ABB 1SDA123555R1 Moulded Case Circuit Breaker - IEC 60947-2
Part Number: 1SDA123555R1
Quick Summary
ABB 1SDA123555R1 is a DC moulded case circuit breaker for DC distribution panels. This device provides reliable overload and short-circuit protection in a compact footprint, helping minimize downtime in automation and power control applications. It conforms to IEC 60947-2 with CE declarations and RoHS compliance, supporting global regulatory requirements. Designed to fit Tmax XT2 TM family configurations with front terminals, it offers straightforward installation and predictable lifecycle costs for panel builders and end users.
Product Information
Extended Description
1SDA123555R1 ABB: C.BREAKER TMAX XT2L 160 DC FIXED FOUR-POLE WITH FRONT TERMINALS AND THERMOMAGNETIC RELEASE TMD R 32
ABB EcoSolutions
Yes
ABB Site Meeting Group Waste To Landfill Target
UL 2799 Zero Waste To Landfill Validation available
End Of Life Disassembling Instructions
Disassembly instructions Tmax XT XT2 TM
Environmental Product Declaration - EPD
EPD Tmax XT XT2 TM (CN)
Recyclability Rate of the Product acc. to EN45555
Design for Closing Resource Loops - Standard EN45555 - 55.7 %
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
Document availability on demand
Customs Tariff Number
85362000
Product Net Width
120 mm
Product Net Height
130 mm
Product Net Depth / Length
82.5 mm
Product Net Weight
1.6 kg
Product Name
Moulded Case Circuit Breaker
Product Type
CB
Version
F
Current Type
DC
Mechanical Durability
25000 cycle | ;240 cycles per hour
Number of Poles
4P
Power Loss
at Rated Operating Conditions per Pole 2.57 W
Rated Current (In)
32 A
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
500 V DC
Rated Service Short-Circuit Breaking Capacity (Ics)
(250 V DC) 2 Poles in Series 85 kA | (500 V DC) 3 Poles in Series 85 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(250 V DC) 2 Poles in Series 85 kA | (500 V DC) 3 Poles in Series 85 kA
Rated Uninterrupted Current (Iu)
160 A
Release
TMD
Release Type
TM
Short-Circuit Performance Level
L
Standards
IEC 60947-2 | GB/T 14028.2
Sub-type
XT2
Terminal Connection Type
Fixed Circuit-Breakers
Declaration of Conformity - CE
EC Declaration of Conformity Tmax XT2
Instructions and Manuals
Installation instructions XT2 DC IEC
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
Feature: Four-pole fixed circuit-breaker with front terminals and a TM release provides robust protection for DC circuits while simplifying wiring and field maintenance. Business Impact: Reduces wiring mistakes, speeds assembly, and lowers service costs by enabling front-access testing and quicker replacement. Application: Suitable for DC power distribution in automation cabinets, panel boards, and motor control centers where space is at a premium. Feature: Rated current of 32 A and rated insulation voltage of 1000 V, with a rated operational voltage of 500 V DC. Business Impact: Delivers dependable short-circuit protection for mid-range DC loads while maintaining insulation margins, enabling safer operation and extended component life. Application: DC distribution within control panels and automation racks used in manufacturing facilities. Feature: Short-circuit performance up to 85 kA (Ics/Icu depending on voltage) and a fixed, front-terminal 4P design. Business Impact: Supports high fault withstand capacity, enhancing system reliability and reducing the risk of cascading failures in power distribution. Application: Critical in panels that require rigorous protection for DC feeders serving drives, sensors, and automation equipment. Feature: Low hold power loss of 2.57 W per pole and mechanical durability rated at 25,000 cycles. Business Impact: Reduces energy waste and wear, contributing to lower operating costs and longer device life. Application: Beneficial in high-cycle environments like uptime-critical manufacturing lines and recurring cycling of automation controllers. Feature: Compliance with IEC 60947-2, RoHS, REACH, and available EPD/eco-solutions data plus disassembly instructions. Business Impact: Eases regulatory compliance, sustainability reporting, and end-of-life planning. Application: Suitable for panel builders prioritizing eco-friendly design, responsible sourcing, and transparent product declarations across global supply chains.
Get a Quick Quote for a ABB 1SDA123555R1
Chat with us on WhatsApp - fast responses guaranteed
Need to speak with someone? We'll call you back within 2 hours during business hours
Interested in ABB 1SDA123555R1?
Enquire Now
FAQs
Installation begins with verifying panel space for a four-pole, front-terminal MCCB from the Tmax XT2 family. Align the device in the designated slot, connect the four DC phase conductors to the fixed terminals, and ensure the front-appear access for testing and maintenance. Tighten terminals to the manufacturer’s torque recommendations and verify insulation and clearance per IEC 60947-2 guidelines.
Key ratings include a rated current of 32 A, rated insulation voltage of 1000 V, rated operational voltage of 500 V DC, and a rated impulse withstand voltage of 8 kV. The device is a 4P DC breaker with a mechanical durability of 25,000 cycles and power loss of 2.57 W per pole, suitable for reliable, long-term service in DC systems.
Yes. It is designed for DC distribution within automation cabinets and motor control centers, aligning with IEC 60947-2 standards. It supports Tmax XT2 TM configurations, front-terminal installation, RoHS and REACH compliance, and provides robust overload and short-circuit protection for critical automation panels.
The unit carries IEC 60947-2 compliance with CE declarations and RoHS compliance. ABB also provides environmental documentation such as EPD (where applicable) and disassembly instructions for end-of-life planning, supporting regulatory requirements and sustainable product stewardship.
Lifecycle considerations include a mechanical durability rating of up to 25,000 cycles and front-terminal access for straightforward maintenance. Regular inspection of terminals, torque checks, and quick swaps in case of wear help maintain reliability. The product is designed to ease disassembly and replacement within standard maintenance workflows for industrial power distribution.