ABB 1SFL437001R6900 Contactor - 1000 V AC/DC, 3P

Part Number: 1SFL437001R6900
Manufacturer
ABB
Part number
1SFL437001R6900

Quick Summary

ABB 1SFL437001R6900 Contactor is a three-pole motor starter that enables reliable starting and isolation of three-phase motors. This design addresses the common challenge of narrow coil voltage ranges and cross‑compatibility across equipment in modern automation lines. It carries CE and UL/CSA declarations and IP ratings to support safe cabinet installation and long-term operation in industrial environments. The unit supports a wide control voltage span of 48–130 V and main voltage up to 1000 V, delivering robust performance for industrial motor control, drive panels, and high-demand switchgear. This combination of compliance, versatility, and proven durability translates into simplified procurement, faster commissioning, and lower total cost of ownership for electrical protection and circuit control applications.

Product Information

Extended Description

1SFL437001R6900 ABB: A 3-phase Contactor suitable for various applications such as Motor starting, Isolation, By-pass and Distribution application up to max 1000 V. Operated with wide control voltage range 48-130 V, AC/DC
Minimum Order Quantity
1 piece
Customs Tariff Number
85364900
Replacement Product ID (NEW)
1SBL407001R1200
Data Sheet, Technical Information
1SBC100192C0206
Instructions and Manuals
Contactors A95, A110, UA95, UA110, AF95, AF110, AE95, AE110, TAE95, TAE110
Dimension Diagram
53540923-1
Product Net Width
90 mm
Product Net Depth / Length
123.5 mm
Product Net Height
148 mm
Product Net Weight
1.9 kg
Number of Main Contacts NO
3
Number of Main Contacts NC
0
Number of Auxiliary Contacts NO
0
Number of Auxiliary Contacts NC
0
Number of Poles
3P
Rated Operational Voltage
Main Circuit 1000 V
Rated Frequency (f)
Main Circuit 50 / 60 Hz
Conventional Free-air Thermal Current (Ith)
acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 145 A
Rated Operational Current AC-1 (Ie)
(690 V) 40 °C 145 A | (690 V) 55 °C 135 A | (690 V) 70 °C 115 A
Rated Operational Current AC-3 (Ie)
(415 V) 55 °C 96 A | (440 V) 55 °C 93 A | (500 V) 55 °C 80 A | (690 V) 55 °C 65 A | (1000 V) 55 °C 30 A | (380 / 400 V) 55 °C 96 A | (220 / 230 / 240 V) 55 °C 96
Rated Operational Current DC-1 (Ie)
(110 V) 2 Poles in Series, 40 °C 145 A | (220 V) 3 Poles in Series, 40 °C 145 A
Rated Operational Current DC-3 (Ie)
(110 V) 2 Poles in Series, 40 °C 145 A | (220 V) 3 Poles in Series, 40 °C 145 A
Rated Operational Current DC-5 (Ie)
(110 V) 2 Poles in Series, 40 °C 145 A | (220 V) 3 Poles in Series, 40 °C 145 A
Rated Operational Power AC-3 (Pe)
(415 V) 55 kW | (440 V) 55 kW | (500 V) 55 kW | (690 V) 55 kW | (1000 V) 40 kW | (380 / 400 V) 45 kW | (220 / 230 / 240 V) 25 kW
Rated Breaking Capacity AC-3
8 x Ie AC-3
Rated Making Capacity AC-3
10 x Ie AC-3
Short-Circuit Protective Devices
gG Type Fuses 160 A
Maximum Breaking Capacity
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 1160 A | cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 800 A
Rated Insulation Voltage (Ui)
acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 1000 V | acc. to UL/CSA 600 V
Rated Impulse Withstand Voltage (Uimp)
Main Circuit 8 kV
Maximum Electrical Switching Frequency
(AC-1) 300 cycles per hour | (AC-2 / AC-4) 150 cycles per hour | (AC-3) 300 cycles per hour
Mechanical Durability
10 million
Maximum Mechanical Switching Frequency
300 cycles per hour
Coil Operating Limits
(acc. to IEC 60947-4-1) 0.85 x Uc Min. ... 1.1 x Uc Max. (at θ ≤ 70 °C)
Rated Control Circuit Voltage (Uc)
50 Hz 48 ... 130 V | 60 Hz 48 ... 130 V | DC Operation 48 ... 130 V
Coil Consumption
Holding at Max. Rated Control Circuit Voltage 50 Hz 7 V·A | Holding at Max. Rated Control Circuit Voltage 60 Hz 7 V·A | Holding at Max. Rated Control Circuit Voltage DC 2 W | Pull-in at Max. Rated Control Circuit Voltage 50 Hz 350 V·A | Pull-in at Max. Rated Control Circuit Voltage 60 Hz 350 V·A | Pull-in at Max. Rated Control Circuit Voltage DC 400 W
Power Loss
at Rated Operating Conditions per Pole 3.5 W
Operate Time
Between Coil De-energization and NC Contact Closing 60 ... 130 ms | Between Coil De-energization and NO Contact Opening 55 ... 125 ms | Between Coil Energization and NC Contact Opening 27 ... 77 ms | Between Coil Energization and NO Contact Closing 30 ... 80 ms
Connecting Capacity Main Circuit
Bar 30 mm² | Flexible with Cable End 1 x 10 ... 70 mm² | Rigid 2 x 6 ... 65 mm²
Connecting Capacity Auxiliary Circuit
Flexible with Ferrule 2x 0.75 ... 2.5 mm² | Flexible with Insulated Ferrule 2x 0.75 ... 2.5 mm² | Flexible 1x0.75 ... 2.5 mm² | Solid 2 x 1 ... 4 mm² | Stranded 1 x 1 .... 4 mm²
Connecting Capacity
Bar 30 mm² | Flexible with Cable End 2 x 6 ... 35 mm² | Rigid 2 x 6 ... 65 mm²
Degree of Protection
acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20 | acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP10
Connecting Terminals (delivered in open position) Main Poles
M8 hexagon socket screw with single connector
Tightening Torque
Main Circuit 8 N·m
Terminal Type
Cable Clamp
Product Name
Block Contactor
Maximum Operating Voltage UL/CSA
Main Circuit 600 V
General Use Rating UL/CSA
(600 V AC) 125 A
Horsepower Rating UL/CSA
(200 V AC) Three Phase 30 hp | (208 V AC) Three Phase 30 hp | (220 ... 240 V AC) Three Phase 30 hp | (440 ... 480 V AC) Three Phase 60 hp | (550 ... 600 V AC) Three Phase 75 hp
Full Load Amps Motor Use
(440 ... 480 V AC) Three Phase 77 A | (550 ... 600 V AC) Three Phase 77 A
Ambient Air Temperature
Close to Contactor Fitted with Thermal O/L Relay (0.85 ... 1.1 Uc) -25 ... 50 °C | Close to Contactor without Thermal O/L Relay (0.85 ... 1.1 Uc) -40 ... 70 °C | Close to Contactor for Storage -60 ... +80 °C
Maximum Operating Altitude Permissible
Without Derating 3000 m
Resistance to Shock acc. to IEC 60068-2-27
Half-sine Pulse for 11 ms, No Change in Contact Position, Open, Shock Direction: A 20 g | Half-sine Pulse for 11 ms, No Change in Contact Position, Closed, Shock Direction: A 20 g | Half-sine Pulse for 11 ms, No Change in Contact Position, Closed, Shock Direction: B1 15 g | Half-sine Pulse for 11 ms, No Change in Contact Position, Closed, Shock Direction: C1 20 g | Half-sine Pulse for 11 ms, No Change in Contact Position, Closed, Shock Direction: C2 20 g | Half-sine Pulse for 11 ms, No Change in Contact Position, Open, Shock Direction: B1 5 g | Half-sine Pulse for 11 ms, No Change in Contact Position, Open, Shock Direction: B2 15 g | Half-sine Pulse for 11 ms, No Change in Contact Position, Open, Shock Direction: C1 20 g | Half-sine Pulse for 11 ms, No Change in Contact Position, Open, Shock Direction: C2 20 g
RoHS Information
CE Declaration of Conformity - Contactor - A(F)95...A(F)300, AM110...AM300, UA95...UA110, (T)AE95....(T)AE110
RoHS Status
Following EU Directive 2011/65/EU
WEEE B2C / B2B
Business To Business
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
ABS Certificate
ABS Certificate, Contactor, AF400...AF2050 (Sweden)
BV Certificate
BV Certificate, Contactor, AF400 ... AF2850
CB Certificate
SE-73661
CCS Certificate
CCS Certificate, Contactor, AF116 to AF2850 (Sweden)
CQC Certificate
CQC Certificate, Contactor, AF95, AF95...RT, AF95B...RT, AF110, AF110...RT, AF110B...RT, Made in Sweden | CQC Certificate, Contactor, AF95-30, AF95-30-11, AF110-30, AF110-30-11, Made in China
Declaration of Conformity - CCC
CCC Declaration of Conformity, Contactor, AF95, AF95...RT, AF95B...RT, AF110, AF110...RT, AF110B...RT, Made in Sweden | CCC Declaration of Conformity, Contactor, AF95-30, AF95-30-11, AF110-30, AF110-30-11, Made in China
Declaration of Conformity - CE
CE Declaration of Conformity - Contactor - A(F)95...A(F)300, AM110...AM300, UA95...UA110, (T)AE95....(T)AE110
DNV GL Certificate
DNV Certificate, Contactor, AF400...AF2850
EAC Certificate
9AKK107046A8618
GL Certificate
GL_20260-04HH
LR Certificate
Lloyds register Certificate, Contactor, AF400...AF2850
RINA Certificate
RINA Certificate, AF95, AF110, AF145, AF185, AF210, AF260, AF300, AF400, AF460, AF580, AF750, AF1250, AF1350, AF1650, AF2050, AF2650, AF116, AF140, AF146, AF190, AF205, AF265, AF305, AF370
RMRS Certificate
RMRS_12-03683-315
Package Level 1 Units
box 1 piece
Package Level 1 Width
130 mm
Package Level 1 Depth / Length
265 mm
Package Level 1 Height
162 mm
Package Level 1 Gross Weight
2.1 kg
Package Level 1 EAN
7320500237342
Object Classification Code
Q
ETIM 7
EC000066 - Power contactor, AC switching
ETIM 8
EC000066 - Power contactor, AC switching
ETIM 9
EC000066 - Power contactor, AC switching
eClass
V11.0 : 27371003
UNSPSC
39121529
IDEA Granular Category Code (IGCC)
4755 >> Contactors
E-Number (Norway)
3228268
E-Number (Sweden)
3228268
Feature: Wide control voltage range of 48–130 V AC/DC. Business Impact: Reduces stock diversity and simplifies control circuit design, lowering inventory and engineering effort. Application: Suitable for 3‑phase motor control in variable voltage environments where coil voltage fluctuates. Feature: Main circuit rated up to 1000 V. Business Impact: Enables direct interface with high-voltage drives and distributors, increasing system flexibility and reliability. Application: Motor starting and distribution in heavy industrial setups.Feature: 3P, 3 poles with NO main contacts. Business Impact: Ensures robust switching for three-phase motors with predictable breaking capacity and switching behavior. Application: Industry-standard motor control in packaging, material handling, and pumps.Feature: IP20 coil terminals and IP10 main terminals. Business Impact: Safer coil wiring inside control cabinets and easier field wiring with reduced risk of contamination. Application: Cabinet-based installations in manufacturing lines.Feature: Mechanical durability rated at 10 million cycles. Business Impact: Lower maintenance cost and longer service life in high-cycle applications. Application: Continuous operation in conveyors and process lines.Feature: 3 x main contacts NO, 3P configuration and comprehensive protection options. Business Impact: Simplifies integration with protection schemes and fusing strategies (gG fuses up to 160 A). Application: Setup for UL/CSA‑compliant motor control centers and switchgear.

Get a Quick Quote for a ABB 1SFL437001R6900

Chat with us on WhatsApp - fast responses guaranteed

Need to speak with someone? We'll call you back within 2 hours during business hours

Interested in ABB 1SFL437001R6900? Enquire Now

FAQs

The 1SFL437001R6900 is a 3P block contactor with NO main contacts and 3 poles. Connect the main circuit to the rated terminal blocks using 30 mm² bars or 2 x 6–65 mm² rigid cables as specified, and wire the coil to a 48–130 V AC/DC control circuit. Ensure IP20 coil terminals and IP10 main terminals are properly connected, and fit the unit with the recommended fusing (gG type, 160 A) per system protection requirements.
AC-3 ratings vary by voltage: at 415 V, 55 °C the Ie is 96 A; at 440 V 55 °C it’s 93 A; at 500 V 55 °C it’s 80 A; at 690 V 55 °C it’s 65 A; at 1000 V it’s 30 A. AC-1 ratings are higher overall and are specified as 690 V, 40 °C 145 A. These figures support motor starting and switching duties in diverse industrial drives.
Yes. The device is rated for operation up to 3000 m without derating, with ambient temperature ranges that accommodate -25 to 50 °C when used with an integrated thermal overload relay, and -40 to 70 °C when operated without it. It includes protection that helps mitigate shock and vibration in standard manufacturing environments.
The contactor is CE certified and UL/CSA listed, with additional global approvals such as CCC, CB, EAC, and others noted in the product declarations. It also adheres to IEC 60947-4-1 for contactors and UL/CSA safety requirements, ensuring compliance for global electrical installation practices.
Mechanical durability is rated at 10 million cycles, with a maximum mechanical switching frequency of 300 cycles per hour. This translates to lower maintenance downtime and longer service life in continuous‑duty applications such as conveyors, pumps, and large HVAC drives. Routine checks focus on contact cleanliness and coil integrity to sustain reliable operation.