ABB AF116-30-00B-11 Block Contactor - UL/CSA Listed
Part Number: 1SFL427002R1100
Quick Summary
Block Contactor AF116-30-00B-11 by ABB provides robust motor control for 3-phase drives in industrial equipment. Design teams often battle voltage swings that cause nuisance trips and energy waste in control panels. This device carries CE Declaration of Conformity, UKCA marking, and UL/CSA listings for global compliance. The AF technology delivers a wide coil tolerance (24-60 V AC or 20-60 V DC) and built-in surge protection, reducing panel energy use and improving reliability in unstable networks. With three main contacts and a 160 A rating at 690 V, it's compact and extensible with add-on auxiliary blocks, delivering lower total cost of ownership for motor control applications.
Product Information
Extended Description
1SFL427002R1100 ABB: The AF116-30-00B-11 is a 3 pole - 690 V IEC or 600 V UL contactor with Main Circuit Bars, controlling motors up to 55 kW / 400 V AC (AC-3) or 75 hp / 480 V UL and switching power circuits up to 160 A (AC-1) or 160 A UL general use. Thanks to the AF technology, the contactor has a wide control voltage range (24-60 V 50/60 Hz and 20-60 V DC), managing large control voltage variations, reducing panel energy consumptions and ensuring distinct operations in unstable networks. Furthermore, surge protection is built-in, offering a compact solution. AF contactors have a block type design, can be easily extended with add-on auxiliary contact blocks and an additional wide range of accessories.
Minimum Order Quantity
1 piece
Customs Tariff Number
85364900
Data Sheet, Technical Information
1SBC100214C0202 - Main catalog Motor protection and control Manual motor starters, contactors and overload relays (PDF) - Edition 2024
Data Sheet, Technical Information (Part 2)
Contactors and Overload relays guide
Instructions and Manuals
Operating instruction, Contactor, AF(S)116, AF140, AF(S)146
CAD Dimensional Drawing
Information - 2D and 3D files for CAD systems
Dimension Diagram
1SFB535001G1051
Product Net Width
90 mm
Product Net Depth / Length
126 mm
Product Net Height
150 mm
Product Net Weight
1.3 kg
Number of Main Contacts NO
3
Number of Main Contacts NC
0
Number of Auxiliary Contacts NO
0
Number of Auxiliary Contacts NC
0
Number of Poles
3P
Rated Operational Voltage
Main Circuit 690 V
Rated Frequency (f)
Main Circuit 50 / 60 Hz
Conventional Free-air Thermal Current (Ith)
acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 160 A
Rated Operational Current AC-1 (Ie)
(690 V) 40 °C 160 A | (690 V) 60 °C 145 A | (690 V) 70 °C 130 A
Rated Operational Current AC-3 (Ie)
(415 V) 55 °C 116 A | (440 V) 55 °C 116 A | (500 V) 55 °C 110 A | (690 V) 55 °C 65 A | (380 / 400 V) 55 °C 116 A | (220 / 230 / 240 V) 55 °C 116 A
Rated Operational Current AC-3e (Ie)
(415 V) 60 °C 116 A | (440 V) 60 °C 116 A | (500 V) 60 °C 110 A | (690 V) 60 °C 65 A | (380 / 400 V) 60 °C 116 A | (220 / 230 / 240 V) 60 °C 116 A
Rated Operational Current DC-1 (Ie)
(110 V) 2 Poles in Series, 40 °C 145 A | (220 V) 3 Poles in Series, 40 °C 145 A
Rated Operational Current DC-3 (Ie)
(110 V) 2 Poles in Series, 40 °C 145 A | (220 V) 3 Poles in Series, 40 °C 145 A
Rated Operational Current DC-5 (Ie)
(110 V) 2 Poles in Series, 40 °C 145 A | (220 V) 3 Poles in Series, 40 °C 145 A
Rated Operational Power AC-3 (Pe)
(415 V) 55 kW | (440 V) 75 kW | (500 V) 75 kW | (690 V) 55 kW | (380 / 400 V) 55 kW | (220 / 230 / 240 V) 30 kW
Rated Operational Power AC-3e (Pe)
(415 V) 55 kW | (440 V) 75 kW | (500 V) 75 kW | (690 V) 55 kW | (380 / 400 V) 55 kW | (220 / 230 / 240 V) 30 kW
Rated Breaking Capacity AC-3
8 x Ie AC-3
Rated Breaking Capacity AC-3e
8.5 x Ie AC-3e
Rated Making Capacity AC-3
10 x Ie AC-3
Rated Making Capacity AC-3e
12 x Ie AC-3e
Short-Circuit Protective Devices
gG Type Fuses 250 A
Rated Short-time Withstand Current Low Voltage (Icw)
at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 928 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 160 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 379 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 1160 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 536 A
Maximum Breaking Capacity
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 2000 A | cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 1000 A
Rated Insulation Voltage (Ui)
acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 1000 V | acc. to UL/CSA 600 V
Rated Impulse Withstand Voltage (Uimp)
Main Circuit 8 kV
Maximum Electrical Switching Frequency
(AC-1) 300 cycles per hour | (AC-2 / AC-4) 150 cycles per hour | (AC-3) 300 cycles per hour
Mechanical Durability
5 million
Maximum Mechanical Switching Frequency
300 cycles per hour
Coil Operating Limits
(acc. to IEC 60947-4-1) 0.85 x Uc Min. ... 1.1 x Uc Max. (at θ ≤ 70 °C)
Rated Control Circuit Voltage (Uc)
50 Hz 24 ... 60 V | 60 Hz 24 ... 60 V | DC Operation 20 ... 60 V
Coil Consumption
Holding at Max. Rated Control Circuit Voltage 50 Hz 5.5 V·A | Holding at Max. Rated Control Circuit Voltage 60 Hz 5.5 V·A | Holding at Max. Rated Control Circuit Voltage DC 2.5 W | Pull-in at Max. Rated Control Circuit Voltage 50 Hz 225 V·A | Pull-in at Max. Rated Control Circuit Voltage 60 Hz 225 V·A | Pull-in at Max. Rated Control Circuit Voltage DC 210 W
Power Loss
at Rated Operating Conditions per Pole 6 W
Operate Time
Between Coil De-energization and NO Contact Opening 37 ... 47 ms | Between Coil Energization and NO Contact Closing 25 ... 55 ms
Connecting Capacity Main Circuit
Flexible 2 x 10 ... 70 mm² | Rigid Cu-Cable 2 x 10 ... 95 mm²
Connecting Capacity Auxiliary Circuit
Flexible with Ferrule 1x 0.75 ... 2.5 mm² | Flexible with Insulated Ferrule 2x 0.75 ... 2.5 mm² | Flexible 2x0.75 ... 2.5 mm² | Solid 2 x 1 ... 4 mm² | Stranded 1 x 1 .... 4 mm²
Connecting Capacity
Flexible 2 x 10 ... 70 mm² | Rigid Cu-Cable 2 x 10 ... 95 mm²
Degree of Protection
acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20 | acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP00
Tightening Torque
Cable Lug 9 N·m | Main Circuit 8 N·m
Terminal Type
Main Circuit: Bars
Product Name
Block Contactor
Maximum Operating Voltage UL/CSA
Main Circuit 600 V
General Use Rating UL/CSA
(600 V AC) 160 A
Horsepower Rating UL/CSA
(200 V AC) Three Phase 30 hp | (208 V AC) Three Phase 30 hp | (220 ... 240 V AC) Three Phase 40 hp | (440 ... 480 V AC) Three Phase 75 hp | (550 ... 600 V AC) Three Phase 100 hp
Full Load Amps Motor Use
(440 ... 480 V AC) Three Phase 96 A | (550 ... 600 V AC) Three Phase 99 A
Ambient Air Temperature
Close to Contactor Fitted with Thermal O/L Relay (0.85 ... 1.1 Uc) -25 ... 50 °C | Close to Contactor without Thermal O/L Relay (0.85 ... 1.1 Uc) -40 ... 70 °C | Close to Contactor for Storage -40 ... 70 °C
Maximum Operating Altitude Permissible
Without Derating 3000 m
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
REACH Declaration
REACH - Letter of Confirmation for block contactors, contactor relays, installation contactors, mini contactors, mini contactor relays, thermal overload relays, electronic overload relays and related accessories
RoHS Information
RoHS II declaration for block contactors, installation contactors, mini contactors, mini contactor relays, thermal overload relays, electronic overload relays and related accessories
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration for Contactors
WEEE B2C / B2B
Business To Business
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
ABB EcoSolutions
Yes
ABB Site Meeting Group Waste To Landfill Target
Non-hazardous waste is sent to a landfill, where there is no alternative option available within 100km of a facility
End Of Life Disassembling Instructions
End-of-life instruction - AF(S)116(B)-**(RT) to AF(S)205(B)-**(RT)
Environmental Product Declaration - EPD
Environmental Product Declaration, AF(S)116-AF(S)146 (SE) Contactors
Improved Energy Efficiency for Customers
Product Efficiency - Product requires less energy to operate compared to similar product on market or older products from the same line
Recyclability Rate of the Product acc. to EN45555
Design for Closing Resource Loops - Standard EN45555 - 87.8 %
Sustainable Material Content in Product (wt. %)
Recycled Metal - 37 %
A2L Certificate – UL
UL Certificate of Compliance A2L, Contactor, AF116 - AF146
ABS Certificate
ABS Approval, Contactor, AF116 ... AF370 (Sweden)
BV Certificate
BV Certificate, Contactor, AF116-30 ... AF370-30...AF116-40...AF370-40
CB Certificate
SEMKO_SE-70479M1
CCS Certificate
CCS Certificate, Contactor, AF116 to AF2850 (Sweden)
CQC Certificate
CQC Certificate, AC Contactor, AF116-*-*-*, AF140-*-*-*, AF146-*-*-*, AF116B-*-*-*, AF140B-*-*-*, AF146B-*-*-*, AFS116-30-*-*,AFS140-30-*-*, AFS146-30-*-*, Made in Sweden
Declaration of Conformity - CCC
CCC Declaration of Conformity, AC Contactor, AF116-*-*-*, AF140-*-*-*, AF146-*-*-*, AF116B-*-*-*, AF140B-*-*-*, AF146B-*-*-*, AFS116-30-*-*,AFS140-30-*-*, AFS146-30-*-*, Made in Sweden
Declaration of Conformity - CE
CE Declaration of Conformity - Contactor - AF116...AF370
Declaration of Conformity - UKCA
UK Declaration of Conformity - Contactors >100A
DNV Certificate
DNV-certificate, Contactors, AF116-30...AF370-30 and AF116-40...AF370-40
EAC Certificate
9AKK107046A8618
LR Certificate
Lloyds register Certificate, Contactor, AF116-30 ... AF370-30, AF116-40...AF370-40
PRS Certificate
PRS Certificate - AF116...AF1650
RINA Certificate
RINA Certificate, AF95, AF110, AF145, AF185, AF210, AF260, AF300, AF400, AF460, AF580, AF750, AF1250, AF1350, AF1650, AF2050, AF2650, AF116, AF140, AF146, AF190, AF205, AF265, AF305, AF370
RMRS Certificate
9AKK107045A6978
UL Certificate
cULus Certificate, Contactor, AF116-30...AF146-30, AFS116-30...AFS146-30
UL Listing Card
UL_E36588
Package Level 1 Units
box 1 piece
Package Level 1 Width
207 mm
Package Level 1 Depth / Length
216 mm
Package Level 1 Height
150 mm
Package Level 1 Gross Weight
1.5 kg
Package Level 1 EAN
7320500476499
Object Classification Code
Q
ETIM 7
EC000066 - Power contactor, AC switching
ETIM 8
EC000066 - Power contactor, AC switching
ETIM 9
EC000066 - Power contactor, AC switching
eClass
V11.0 : 27371003
UNSPSC
39121529
IDEA Granular Category Code (IGCC)
4758 >> Iec Contactors
E-Number (Finland)
3706173
AF technology provides a wide coil voltage range and surge protection, reducing panel energy consumption and nuisance trips in unstable networks. This translates to lower operating costs and higher reliability for critical machinery. The 3-pole main contactor handles motors up to 55 kW at 400 V AC (AC-3) or 75 hp at UL ratings, with AC-1 currents up to 160 A, offering flexible design for varied loads. The block-type design enables simple expansion with auxiliary contact blocks, streamlining future automation upgrades without replacing the base unit. Main circuit bars and IP00 termination simplify installation and improve electrical safety in panel cabinets. Compliance with CE, UKCA, and UL/CSA standards, plus RoHS and REACH declarations, supports regulatory and sustainability goals. This combination delivers lower lifecycle costs and easier maintenance for motor control installations.
Get a Quick Quote for a ABB 1SFL427002R1100
Chat with us on WhatsApp - fast responses guaranteed
Need to speak with someone? We'll call you back within 2 hours during business hours
Interested in ABB 1SFL427002R1100?
Enquire Now
FAQs
Install as a 3-pole block contactor using the main circuit bars with rated connections of 2 x 10 ... 70 mm² for flexible use. Connect the coil to 24–60 V AC or 20–60 V DC, secure coil terminals IP20, and torque main circuits to 8 N·m while ensuring safe clearance and proper ventilation.
Rated Operational Current AC-3 at 415 V is 116 A (55 °C) and at 440 V, 116 A; at 690 V, 65 A (55 °C). AC-1 ratings are 160 A at 690 V (60 °C) and 145 A at 690 V (70 °C), with 160 A at 40 °C open-circuit condition.
Yes. It supports multiple voltage families: AC-3 power switching up to 75 kW at 440–500 V and 55 kW at 690 V, with corresponding AC-1 currents around 145–160 A depending on ambient temperature and voltage class.
CE Declaration of Conformity, UKCA marking, and UL/CSA listings. Additional RoHS and REACH declarations, EPD documentation, and certificates from BV, LR, DNV, and RINA support global regulatory and sustainability requirements.
AF technology provides wide coil tolerance and built-in surge protection, reducing nuisance trips and panel energy use. Mechanical durability is rated at around 5 million cycles, and the unit supports easy expansion with auxiliary blocks, lowering downtime and maintenance costs over the life of the installation.