ABB 1SDA123569R1 MCCB - UL 2799 Zero Waste Validation

Part Number: 1SDA123569R1
Manufacturer
ABB
Part number
1SDA123569R1

Quick Summary

ABB 1SDA123569R1 DC MCCB protects DC buses in industrial power distribution. Engineers face downtime from complex, unreliable DC protection; this device simplifies installation and boosts reliability. It aligns with IEC 60947-2, CE conformity, and RoHS, plus ABB EcoSolutions' UL 2799 Zero Waste To Landfill Validation. As a 3P DC MCCB, it enables compact panel designs and predictable maintenance, delivering cost savings and increased uptime across electrical protection & circuit control.

Product Information

Extended Description

1SDA123569R1 ABB: XT2X160 DC TMA63 FF 3P
ABB EcoSolutions
Yes
ABB Site Meeting Group Waste To Landfill Target
UL 2799 Zero Waste To Landfill Validation available
End Of Life Disassembling Instructions
Disassembly instructions Tmax XT XT2 TM
Environmental Product Declaration - EPD
EPD Tmax XT XT2 TM (CN)
Recyclability Rate of the Product acc. to EN45555
Design for Closing Resource Loops - Standard EN45555 - 55.7 %
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
Document availability on demand
Customs Tariff Number
85362000
Product Net Width
90 mm
Product Net Height
130 mm
Product Net Depth / Length
82.5 mm
Product Net Weight
1.2 kg
Product Name
Moulded Case Circuit Breaker
Product Type
CB
Version
F
Current Type
DC
Mechanical Durability
25000 cycle | ;240 cycles per hour
Number of Poles
3P
Power Loss
at Rated Operating Conditions per Pole 4.85 W
Rated Current (In)
63 A
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
500 V DC
Rated Service Short-Circuit Breaking Capacity (Ics)
(250 V DC) 2 Poles in Series 100 kA | (500 V DC) 3 Poles in Series 50 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(250 V DC) 2 Poles in Series 100 kA | (500 V DC) 3 Poles in Series 50 kA
Rated Uninterrupted Current (Iu)
160 A
Release
TMA
Release Type
TM
Short-Circuit Performance Level
X
Standards
IEC 60947-2 | GB/T 14028.2
Sub-type
XT2
Terminal Connection Type
Fixed Circuit-Breakers
Declaration of Conformity - CE
EC Declaration of Conformity Tmax XT2
Instructions and Manuals
Installation instructions XT2 DC IEC
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
Feature → Business Impact → Application: The 3P DC configuration (63 A In) provides robust fault clearance for high-density DC networks, reducing downtime and improving system availability in energy storage, DC drives, and distribution panels. Application notes show faster commissioning and safer startup in battery rooms, telecom DC buses, and 24/7 process lines. Feature → Measurable Outcome → Application: Power loss of 4.85 W per pole lowers heat generation inside enclosures, enhancing cooling efficiency and extending component life in compact switchgear installations. Application: tightly packed control panels where thermal margin is critical. Feature → Compliance & Sustainability → Application: IEC 60947-2, CE, RoHS declarations plus EPD/UL 2799 Zero Waste Validation support regulatory alignment and responsible end-of-life practices, aiding procurement in regulated industries such as manufacturing and utilities. Feature → Durability & Life Cycle → Application: 25,000 mechanical cycles and 240 cycles/hour durability minimize maintenance cycles, lowering total cost of ownership in continuous-operation facilities. Feature → Installation & Compatibility → Application: Fixed terminal connections and 3P design simplify panel integration, enabling straightforward retrofits and compatible mounting with Tmax XT2 series enclosures. Industry context: panel builders gain repeatable assembly time and reduced risk of mis-wiring when upgrading DC protection.

Get a Quick Quote for a ABB 1SDA123569R1

Chat with us on WhatsApp - fast responses guaranteed

Need to speak with someone? We'll call you back within 2 hours during business hours

Interested in ABB 1SDA123569R1? Enquire Now

FAQs

Yes. The 1SDA123569R1 is a fixed-terminal, 3-pole DC Moulded Case Circuit Breaker designed for standard MCCB installations. It fits compact control panels with a 90 mm width, 130 mm height, and 82.5 mm depth, and it's compatible with Tmax XT2 style enclosures. Ensure proper clearance and ventilation per installation instructions.
Key ratings include I_n = 63 A, U_i = 1000 V, U_op = 500 V DC, and a short-circuit breaking capacity of up to 50 kA at 500 V DC (3 poles in series) or 100 kA at 250 V DC (2 poles in series). It also offers a rated service short-circuit capacity (I_cs) and ultimate capacity (I_cu) aligned with IEC 60947-2, ensuring fast fault clearance.
Ideal for energy storage systems, DC drives, telecom DC buses, and industrial power distribution where high-density DC protection is required. The 3P design supports DC distribution on 500 V and 250 V DC rails, delivering reliable protection in battery rooms, renewable energy interfaces, and data-center electrical infrastructures.
The unit complies with IEC 60947-2, carries CE conformity and RoHS declarations, and is supported by ABB EcoSolutions’ UL 2799 Zero Waste To Landfill Validation. Additional environmental considerations include EPD availability and recycling guidance, aligning with sustainability targets and regulatory requirements for responsible sourcing and disposal.
With 25,000 mechanical cycles and 4.85 W per pole power loss, the device offers extended service life and reduced thermal stress, lowering maintenance costs and downtime. Its modular features and clear end-of-life instructions support easier replacements and asset retirement, improving total cost of ownership across DC protection deployments.