The 1SFL427002R3300 ABB Block Contactor is a 3-pole motor starter designed for 690 V IEC and 600 V UL applications, capable of controlling motors up to 55 kW at 400 V AC (AC-3) or 75 hp at 480 V UL. In panel design, engineers often battle control voltage fluctuations that impact reliability; this device mitigates that with a wide control voltage range and robust surge protection. It leverages ABB AF technology to tolerate voltage variation and maintain distinct operation even in unstable networks. Certifications such as CE and UL/CSA support global compliance, while UKCA and other declarations reinforce market readiness. Together with AF technology and modular accessories, this solution adds efficiency, reduces wiring complexity, and supports scalable automation deployments.

Product Information

Extended Description

1SFL427002R3300 ABB: The AF116-30-00B-33 is a 3 pole - 690 V IEC or 600 V UL contactor with Main Circuit Bars, controlling motors up to 55 kW / 400 V AC (AC-3) or 75 hp / 480 V UL and switching power circuits up to 160 A (AC-1) or 160 A UL general use. Thanks to the AF technology, the contactor has a wide control voltage range (100-250 V 50/60 Hz and DC), managing large control voltage variations, reducing panel energy consumptions and ensuring distinct operations in unstable networks. Furthermore, surge protection is built-in, offering a compact solution. AF contactors have a block type design, can be easily extended with add-on auxiliary contact blocks and an additional wide range of accessories.
Minimum Order Quantity
1 piece
Customs Tariff Number
85364900
Data Sheet, Technical Information
1SBC100214C0202 - Main catalog Motor protection and control Manual motor starters, contactors and overload relays (PDF) - Edition 2024
Data Sheet, Technical Information (Part 2)
Contactors and Overload relays guide
Instructions and Manuals
Operating instruction, Contactor, AF(S)116, AF140, AF(S)146
CAD Dimensional Drawing
Information - 2D and 3D files for CAD systems
Product Net Width
90 mm
Product Net Depth / Length
142.5 mm
Product Net Height
150 mm
Product Net Weight
1.3 kg
Number of Main Contacts NO
3
Number of Main Contacts NC
0
Number of Auxiliary Contacts NO
0
Number of Auxiliary Contacts NC
0
Number of Poles
3P
Rated Operational Voltage
Main Circuit 690 V
Rated Frequency (f)
Main Circuit 60 Hz
Conventional Free-air Thermal Current (Ith)
acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 160 A
Rated Operational Current AC-1 (Ie)
(690 V) 40 °C 160 A | (690 V) 60 °C 145 A | (690 V) 70 °C 130 A
Rated Operational Current AC-3 (Ie)
(415 V) 55 °C 116 A | (440 V) 55 °C 116 A | (500 V) 55 °C 110 A | (690 V) 55 °C 65 A | (380 / 400 V) 55 °C 116 A | (220 / 230 / 240 V) 55 °C 116 A
Rated Operational Current AC-3e (Ie)
(415 V) 60 °C 116 A | (440 V) 60 °C 116 A | (500 V) 60 °C 110 A | (690 V) 60 °C 65 A | (380 / 400 V) 60 °C 116 A | (220 / 230 / 240 V) 60 °C 116 A
Rated Operational Power AC-3 (Pe)
(415 V) 55 kW | (440 V) 75 kW | (500 V) 75 kW | (690 V) 55 kW | (380 / 400 V) 55 kW | (220 / 230 / 240 V) 30 kW
Rated Operational Power AC-3e (Pe)
(415 V) 55 kW | (440 V) 75 kW | (500 V) 75 kW | (690 V) 55 kW | (380 / 400 V) 55 kW | (220 / 230 / 240 V) 30 kW
Rated Breaking Capacity AC-3
8 x Ie AC-3
Rated Breaking Capacity AC-3e
8.5 x Ie AC-3e
Rated Making Capacity AC-3
10 x Ie AC-3
Rated Making Capacity AC-3e
12 x Ie AC-3e
Short-Circuit Protective Devices
gG Type Fuses 250 A
Rated Short-time Withstand Current Low Voltage (Icw)
at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 928 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 160 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 379 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 1160 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 536 A
Rated Insulation Voltage (Ui)
acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 1000 V | acc. to UL/CSA 600 V
Rated Impulse Withstand Voltage (Uimp)
8 kV
Maximum Electrical Switching Frequency
(AC-1) 300 cycles per hour | (AC-2 / AC-4) 150 cycles per hour | (AC-3) 300 cycles per hour
Mechanical Durability
5 million
Maximum Mechanical Switching Frequency
300 cycles per hour
Coil Operating Limits
(acc. to IEC 60947-4-1) Uc (at θ ≤ 70 °C)
Rated Control Circuit Voltage (Uc)
50 Hz 100 ... 250 V | 60 Hz 100 ... 250 V | DC Operation 100 ... 250 V
Coil Consumption
Holding at Max. Rated Control Circuit Voltage 50 Hz 6 V·A | Holding at Max. Rated Control Circuit Voltage 60 Hz 6 V·A | Pull-in at Max. Rated Control Circuit Voltage 50 Hz 130 V·A | Pull-in at Max. Rated Control Circuit Voltage 60 Hz 130 V·A | Pull-in at Max. Rated Control Circuit Voltage DC 135 W
Power Loss
at Rated Operating Conditions per Pole 6 W
Operate Time
Between Coil De-energization and NO Contact Opening 37 ... 47 ms | Between Coil Energization and NO Contact Closing 25 ... 55 ms
Degree of Protection
acc. to IEC 60529, IEC 60947-1, EN 60529 Auxiliary Terminals IP40
Terminal Type
Main Circuit: Bars
Product Name
Block Contactor
General Use Rating UL/CSA
(600 V AC) 160 A
Horsepower Rating UL/CSA
(200 ... 208 V AC) Three Phase 15 Hp | (200 V AC) Three Phase 30 hp | (208 V AC) Three Phase 30 hp | (220 ... 240 V AC) Three Phase 20 Hp | (220 ... 240 V AC) Three Phase 40 hp | (440 ... 480 V AC) Three Phase 40 Hp | (440 ... 480 V AC) Three Phase 75 hp | (550 ... 600 V AC) Three Phase 50 Hp | (550 ... 600 V AC) Three Phase 100 hp
Ambient Air Temperature
Close to Contactor Fitted with Thermal O/L Relay (0.85 ... 1.1 Uc) -25 ... 55 °C | Close to Contactor without Thermal O/L Relay (0.85 ... 1.1 Uc) -40 ... 70 °C | Close to Contactor for Storage -40 ... 70 °C
Maximum Operating Altitude Permissible
Without Derating 3000 m
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
REACH Declaration
REACH - Letter of Confirmation for block contactors, contactor relays, installation contactors, mini contactors, mini contactor relays, thermal overload relays, electronic overload relays and related accessories
RoHS Information
RoHS II declaration for block contactors, installation contactors, mini contactors, mini contactor relays, thermal overload relays, electronic overload relays and related accessories
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration for Contactors
WEEE B2C / B2B
Business To Business
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
ABB EcoSolutions
Yes
ABB Site Meeting Group Waste To Landfill Target
Non-hazardous waste is sent to a landfill, where there is no alternative option available within 100km of a facility
End Of Life Disassembling Instructions
End-of-life instruction - AF(S)116(B)-**(RT) to AF(S)205(B)-**(RT)
Environmental Product Declaration - EPD
Environmental Product Declaration, AF(S)116-AF(S)146 (SE) Contactors
Improved Energy Efficiency for Customers
Product Efficiency - Product requires less energy to operate compared to similar product on market or older products from the same line
Recyclability Rate of the Product acc. to EN45555
Design for Closing Resource Loops - Standard EN45555 - 87.8 %
Sustainable Material Content in Product (wt. %)
Recycled Metal - 37 %
A2L Certificate – UL
UL Certificate of Compliance A2L, Contactor, AF116 - AF146
ABS Certificate
ABS Approval, Contactor, AF116 ... AF370 (Sweden)
BV Certificate
BV Certificate, Contactor, AF116-30 ... AF370-30...AF116-40...AF370-40
CB Certificate
SEMKO_SE-70479M1
CCS Certificate
CCS Certificate, Contactor, AF116 to AF2850 (Sweden)
CQC Certificate
CQC Certificate, AC Contactor, AF116-*-*-*, AF140-*-*-*, AF146-*-*-*, AF116B-*-*-*, AF140B-*-*-*, AF146B-*-*-*, AFS116-30-*-*,AFS140-30-*-*, AFS146-30-*-*, Made in Sweden
Declaration of Conformity - CCC
CCC Declaration of Conformity, AC Contactor, AF116-*-*-*, AF140-*-*-*, AF146-*-*-*, AF116B-*-*-*, AF140B-*-*-*, AF146B-*-*-*, AFS116-30-*-*,AFS140-30-*-*, AFS146-30-*-*, Made in Sweden
Declaration of Conformity - CE
CE Declaration of Conformity - Contactor - AF116...AF370
Declaration of Conformity - UKCA
UK Declaration of Conformity - Contactors >100A
DNV Certificate
DNV-certificate, Contactors, AF116-30...AF370-30 and AF116-40...AF370-40
EAC Certificate
9AKK107046A8618
LR Certificate
Lloyds register Certificate, Contactor, AF116-30 ... AF370-30, AF116-40...AF370-40
PRS Certificate
PRS Certificate - AF116...AF1650
RINA Certificate
RINA Certificate, AF95, AF110, AF145, AF185, AF210, AF260, AF300, AF400, AF460, AF580, AF750, AF1250, AF1350, AF1650, AF2050, AF2650, AF116, AF140, AF146, AF190, AF205, AF265, AF305, AF370
RMRS Certificate
9AKK107045A6978
UL Certificate
cULus Certificate, Contactor, AF116-30...AF146-30, AFS116-30...AFS146-30
UL Listing Card
UL_E36588
Package Level 1 Units
box 1 piece
Package Level 1 Width
207 mm
Package Level 1 Depth / Length
216 mm
Package Level 1 Height
150 mm
Package Level 1 Gross Weight
1.5 kg
Package Level 1 EAN
7320500481011
Object Classification Code
Q
ETIM 7
EC000066 - Power contactor, AC switching
ETIM 8
EC000066 - Power contactor, AC switching
ETIM 9
EC000066 - Power contactor, AC switching
eClass
V11.0 : 27371003
UNSPSC
39121529
IDEA Granular Category Code (IGCC)
4758 >> Iec Contactors
Feature → Business Impact → Application: AF technology delivers a wide control voltage range of 100-250 V AC/50/60 Hz and DC, enabling reliable operation across voltage fluctuations and reducing commissioning time in panel builds. This translates to lower energy waste and fewer field faults in distributed installations, ideal for food processing lines and conveyors where uptime matters. Feature → Business Impact → Application: Built-in surge protection in a compact block design reduces external components, saves space in control panels, and cuts cabinet cost while improving motor start reliability in harsh environments such as water treatment and HVAC systems. Feature → Business Impact → Application: Three NO main contacts with 690 V / 60 Hz operation, rated IE up to 160 A AC-1 and up to 65 A AC-3/AC-3e, deliver high switching performance for pumps and fans, with predictable protective coordination in building automation. Feature → Business Impact → Application: Main circuit bars and connector design enable fast installation and straightforward retrofits, reducing commissioning time by professionals in machine builders and panel shops. Feature → Business Impact → Application: Coil consumption values (6 W hold, 130 VA pull-in typical) support energy-aware control in applications requiring tight thermal management, such as presses or extrusion lines, while ensuring reliable pull-in under modest voltage variations. Feature → Business Impact → Application: High mechanical durability (up to 5 million operations) and a maximum mechanical switching frequency of 300 cycles/hour give long service life in demanding duty cycles found in material handling and packaging lines. Feature → Business Impact → Application: Compliance with RoHS, REACH, TSCA and WEEE B2B requirements streamlines procurement and regulatory reporting for global manufacturers, enhancing sustainability credentials. Feature → Business Impact → Application: 3P configuration with 3NO contacts and no NC contacts simplifies wiring and reduces panel complexity, ideal for standard motor starter assemblies in mining, metals processing, and water/wastewater treatment.

Get a Quick Quote for a ABB 1SFL427002R3300

Chat with us on WhatsApp - fast responses guaranteed

Need to speak with someone? We'll call you back within 2 hours during business hours

Interested in ABB 1SFL427002R3300? Enquire Now

FAQs

Yes. The AF116-30-00B-33 based 3-pole design uses main circuit bars for the primary connection, supporting 690 V rated operation and up to 160 A AC-1, with 65 A AC-3/AC-3e ratings, making it straightforward to integrate into new or retrofit panel assemblies.
The coil control voltage spans 100-250 V for 50 Hz, 60 Hz, and DC operation. This wide range ensures reliable pull-in and hold-in in fluctuating electrical environments, reducing the likelihood of nuisance tripping in unstable networks.
The device carries CE declarations of conformity and UL/CSA approvals for general use at 600 V, with additional certifications such as UKCA, UL certificates, and various third-party confirmations (BV, DNV, RINA, etc.) supporting global compliance and market access.
Ambient temperature ranges include -25 to 55°C with an O/L relay fitted, and -40 to 70°C without O/L; maximum operating altitude is up to 3000 m without derating, making it suitable for many industrial sites with environmental extremes.
Key metrics include 5 million mechanical durability cycles, a 37-47 ms operate time, 6 W coil power loss per pole, and a 300 cycles/hour maximum electrical switching frequency. These translate to long service life, reduced downtime, and lower maintenance costs in packaging, pumping and material handling lines.