ABB 1SDA123633R1 Moulded Case Circuit Breaker - 8 kV

Part Number: 1SDA123633R1
Manufacturer
ABB
Part number
1SDA123633R1

Quick Summary

1SDA123633R1 is a DC Moulded Case Circuit Breaker designed for reliable protection in 750 V DC power distributions. This ABB device helps protect critical DC buses in industrial control, data centers, and automated facilities by rapidly interrupting fault currents while minimizing downtime. Engineers face uptime and safety challenges in high-energy DC networks, making a robust MCCB essential. With IEC 60947-2 conformity and CE declarations, plus RoHS and REACH compliance, the XT6 family aligns with ABB EcoSolutions for greener end-of-life outcomes. The combination of a 630 A nominal rating and 800 A uninterrupted service delivers operational resilience, while 8 kV impulse withstand supports harsh electrical environments. These features translate into lower total cost of ownership and improved system reliability for your DC protection strategy.

Product Information

Extended Description

1SDA123633R1 ABB: XT6N 800 DC TMA630 FF 3P
ABB EcoSolutions
Yes
ABB Site Meeting Group Waste To Landfill Target
UL 2799 Zero Waste To Landfill Validation available
End Of Life Disassembling Instructions
Disassembly instructions Tmax XT XT6 TM
Environmental Product Declaration - EPD
EPD Tmax XT XT6 TM (CN)
Recyclability Rate of the Product acc. to EN45555
Design for Closing Resource Loops - Standard EN45555 - 60 %
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
Document availability on demand
Environmental Information
Breakers - Packaging disposal information
Customs Tariff Number
85362000
Product Net Width
210 mm
Product Net Height
268 mm
Product Net Depth / Length
103.5 mm
Product Net Weight
9.5 kg
Product Name
Moulded Case Circuit Breaker
Product Type
CB
Version
F
Current Type
DC
Mechanical Durability
20000 cycle | ;120 cycles per hour
Number of Poles
3P
Power Loss
at Rated Operating Conditions per Pole 34.4 W
Rated Current (In)
630 A
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
750 V DC
Rated Service Short-Circuit Breaking Capacity (Ics)
(250 V DC) 2 Poles in Series 25 kA | (500 V DC) 2 Poles in Series 18 kA | (750 V DC) 3 Poles in Series 12.5 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(250 V DC) 2 Poles in Series 50 kA | (500 V DC) 2 Poles in Series 36 kA | (750 V DC) 3 Poles in Series 25 kA
Rated Uninterrupted Current (Iu)
800 A
Release
TMA
Release Type
TM
Short-Circuit Performance Level
N
Standards
IEC 60947-2 | GB/T 14028.2
Sub-type
XT6
Terminal Connection Type
Fixed Circuit-Breakers
Declaration of Conformity - CE
EC Declaration of Conformity Tmax XT6
Instructions and Manuals
Installation instructions XT6 DC IEC
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
Feature → Business Impact → Application: 630 A rated current and 3P configuration provide strong bus protection for medium- to high-load DC networks, reducing fault impact and enabling quick isolation in industrial power distribution. This supports higher line uptime and safer operation in automation cell banks, machinery, and DC distribution panels. Feature → Business Impact → Application: 800 A uninterrupted current rating ensures continuous protection under heavy DC load conditions, enabling data centers and manufacturing lines to sustain critical processes even during brief overload events. Feature → Business Impact → Application: 750 V DC rated operational voltage with 1000 V insulation voltage expands safe integration in high-energy applications, allowing tighter enclosure design and improved clearance margins in compact switchgear. Feature → Business Impact → Application: 8 kV rated impulse withstand voltage (Uimp) plus IEC 60947-2 compliance provides robust protection against transient surges, supporting telecom and industry 4.0 power rails with reduced risk of nuisance trips. Feature → Business Impact → Application: Fixed circuit-breaker terminal connection simplifies installation and service in standard enclosures, enabling faster commissioning and easier retrofits in control cabinets and MCCs. Feature → Business Impact → Application: 34.4 W per pole power loss under rated conditions improves energy efficiency in continuous-duty DC systems, lowering heat load and cooling requirements in high-density switchgear. Feature → Business Impact → Application: 20000 mechanical cycles and a 3P XT6 sub-type deliver reliable long-term operation in demanding environments, reducing maintenance frequency and extending service life across production lines. Feature → Business Impact → Application: Environmentally aware packaging, 60% recyclability target per EN45555, and EPD/REACH/RoHS declarations simplify compliance and enable greener lifecycle management for ABB EcoSolutions projects. This combination of protection, efficiency, and sustainability is particularly suited for data centers, electric traction, and industrial automation where reliability and regulatory alignment are non-negotiable.

Get a Quick Quote for a ABB 1SDA123633R1

Chat with us on WhatsApp - fast responses guaranteed

Need to speak with someone? We'll call you back within 2 hours during business hours

Interested in ABB 1SDA123633R1? Enquire Now