ABB 1SDA123635R1 Moulded Case Circuit Breaker - IEC 60947-2
Part Number: 1SDA123635R1
Quick Summary
ABB 1SDA123635R1 is a DC moulded case circuit breaker designed to protect critical power distribution in industrial automation. It supports up to 800 A and 750 V DC, delivering reliable short-circuit protection for harsh manufacturing, data centers, and process lines. The device addresses common pain points such as nuisance tripping, maintenance downtime, and unsafe live-switch operations by combining precise release logic with a robust Tmax XT6 TM mechanism. It carries IEC 60947-2 and CE conformity, along with RoHS and REACH compliance, aligning with global sustainability and regulatory requirements. By integrating with ABB EcoSolutions, this module helps optimize lifecycle costs, simplify end-of-life management, and improve overall grid reliability in DC networks.
Product Information
Extended Description
1SDA123635R1 ABB: XT6N 800 DC TMA800 FF 3P
ABB EcoSolutions
Yes
ABB Site Meeting Group Waste To Landfill Target
UL 2799 Zero Waste To Landfill Validation available
End Of Life Disassembling Instructions
Disassembly instructions Tmax XT XT6 TM
Environmental Product Declaration - EPD
EPD Tmax XT XT6 TM (CN)
Recyclability Rate of the Product acc. to EN45555
Design for Closing Resource Loops - Standard EN45555 - 60 %
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
Document availability on demand
Environmental Information
Breakers - Packaging disposal information
Customs Tariff Number
85362000
Product Net Width
210 mm
Product Net Height
268 mm
Product Net Depth / Length
103.5 mm
Product Net Weight
9.5 kg
Product Name
Moulded Case Circuit Breaker
Product Type
CB
Version
F
Current Type
DC
Mechanical Durability
20000 cycle | ;120 cycles per hour
Number of Poles
3P
Power Loss
at Rated Operating Conditions per Pole 54.2 W
Rated Current (In)
800 A
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
750 V DC
Rated Service Short-Circuit Breaking Capacity (Ics)
(250 V DC) 2 Poles in Series 25 kA | (500 V DC) 2 Poles in Series 18 kA | (750 V DC) 3 Poles in Series 12.5 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(250 V DC) 2 Poles in Series 50 kA | (500 V DC) 2 Poles in Series 36 kA | (750 V DC) 3 Poles in Series 25 kA
Rated Uninterrupted Current (Iu)
800 A
Release
TMA
Release Type
TM
Short-Circuit Performance Level
N
Standards
IEC 60947-2 | GB/T 14028.2
Sub-type
XT6
Terminal Connection Type
Fixed Circuit-Breakers
Declaration of Conformity - CE
EC Declaration of Conformity Tmax XT6
Instructions and Manuals
Installation instructions XT6 DC IEC
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
Feature: 3P fixed circuit-breaker architecture with 800 A rating. Business impact: robust three-phase DC protection reduces fault propagation and simplifies panel design. Application: heavy DC distribution in manufacturing lines and data centers. Feature: Tmax XT6 TM release (TMA) for precise, fast protection. Business impact: minimizes downtime and improves safety during fault events. Application: critical power rails and motor drives in industrial automation. Feature: IEC 60947-2 and CE conformity with RoHS/REACH. Business impact: ensures regulatory compliance and sustainability across global sites. Application: new builds and retrofits requiring standards alignment. Feature: End-of-life and recycling guidance (60% recyclability per EN45555). Business impact: supports sustainability targets and responsible disposal. Application: long-term environmental program and supplier audits. Feature: Disassembly instructions provided for maintenance and disposal. Business impact: reduces service time and improves green-field or brown-field upgrade efficiency. Application: field service, retrofits, and end-of-life planning. Feature: Dimensions and weight (210 mm width, 268 mm height, 103.5 mm depth; 9.5 kg). Business impact: clear footprint planning and straightforward mounting. Application: panel design and enclosure sizing for DC systems. Feature: 54.2 W power loss per pole. Business impact: accurate thermal management planning and energy efficiency improvements. Application: heat management in dense DC panels and racks.
Get a Quick Quote for a ABB 1SDA123635R1
Chat with us on WhatsApp - fast responses guaranteed
Need to speak with someone? We'll call you back within 2 hours during business hours
Interested in ABB 1SDA123635R1?
Enquire Now