) 2 Poles in Series 50 kA | (500 V DC) 3 Poles in Series 50 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(250 V DC) 2 Poles in Series 50 kA | (500 V DC) 3 Poles in Series 50 kA
Rated Uninterrupted Current (Iu)
160 A
Release
TMD
Release Type
TM
Short-Circuit Performance Level
S
Standards
IEC 60947-2 | GB/T 14028.2
Sub-type
XT2
Terminal Connection Type
Fixed Circuit-Breakers
Declaration of Conformity - CE
EC Declaration of Conformity Tmax XT2
Instructions and Manuals
Installation instructions XT2 DC IEC
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
The 3P design with a 16 A rating is tailored for compact DC feeders, enabling panel space optimization and cost efficiency while maintaining predictable tripping behavior for critical DC circuits. This directly reduces footprint and simplifies cabinet layouts in automation rooms, data centers, and plant power rails. The device delivers a high short-circuit capacity of up to 50 kA (Ics/Icu) at both 250 V DC (2 poles in series) and 500 V DC (3 poles in series), providing robust fault isolation and minimizing downtime during fault events. In practice, this means fewer cascade failures and faster recovery in high-energy DC buses, which is essential for continuous production lines and mission-critical automation. Compliance with IEC 60947-2 and GB/T 14028.2 ensures predictable performance across regional standards, easing supplier qualification and system integration. The RoHS and REACH declarations, plus ABB EcoSolutions data, support sustainability targets and allow for easier reporting in corporate ESG programs. With a rated operational voltage of 500 V DC and an insulation voltage of 1000 V, the breaker offers increased safety margins for higher-voltage DC networks and surge-prone environments. The 1.33 W power loss per pole minimizes heat generation, reducing cooling requirements and enabling longer service intervals. Mechanical durability of 25,000 cycles supports frequent switching, lowering maintenance frequency and operational costs for automated lines. The fixed-terminal connection and 3P configuration simplify installation, wiring, and future upgrades, ensuring a reliable, scalable protection solution for evolving control panels.

Get a Quick Quote for a ABB 1SDA123519R1

Chat with us on WhatsApp - fast responses guaranteed

Need to speak with someone? We'll call you back within 2 hours during business hours

Interested in ABB 1SDA123519R1? Enquire Now