ABB AF140-30-22B-34 Block Contactor - 690 V / 200 A

Part Number: 1SFL447002R3422
Manufacturer
ABB
Part number
1SFL447002R3422

Quick Summary

The ABB AF140-30-22B-34 block contactor is designed to safely switch motors up to 75 kW at 400 V AC and 100 hp at 480 V UL, with a 3-pole configuration and pre-mounted auxiliary contacts. In demanding environments, voltage fluctuations can cause nuisance tripping; this device mitigates that risk with a wide control voltage range and built-in protection. It carries CE, UL/CSA, and UKCA certifications, supporting global deployment and compliance. The solution combines AF technology with a compact, extendable design, delivering reliable motor control in automated lines while enabling energy-efficient control through scalable accessory options.

Product Information

Extended Description

1SFL447002R3422 ABB: The AF140-30-22B-34 is a 3 pole - 690 V IEC or 600 V UL contactor with pre-mounted auxiliary contacts and Main Circuit Bars, controlling motors up to 75 kW / 400 V AC (AC-3) or 100 hp / 480 V UL and switching power circuits up to 200 A (AC-1) or 200 A UL general use. Thanks to the AF technology, the contactor has a wide control voltage range (250-500 V 50/60 Hz and DC), managing large control voltage variations, reducing panel energy consumptions and ensuring distinct operations in unstable networks. Furthermore, surge protection is built-in, offering a compact solution. AF contactors have a block type design, can be easily extended with add-on auxiliary contact blocks and an additional wide range of accessories.
Minimum Order Quantity
1 piece
Customs Tariff Number
85364900
Data Sheet, Technical Information
1SBC100214C0202 - Main catalog Motor protection and control Manual motor starters, contactors and overload relays (PDF) - Edition 2024
Data Sheet, Technical Information (Part 2)
Contactors and Overload relays guide
Instructions and Manuals
Operating instruction, Contactor, AF(S)116, AF140, AF(S)146
CAD Dimensional Drawing
Information - 2D and 3D files for CAD systems
Product Net Width
90 mm
Product Net Depth / Length
142.5 mm
Product Net Height
150 mm
Product Net Weight
1.3 kg
Number of Main Contacts NO
3
Number of Main Contacts NC
0
Number of Auxiliary Contacts NO
2
Number of Auxiliary Contacts NC
2
Number of Poles
3P
Rated Operational Voltage
Main Circuit 690 V
Rated Frequency (f)
Main Circuit 60 Hz
Conventional Free-air Thermal Current (Ith)
acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 200 A
Rated Operational Current AC-1 (Ie)
(690 V) 40 °C 200 A
Rated Operational Current AC-3 (Ie)
(415 V) 55 °C 140 A | (440 V) 55 °C 140 A | (500 V) 55 °C 80 A | (690 V) 55 °C 80 A | (380 / 400 V) 55 °C 140 A | (220 / 230 / 240 V) 55 °C 140 A
Rated Operational Current AC-3e (Ie)
(415 V) 60 °C 140 A | (440 V) 60 °C 140 A | (500 V) 60 °C 130 A | (690 V) 60 °C 80 A | (380 / 400 V) 60 °C 140 A | (220 / 230 / 240 V) 60 °C 140 A
Rated Operational Power AC-3 (Pe)
(415 V) 75 kW | (440 V) 90 kW | (500 V) 90 kW | (690 V) 75 kW | (380 / 400 V) 75 kW | (220 / 230 / 240 V) 37 kW
Rated Operational Power AC-3e (Pe)
(415 V) 75 kW | (440 V) 90 kW | (500 V) 90 kW | (690 V) 75 kW | (380 / 400 V) 75 kW | (220 / 230 / 240 V) 37 kW
Rated Breaking Capacity AC-3
8 x Ie AC-3
Rated Breaking Capacity AC-3e
8.5 x Ie AC-3e
Rated Making Capacity AC-3
10 x Ie AC-3
Rated Making Capacity AC-3e
12 x Ie AC-3e
Short-Circuit Protective Devices
gG Type Fuses 315 A
Rated Short-time Withstand Current Low Voltage (Icw)
at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 1168 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 200 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 477 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 1460 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 674 A
Rated Insulation Voltage (Ui)
acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 1000 V | acc. to UL/CSA 600 V
Rated Impulse Withstand Voltage (Uimp)
8 kV
Maximum Electrical Switching Frequency
(AC-1) 300 cycles per hour | (AC-2 / AC-4) 150 cycles per hour | (AC-3) 300 cycles per hour
Mechanical Durability
5 million
Maximum Mechanical Switching Frequency
300 cycles per hour
Coil Operating Limits
(acc. to IEC 60947-4-1) Uc (at θ ≤ 70 °C)
Rated Control Circuit Voltage (Uc)
50 Hz 250 ... 500 V | 60 Hz 250 ... 500 V | DC Operation 250 ... 500 V
Coil Consumption
Average Pull-in Value 50 Hz 260 V·A | Average Pull-in Value 60 Hz 260 V·A | Holding at Max. Rated Control Circuit Voltage 50 Hz 16.1 V·A | Holding at Max. Rated Control Circuit Voltage 60 Hz 16.1 V·A | Pull-in at Max. Rated Control Circuit Voltage 50 Hz 205 V·A | Pull-in at Max. Rated Control Circuit Voltage 60 Hz 205 V·A | Pull-in at Max. Rated Control Circuit Voltage DC 230 W
Power Loss
at Rated Operating Conditions per Pole 9 W
Operate Time
Between Coil De-energization and NO Contact Opening 37 ... 47 ms | Between Coil Energization and NO Contact Closing 25 ... 55 ms
Degree of Protection
acc. to IEC 60529, IEC 60947-1, EN 60529 Auxiliary Terminals IP40
Terminal Type
Main Circuit: Bars
Product Name
Block Contactor
NEMA Size
4
Continuous Current Rating NEMA
135 A
Horsepower Rating NEMA
(200 V AC) Three Phase 40 Hp | (230 V AC) Three Phase 50 Hp | (460 V AC) Three Phase 100 Hp | (575 V AC) Three Phase 100 Hp
Horsepower Rating UL/CSA
(200 ... 208 V AC) Three Phase 15 Hp | (200 V AC) Three Phase 40 hp | (208 V AC) Three Phase 40 hp | (220 ... 240 V AC) Three Phase 20 Hp | (220 ... 240 V AC) Three Phase 50 hp | (440 ... 480 V AC) Three Phase 40 Hp | (440 ... 480 V AC) Three Phase 100 hp | (550 ... 600 V AC) Three Phase 50 Hp | (550 ... 600 V AC) Three Phase 125 hp
Ambient Air Temperature
Close to Contactor Fitted with Thermal O/L Relay (0.85 ... 1.1 Uc) -25 ... 55 °C | Close to Contactor without Thermal O/L Relay (0.85 ... 1.1 Uc) -40 ... 70 °C | Close to Contactor for Storage -40 ... 70 °C
Maximum Operating Altitude Permissible
Without Derating 3000 m
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
REACH Declaration
REACH - Letter of Confirmation for block contactors, contactor relays, installation contactors, mini contactors, mini contactor relays, thermal overload relays, electronic overload relays and related accessories
RoHS Information
RoHS II declaration for block contactors, installation contactors, mini contactors, mini contactor relays, thermal overload relays, electronic overload relays and related accessories
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration for Contactors
WEEE B2C / B2B
Business To Business
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
ABB EcoSolutions
Yes
ABB Site Meeting Group Waste To Landfill Target
Non-hazardous waste is sent to a landfill, where there is no alternative option available within 100km of a facility
End Of Life Disassembling Instructions
End-of-life instruction - AF(S)116(B)-**(RT) to AF(S)205(B)-**(RT)
Environmental Product Declaration - EPD
Environmental Product Declaration, AF(S)116-AF(S)146 (SE) Contactors
Improved Energy Efficiency for Customers
Product Efficiency - Product requires less energy to operate compared to similar product on market or older products from the same line
Recyclability Rate of the Product acc. to EN45555
Design for Closing Resource Loops - Standard EN45555 - 87.8 %
Sustainable Material Content in Product (wt. %)
Recycled Metal - 37 %
A2L Certificate – UL
UL Certificate of Compliance A2L, Contactor, AF116 - AF146
ABS Certificate
ABS Approval, Contactor, AF116 ... AF370 (Sweden)
BV Certificate
BV Certificate, Contactor, AF116-30 ... AF370-30...AF116-40...AF370-40
CB Certificate
SEMKO_SE-70479M1
CCS Certificate
CCS Certificate, Contactor, AF116 to AF2850 (Sweden)
CQC Certificate
CQC Certificate, AC Contactor, AF116-*-*-*, AF140-*-*-*, AF146-*-*-*, AF116B-*-*-*, AF140B-*-*-*, AF146B-*-*-*, AFS116-30-*-*,AFS140-30-*-*, AFS146-30-*-*, Made in Sweden
Declaration of Conformity - CCC
CCC Declaration of Conformity, AC Contactor, AF116-*-*-*, AF140-*-*-*, AF146-*-*-*, AF116B-*-*-*, AF140B-*-*-*, AF146B-*-*-*, AFS116-30-*-*,AFS140-30-*-*, AFS146-30-*-*, Made in Sweden
Declaration of Conformity - CE
CE Declaration of Conformity - Contactor - AF116...AF370
Declaration of Conformity - UKCA
UK Declaration of Conformity - Contactors >100A
DNV Certificate
DNV-certificate, Contactors, AF116-30...AF370-30 and AF116-40...AF370-40
DNV GL Certificate
DNV-certificate, Contactors, AF116-30...AF370-30 and AF116-40...AF370-40
EAC Certificate
9AKK107046A8618
GL Certificate
DNV-certificate, Contactors, AF116-30...AF370-30 and AF116-40...AF370-40
LR Certificate
Lloyds register Certificate, Contactor, AF116-30 ... AF370-30, AF116-40...AF370-40
PRS Certificate
PRS Certificate - AF116...AF1650
RINA Certificate
RINA Certificate, AF95, AF110, AF145, AF185, AF210, AF260, AF300, AF400, AF460, AF580, AF750, AF1250, AF1350, AF1650, AF2050, AF2650, AF116, AF140, AF146, AF190, AF205, AF265, AF305, AF370
RMRS Certificate
9AKK107045A6978
UL Certificate
cULus Certificate, Contactor, AF116-30...AF146-30, AFS116-30...AFS146-30
UL Listing Card
UL_E36588
Package Level 1 Units
box 1 piece
Package Level 1 Width
207 mm
Package Level 1 Depth / Length
216 mm
Package Level 1 Height
150 mm
Package Level 1 Gross Weight
1.5 kg
Package Level 1 EAN
7320500480847
Object Classification Code
Q
ETIM 7
EC000066 - Power contactor, AC switching
ETIM 8
EC000066 - Power contactor, AC switching
ETIM 9
EC000066 - Power contactor, AC switching
eClass
V11.0 : 27371003
UNSPSC
39121529
IDEA Granular Category Code (IGCC)
4755 >> Contactors
Feature: AF technology provides a wide control voltage range of 250-500 V AC/DC, enabling operation across varying networks. Business Impact: Reduces panel energy consumption and minimizes controller churn during voltage swings. Application: Ideal for installations with unstable mains or where multiple supply voltages are present. Feature: Built-in surge protection protects the coil and extending life of the control circuit. Business Impact: Lower maintenance costs and reduced downtime from coil failure. Application: Critical in high-startup current applications like conveyors and pumps. Feature: 3-pole main circuit rated up to 690 V and 200 A, with 3 NO main contacts. Business Impact: Supports motors up to 75 kW at 415 V and 80 A at higher voltages, improving drive reliability. Application: Heavy-duty motor control in general automation. Feature: Pre-mounted auxiliary contacts (2 NO + 2 NC) and main circuit bars. Business Impact: Simplifies wiring, reduces panel depth, and speeds installation. Application: Panel builders benefit from faster commissioning and repeatable layouts. Feature: Easily extendable with add-on auxiliary blocks; compatible with AF(S) accessories. Business Impact: Scales from simple start/stop to complex interlocks without replacing hardware. Application: Modular control schemes for multi-motor lines. Feature: Certifications and compliance (CE, UL/CSA, UKCA) ensure regulatory readiness. Business Impact: Facilitates procurement across regions and reduces compliance risk. Application: Global manufacturing facilities and export-facing projects. Industry context and insights: AF contactors are designed for efficiency and reliability in industrial automation, with focus on minimizing energy waste and enabling compact, serviceable control panels. The combination of wide control voltage tolerance and built-in surge protection aligns with modern energy-efficiency targets and lifecycle cost reductions in plant modernization projects.

Get a Quick Quote for a ABB 1SFL447002R3422

Chat with us on WhatsApp - fast responses guaranteed

Need to speak with someone? We'll call you back within 2 hours during business hours

Interested in ABB 1SFL447002R3422? Enquire Now

FAQs

The AF140-30-22B-34 is a 3-pole block contactor designed to work within the AF(S) family. It ships with pre-mounted auxiliary contacts and main circuit bars, enabling seamless integration into existing AF-based control cabinets. Its extendable design supports add-on auxiliary blocks, simplifying upgrades without reworking panel layouts or wiring harnesses.
For AC-3 operation, ratings vary by voltage: at 415 V and 55 °C it is 140 A, at 440 V it is 140 A, at 500 V it drops to 80 A, and at 690 V it remains 80 A. For AC-1, rated operational current is 200 A at 690 V (40 °C). These values support motor starts up to 75 kW (AC-3) and general circuit switching up to 200 A.
Yes. It is a 3P block contactor rated for 690 V main circuit with 200 A Ie and 75 kW maximum motor power at standard voltages. Its AF technology and built-in surge protection enhance reliability in motor protection schemes, while the 3NO main contacts and 2NO/2NC auxiliaries support soft-start interlocks and overload relay integration.
This unit carries CE declarations of conformity, UL/CSA certification, and UKCA marking, with related certificates referenced in its data package. It is designed to meet global safety and environmental standards, reducing the regulatory burden for multinational installations and helping ensure supplier compliance across regions.
AF technology offers a wide control voltage range (250-500 V) and integrated surge protection, reducing coil wear and energization stress. The device has a mechanical durability rating of around 5 million cycles, supporting long service life in automation lines. Minimal extended maintenance translates to lower operating costs and fewer unplanned downtime events.