ABB 1SDA123599R1 Moulded Case Circuit Breaker - XT4 DC 4P IEC 60947-2

Part Number: 1SDA123599R1
Manufacturer
ABB
Part number
1SDA123599R1

Quick Summary

ABB 1SDA123599R1 Moulded Case Circuit Breaker provides DC-protected power distribution for industrial automation systems. This device is designed to safeguard critical DC buses while minimizing voltage drop and heat generation in demanding environments. Engineers often confront DC protection challenges that demand high fault-current tolerance, compact footprint, and predictable lifecycle costs. The XT4 TM release supports up to 200 A with 750 V DC operation and up to 100 kA service short-circuit capacity, backed by IEC 60947-2 compliance and CE RoHS declarations. With end-of-life disassembly guidance and a clear recyclability path, this solution offers sustainable protection for panel builders, OEMs, and maintenance teams looking to reduce downtime and ensure regulatory compliance across global projects. secondary benefits include EPD data and designed-for-closing-resource-loop considerations that support broader sustainability goals.

Product Information

Extended Description

1SDA123599R1 ABB: XT4X 250 DC TMA200 FF 4P
ABB EcoSolutions
Yes
ABB Site Meeting Group Waste To Landfill Target
UL 2799 Zero Waste To Landfill Validation available
End Of Life Disassembling Instructions
Disassembly instructions Tmax XT XT4 TM
Environmental Product Declaration - EPD
EPD Tmax XT XT4 TM (CN)
Recyclability Rate of the Product acc. to EN45555
Design for Closing Resource Loops - Standard EN45555 - 56.3 %
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
Document availability on demand
Customs Tariff Number
85362000
Product Net Width
140 mm
Product Net Height
160 mm
Product Net Depth / Length
82.5 mm
Product Net Weight
3.5 kg
Product Name
Moulded Case Circuit Breaker
Product Type
CB
Version
F
Current Type
DC
Mechanical Durability
25000 cycle | ;240 cycles per hour
Number of Poles
4P
Power Loss
at Rated Operating Conditions per Pole 11.88 W
Rated Current (In)
200 A
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
750 V DC
Rated Service Short-Circuit Breaking Capacity (Ics)
(250 V DC) 2 Poles in Series 100 kA | (500 V DC) 2 Poles in Series 100 kA | (500 V DC) 3 Poles in Series 100 kA | (750 V DC) 3 Poles in Series 70 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(250 V DC) 2 Poles in Series 100 kA | (500 V DC) 2 Poles in Series 100 kA | (500 V DC) 3 Poles in Series 100 kA | (750 V DC) 3 Poles in Series 70 kA
Rated Uninterrupted Current (Iu)
250 A
Release
TMA
Release Type
TM
Short-Circuit Performance Level
X
Standards
IEC 60947-2 | GB/T 14028.2
Sub-type
XT4
Terminal Connection Type
Fixed Circuit-Breakers
Declaration of Conformity - CE
EC Declaration of Conformity Tmax XT4
Instructions and Manuals
Installation instructions XT4 DC IEC
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
Feature → Business Impact → Application: The 200 A rated current within a 4-pole DC MCCB enables robust protection on common industrial DC feeders, reducing the likelihood of nuisance faults and enabling tighter protection coordination with upstream power supplies and energy storage systems. This translates to fewer unplanned outages and lower maintenance costs in automation panels and battery rooms. Application: DC power distribution in control cabinets, data centers, and renewable energy interfaces where high fault current is possible. Feature → Business Impact → Application: Mechanical durability of 25,000 cycles delivers predictable lifecycle performance in frequent switching environments, reducing replacement cycles and associated downtime. Application: Frequent energization/de-energization scenarios in manufacturing lines and motor control centers. Feature → Business Impact → Application: 11.88 W power loss per pole minimizes heat buildup and energy waste, improving thermal management and reducing cooling requirements in confined switchgear spaces. Application: Tight thermal design in compact switchboards and data-center rack enclosures. Feature → Business Impact → Application: IEC 60947-2 along with GB/T 14028.2 compliance simplifies procurement and cross-border qualification, enabling faster project approvals. Application: Global OEMs and integrators targeting unified standards across regions. Feature → Business Impact → Application: End-of-life disassembly instructions and EPD support responsible recycling, lowering total cost of ownership and aligning with corporate sustainability programs. Application: Greenfield and retrofit projects pursuing landfill reduction targets. Feature → Business Impact → Application: Fixed terminal connection type provides straightforward installation and reliable conductivity, reducing commissioning time and field wiring errors. Application: Panel assembly in electrical rooms and control panels where secure, permanent terminations are required.

Get a Quick Quote for a ABB 1SDA123599R1

Chat with us on WhatsApp - fast responses guaranteed

Need to speak with someone? We'll call you back within 2 hours during business hours

Interested in ABB 1SDA123599R1? Enquire Now