ABB 1SDA123552R1 Moulded Case Circuit Breaker - IEC 60947-2

Part Number: 1SDA123552R1
Manufacturer
ABB
Part number
1SDA123552R1

Quick Summary

ABB 1SDA123552R1 Moulded Case Circuit Breaker is a DC protective device for power distribution in industrial DC circuits. It helps minimize nuisance trips and simplifies installation while meeting regulatory and safety requirements. Key certifications include IEC 60947-2, GB/T 14028.2, and CE conformity, underscoring global compliance in critical DC applications. Across modern data centers, manufacturing lines, and PV systems, reliable protection translates to reduced downtime and lower operating costs. This DC MCCB also supports front-terminal wiring for faster assembly and improved traceability in panel builds. Its compact 4P design, 16 A rating, and high fault-clearing capacity help design engineers meet space, safety, and reliability targets.

Product Information

Extended Description

1SDA123552R1 ABB: C.BREAKER TMAX XT2L 160 DC FIXED FOUR-POLE WITH FRONT TERMINALS AND THERMOMAGNETIC RELEASE TMD R 16
ABB EcoSolutions
Yes
ABB Site Meeting Group Waste To Landfill Target
UL 2799 Zero Waste To Landfill Validation available
End Of Life Disassembling Instructions
Disassembly instructions Tmax XT XT2 TM
Environmental Product Declaration - EPD
EPD Tmax XT XT2 TM (CN)
Recyclability Rate of the Product acc. to EN45555
Design for Closing Resource Loops - Standard EN45555 - 55.7 %
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
Document availability on demand
Customs Tariff Number
85362000
Product Net Width
120 mm
Product Net Height
130 mm
Product Net Depth / Length
82.5 mm
Product Net Weight
1.6 kg
Product Name
Moulded Case Circuit Breaker
Product Type
CB
Version
F
Current Type
DC
Mechanical Durability
25000 cycle | ;240 cycles per hour
Number of Poles
4P
Power Loss
at Rated Operating Conditions per Pole 1.33 W
Rated Current (In)
16 A
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
500 V DC
Rated Service Short-Circuit Breaking Capacity (Ics)
(250 V DC) 2 Poles in Series 85 kA | (500 V DC) 3 Poles in Series 85 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(250 V DC) 2 Poles in Series 85 kA | (500 V DC) 3 Poles in Series 85 kA
Rated Uninterrupted Current (Iu)
160 A
Release
TMD
Release Type
TM
Short-Circuit Performance Level
L
Standards
IEC 60947-2 | GB/T 14028.2
Sub-type
XT2
Terminal Connection Type
Fixed Circuit-Breakers
Declaration of Conformity - CE
EC Declaration of Conformity Tmax XT2
Instructions and Manuals
Installation instructions XT2 DC IEC
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
Feature: Four-pole fixed circuit-breaker with front terminals and a thermomagnetic release. Business Impact: Enables clean, front-access wiring and reliable fault interruption, reducing panel complexity and maintenance time. Application: Ideal for DC distribution panels and drive systems in industrial installations. Feature: Rated current of 16 A with a 500 V DC operating voltage and 1000 V insulation voltage. Business Impact: Provides robust protection for DC buses and drives while maintaining a healthy safety margin. Application: DC power networks, motor drives, and solar PV inverters requiring solid overcurrent protection. Feature: High short-circuit ratings (I_cs and I_cu up to 85 kA depending on voltage and pole configuration). Business Impact: Improves system resilience against faults, lowering risk of cascading failures and costly downtime. Application: Heavy DC loads, battery storage interfaces, and high-demand DC feeders. Feature: Release type TM with thermomagnetic (TMD) operation and XT2 sub-type. Business Impact: Delivers selective, fast tripping under fault conditions, enhancing equipment protection and reducing arc energy. Application: Drives, motors, and other inductive DC loads in demanding environments. Feature: Mechanical durability rated at 25,000 cycles and front-terminal fixed connections. Business Impact: Extends service life, lowers maintenance frequency, and simplifies installation in retrofit projects. Application: Frequent switching environments and compact panel assemblies in industrial automation. Feature: Compliance and sustainability attributes including IEC 60947-2, RoHS, CE declarations, and a recyclable design profile. Business Impact: Eases global procurement and supports green manufacturing goals. Application: Global delivery to multi-region sites with strict regulatory requirements. This content is crafted with a focus on DC protection, front-terminal MCCB installation, and robust short-circuit performance to support engineers optimizing for reliability, efficiency, and cost of ownership.

Get a Quick Quote for a ABB 1SDA123552R1

Chat with us on WhatsApp - fast responses guaranteed

Need to speak with someone? We'll call you back within 2 hours during business hours

Interested in ABB 1SDA123552R1? Enquire Now

FAQs

Install the four-pole, fixed-connection MCCB with front terminals into the panel per the manufacturer's mounting guidelines. Align with the DC bus, tighten terminals to secure the front-access wiring, and verify the device is properly seated to maintain insulation and clearance. Ensure the rated current (16 A) and voltage (500 V DC) match the circuit being protected and check that the release (TMD) is correctly configured for the load type.
For the ABB 1SDA123552R1, the rated service short-circuit current Ics is up to 85 kA with 250 V DC (2 poles in series) and up to 85 kA with 500 V DC (3 poles in series). The rated ultimate short-circuit current Icu conforms to the same configuration-based values. This ensures robust protection for high fault currents in DC networks.
Yes. The 1SDA123552R1 is designed for DC protection in applications such as PV DC networks and motor drives, offering a 500 V DC operating range and a 16 A rating. Its XT2 family release (TM/TMD) provides reliable tripping, while the front-terminal design supports easy integration into compact PV inverters and drive panels.
This ABB MCCB complies with IEC 60947-2 and GB/T 14028.2, and carries CE declarations of conformity. It also aligns with RoHS requirements and the EN45555 recyclability framework, supporting sustainability goals and regulatory compliance across regions.
The device provides a mechanical durability rating of 25,000 cycles, reducing maintenance interruptions in high-switching environments. Front-terminal fixed connections simplify servicing and replacements, while RoHS and CE compliance minimize regulatory hurdles. Overall, these features translate to lower total cost of ownership and improved uptime for DC power systems.