ABB 1SDA123529R1 Moulded Case Circuit Breaker - IEC 60947-2

Part Number: 1SDA123529R1
Manufacturer
ABB
Part number
1SDA123529R1

Quick Summary

ABB 1SDA123529R1 is a 3-pole DC moulded case circuit breaker designed to protect DC power distribution in industrial automation and energy storage applications. It helps reduce downtime by providing precise, rapid interruption during fault events in 500 V DC systems up to 160 A. The device carries IEC 60947-2 certification and a CE declaration of conformity, along with RoHS compliance and an environmental performance footprint (EPD) through ABB EcoSolutions. With recyclable design considerations and end-of-life disassembly guidance, this MCCB supports sustainable, compliant installations in control panels and DC distribution boards while delivering reliable protection and lifecycle cost benefits for panel builders and end users.

Product Information

Extended Description

1SDA123529R1 ABB: XT2S160 DC TMA160 FF 3P
ABB EcoSolutions
Yes
ABB Site Meeting Group Waste To Landfill Target
UL 2799 Zero Waste To Landfill Validation available
End Of Life Disassembling Instructions
Disassembly instructions Tmax XT XT2 TM
Environmental Product Declaration - EPD
EPD Tmax XT XT2 TM (CN)
Recyclability Rate of the Product acc. to EN45555
Design for Closing Resource Loops - Standard EN45555 - 55.7 %
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
Document availability on demand
Customs Tariff Number
85362000
Product Net Width
90 mm
Product Net Height
130 mm
Product Net Depth / Length
82.5 mm
Product Net Weight
1.2 kg
Product Name
Moulded Case Circuit Breaker
Product Type
CB
Version
F
Current Type
DC
Mechanical Durability
25000 cycle | ;240 cycles per hour
Number of Poles
3P
Power Loss
at Rated Operating Conditions per Pole 16.15 W
Rated Current (In)
160 A
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
500 V DC
Rated Service Short-Circuit Breaking Capacity (Ics)
(250 V DC) 2 Poles in Series 50 kA | (500 V DC) 3 Poles in Series 50 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(250 V DC) 2 Poles in Series 50 kA | (500 V DC) 3 Poles in Series 50 kA
Rated Uninterrupted Current (Iu)
160 A
Release
TMA
Release Type
TM
Short-Circuit Performance Level
S
Standards
IEC 60947-2 | GB/T 14028.2
Sub-type
XT2
Terminal Connection Type
Fixed Circuit-Breakers
Declaration of Conformity - CE
EC Declaration of Conformity Tmax XT2
Instructions and Manuals
Installation instructions XT2 DC IEC
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
Feature → Business Impact → Application: 3P DC design provides robust protection for DC power circuits, reducing the risk of cascading faults in critical automation systems; lowers downtime and repair costs in plant environments such as manufacturing lines and data centers. Application in centralized DC distribution cabinets ensures consistent protection for 160 A loads with minimal voltage drop and predictable tripping behavior. Feature → Business Impact → Application: Rated Operational Voltage of 500 V DC and Ui of 1000 V enables safe integration into high-voltage DC bus systems used in automation tiers and battery storage, improving system integrity during transients. Application: DC motor drives, energy storage, and automation cabinets; installation in fixed circuit-breaker configurations supports straightforward panel mounting and serviceability. Feature → Business Impact → Application: Ics and Icu ratings (50 kA in specified configurations) deliver reliable short-circuit performance, decreasing the risk of equipment damage and downtime. Application: Critical protection for PV inverters, DC link buses, and motor control centers. Feature → Business Impact → Application: Mechanical durability of 25,000 cycles and 16.15 W power loss per pole translate to long service life and lower energy waste, supporting total cost of ownership improvements in mission-critical lines. Application: Frequent switching environments, battery-backed systems, and high-cycle DC distribution panels. Feature → Business Impact → Application: Compact dimensions (90 mm x 130 mm x 82.5 mm) and 1.2 kg weight enable easy integration into compact control panels and space-constrained enclosures. Application: Modern industrial cabinets and retrofit projects where space is at a premium. Feature → Business Impact → Application: ABB EcoSolutions alignment, RoHS/REACH declarations, EPD documentation, and EN45555 recyclability guidance support regulatory compliance and sustainability targets for modern factories and green turnkey projects. Application: EPC projects, green data centers, and equipment refurbishments seeking low environmental impact. Feature → Business Impact → Application: End-of-life disassembly instructions and disassembly guidelines facilitate safe retirement of MCCBs, reducing waste handling costs and supporting circular economy goals. Application: Plant upgrading programs and asset retirement planning.

Get a Quick Quote for a ABB 1SDA123529R1

Chat with us on WhatsApp - fast responses guaranteed

Need to speak with someone? We'll call you back within 2 hours during business hours

Interested in ABB 1SDA123529R1? Enquire Now