ABB 1SDA123559R1 Moulded Case Circuit Breaker - IEC 60947-2

Part Number: 1SDA123559R1
Manufacturer
ABB
Part number
1SDA123559R1

Quick Summary

ABB 1SDA123559R1 is a 4-pole DC molded case circuit breaker for protecting DC power distribution in industrial automation. Engineers often struggle with reliable fault protection in compact switchgear, requiring front-access installation and safe maintenance procedures. This device aligns with IEC 60947-2, CE conformity, and RoHS compliance, while offering an Environmental Product Declaration and recyclability data to support sustainability goals. For retrofit and ongoing uptime, it delivers a compact footprint, robust trip performance, and straightforward integration with ABB EcoSolutions strategies, reducing lifecycle cost and simplifying procurement for panel builders and end users. Its modular design supports standard enclosures and common voltage classes for easy spec alignment.

Product Information

Extended Description

1SDA123559R1 ABB: C.BREAKER TMAX XT2L 160 DC FIXED FOUR-POLE WITH FRONT TERMINALS AND THERMOMAGNETIC RELEASE TMA R 80
ABB EcoSolutions
Yes
ABB Site Meeting Group Waste To Landfill Target
UL 2799 Zero Waste To Landfill Validation available
End Of Life Disassembling Instructions
Disassembly instructions Tmax XT XT2 TM
Environmental Product Declaration - EPD
EPD Tmax XT XT2 TM (CN)
Recyclability Rate of the Product acc. to EN45555
Design for Closing Resource Loops - Standard EN45555 - 55.7 %
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
Document availability on demand
Customs Tariff Number
85362000
Product Net Width
120 mm
Product Net Height
130 mm
Product Net Depth / Length
82.5 mm
Product Net Weight
1.6 kg
Product Name
Moulded Case Circuit Breaker
Product Type
CB
Version
F
Current Type
DC
Mechanical Durability
25000 cycle | ;240 cycles per hour
Number of Poles
4P
Power Loss
at Rated Operating Conditions per Pole 5.8 W
Rated Current (In)
80 A
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
500 V DC
Rated Service Short-Circuit Breaking Capacity (Ics)
(250 V DC) 2 Poles in Series 85 kA | (500 V DC) 3 Poles in Series 85 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(250 V DC) 2 Poles in Series 85 kA | (500 V DC) 3 Poles in Series 85 kA
Rated Uninterrupted Current (Iu)
160 A
Release
TMA
Release Type
TM
Short-Circuit Performance Level
L
Standards
IEC 60947-2 | GB/T 14028.2
Sub-type
XT2
Terminal Connection Type
Fixed Circuit-Breakers
Declaration of Conformity - CE
EC Declaration of Conformity Tmax XT2
Instructions and Manuals
Installation instructions XT2 DC IEC
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
Feature: Front-terminal, fixed circuit-breaker design enables fast wiring and secure mounting, reducing install time and commissioning risk in new builds and retrofits within DC panels. It also simplifies assembly line testing and field verification, delivering higher first-pass acceptance rates in panel builds. This feature accelerates project timelines and reduces labor costs during panel integration. Feature: Four-pole DC protection with TMA release delivers coordinated tripping for balanced DC networks, enabling selective protection for critical loads in automation systems. The TM release supports rapid clear of faults while preserving service continuity for non-fault sections. It also aids coordination with adjacent busbars and protective devices in complex DC architectures. Feature: Electrical performance at 500 V DC and 80 A with 8 kV impulse withstand ensures safe operation under surge events, protecting DC drives and power converters from faults. Rated service short-circuit current of 85 kA in a two- or three-pole series configuration delivers robust protection for high-energy DC rails. Engineers benefit from predictable trip behavior and clear fault delineation during investigations. Feature: Power loss of 5.8 W per pole reduces heat in enclosures, improving thermal margins and reducing cooling load. This translates to lower total cost of ownership and greater reliability in compact cabinets. The design supports modular heat dissipation strategies with standard enclosure depths. Feature: Mechanical durability of up to 25,000 cycles at 240 cycles per hour supports long-life operation in high-use control panels. This durability minimizes maintenance outages and aligns with lean manufacturing maintenance strategies. Field service intervals can be extended due to rugged mechanism and robust contact interfaces. Feature: Sustainability and compliance data include RoHS, REACH declarations, and EN45555 recyclability at 55.7 percent. The ABB EcoSolutions program provides end-of-life guidance, disassembly instructions, and EPD documentation to support circular economy targets, simplifying audits and supplier assessments.

Get a Quick Quote for a ABB 1SDA123559R1

Chat with us on WhatsApp - fast responses guaranteed

Need to speak with someone? We'll call you back within 2 hours during business hours

Interested in ABB 1SDA123559R1? Enquire Now

FAQs

This four-pole DC MCB is ideal for protecting DC power distribution within industrial automation panels. Its front-terminal design and fixed mounting simplify wiring, testing, and commissioning, making it suitable for both new installations and retrofits in demanding DC environments.
The device is compliant with IEC 60947-2 and GB/T 14028.2, with CE conformity and RoHS declarations. It also aligns with sustainability documentation such as EPD data and EN45555 recyclability metrics, supporting corporate compliance and audits.
Key specs include a rated current of 80 A, rated operational voltage of 500 V DC, rated insulation voltage of 1000 V, and an impulse withstand voltage of 8 kV. It supports a 4P configuration with a robust short-circuit rating suitable for DC rails in automation systems.
Front-terminal wiring simplifies field connections, reduces commissioning time, and improves verification accuracy. It also enables easier retrofits in tight panel spaces and enhances serviceability by allowing quick access for inspection and replacement without dismantling the enclosure.
The device offers up to 25,000 mechanical cycles at a duty of 240 cycles per hour, with a power loss of 5.8 W per pole. This combination supports long service life, lower maintenance costs, and higher availability in continuous DC protection applications.