ABB 1SDA127161R1 Moulded Case Circuit Breaker - IEC 60947-2

Part Number: 1SDA127161R1
Manufacturer
ABB
Part number
1SDA127161R1

Quick Summary

ABB 1SDA127161R1 is a DC 3-pole molded case circuit breaker for DC power distribution in industrial automation systems. Many engineers struggle with selecting protectors that tolerate continuous DC operation while delivering fast, predictable trip performance. It complies with IEC 60947-2 and GB/T 14028.2, and carries CE conformity along with RoHS/REACH environmental compliance, supporting global safety and sustainability targets. Designed for reliable DC protection in switchgear and control panels, it helps reduce downtime and streamline procurement across global projects.

Product Information

Extended Description

1SDA127161R1 ABB: XT4S DC 160 TMD125 FF 3P
ABB EcoSolutions
Yes
ABB Site Meeting Group Waste To Landfill Target
UL 2799 Zero Waste To Landfill Validation available
End Of Life Disassembling Instructions
Disassembly instructions Tmax XT XT4 TM
Environmental Product Declaration - EPD
EPD Tmax XT XT4 TM (CN)
Recyclability Rate of the Product acc. to EN45555
Design for Closing Resource Loops - Standard EN45555 - 56.3 %
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
Document availability on demand
Customs Tariff Number
85362000
Product Net Width
105 mm
Product Net Height
160 mm
Product Net Depth / Length
82.5 mm
Product Net Weight
2.5 kg
Product Name
Moulded Case Circuit Breaker
Product Type
CB
Version
F
Current Type
DC
Mechanical Durability
25000 cycle | 240 cycles per hour
Number of Poles
3P
Power Loss
at Rated Operating Conditions per Pole 7.40 W
Rated Current (In)
125 A
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
750 V DC
Rated Service Short-Circuit Breaking Capacity (Ics)
(250 V DC) 2 Poles in Series 50 kA | (500 V DC) 2 Poles in Series 50 kA | (500 V DC) 3 Poles in Series 50 kA | (750 V DC) 3 Poles in Series 36 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(250 V DC) 2 Poles in Series 50 kA | (500 V DC) 2 Poles in Series 50 kA | (500 V DC) 3 Poles in Series 50 kA | (750 V DC) 3 Poles in Series 36 kA
Rated Uninterrupted Current (Iu)
250 A
Release
TMD
Release Type
TM
Short-Circuit Performance Level
S
Standards
IEC 60947-2 | GB/T 14028.2
Sub-type
XT4
Terminal Connection Type
Fixed Circuit-Breakers
Declaration of Conformity - CE
EC Declaration of Conformity Tmax XT4
Instructions and Manuals
Installation instructions XT4 DC IEC
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
Feature → Business Impact → Application: The 3P configuration, rated 125 A, and DC operation target high-current DC distribution with stable trip characteristics, reducing nuisance trips and improving line reliability in control panels. This translates to fewer production interruptions and lower maintenance costs for conveyor and machine-line systems. The XT4 TM release (TMD/TM) provides rapid, predictable protection against short circuits, enabling safe startup sequences in automated equipment and data-center rack power distributions. With an insulation rating of 1000 V and 750 V DC nominal, it supports high-voltage DC bus protection in renewable energy inverters and motor drives, while the 8 kV impulse withstand enhances surge resilience in demanding factory environments. The device’s fixed terminal connections simplify installation and reduce commissioning time during panel assembly, improving overall project timelines. Energy loss is minimized at 7.40 W per pole, contributing to cooler, more efficient power distribution boards in compact control enclosures. The product is aligned with ABB EcoSolutions, End Of Life disassembly instructions, and a measurable recyclability rate (56.3% per EN45555), supporting sustainability-driven procurement. RoHS/REACH compliance and CMRT readiness offer compliance confidence for global customers, while the low weight of 2.5 kg eases handling during installation and retrofits in existing panels. Compatibility with XT4 DC IEC installation instructions ensures a familiar, streamlined mounting process for engineers upgrading legacy CBs.

Get a Quick Quote for a ABB 1SDA127161R1

Chat with us on WhatsApp - fast responses guaranteed

Need to speak with someone? We'll call you back within 2 hours during business hours

Interested in ABB 1SDA127161R1? Enquire Now

FAQs

Yes. The 1SDA127161R1 is a fixed-terminal, 3P MCCB in the XT4 family designed for DC protection. It pairs with standard XT4 DC installation instructions and fixed circuit-breaker terminals, enabling straightforward retrofits and seamless integration into ABB-based switchgear and control panels.
Key ratings include In of 125 A, Ui of 1000 V, Uimp of 8 kV, and Ics/Icu depending on voltage and pole configuration (up to 50 kA). It operates at up to 750 V DC, with a rated service short-circuit capacity suitable for DC protection in industrial environments.
Yes. With DC operation, XT4, and 3P configuration, it suits DC distribution in motor drives, control panels, and renewable energy interfaces. The 125 A rating, 750 V DC rating, and high short-circuit withstand capability support reliable protection for DC buses in industrial automation and energy systems.
The device adheres to IEC 60947-2 and GB/T 14028.2, with CE Declaration of Conformity and RoHS/REACH compliance. Environmental data include EPD (CN) for Tmax XT XT4 TM, and a recyclability rate per EN45555, supporting regulatory and sustainability requirements.
The unit provides long mechanical durability (up to 25,000 cycles at 240 cycles/hour), predictable trip performance, and clear disassembly guidance for end-of-life handling. With low energy loss (7.40 W per pole) and standardized installation, it reduces downtime and maintenance costs while improving total cost of ownership across panel upgrades.