ABB 1SFL467002R4200 Block Contactor - UL/CSA 1000 V

Part Number: 1SFL467002R4200
Manufacturer
ABB
Part number
1SFL467002R4200

Quick Summary

Block Contactor ABB 1SFL467002R4200 is a three-pole motor controller designed for AC-3 duty in industrial panels. In modern plants where reliability and energy efficiency are critical, voltage sags, transients, and nuisance tripping can trigger motor wear and unnecessary downtime. The device ships with CE Declaration of Conformity, UL/CSA listings, and UKCA marking, and it also complies with RoHS and REACH, supporting compliant global installations. Its compact AF technology, built-in surge protection, and easy expansion with auxiliary contact blocks simplify panel wiring, shrink footprint, and improve serviceability for engineers and procurement teams during commissioning and maintenance. This combination delivers measurable improvements in motor protection and overall plant productivity.

Product Information

Extended Description

1SFL467002R4200 ABB: The AF146-30-00B-42 is a 3 pole - 1000 V IEC or 600 V UL contactor with Main Circuit Bars, controlling motors up to 75 kW / 400 V AC (AC-3) or 100 hp / 480 V UL and switching power circuits up to 225 A (AC-1) or 200 A UL general use. Thanks to the AF technology, the contactor has a control voltage range (110-120 V 50/60 Hz),faster operation time, reducing panel energy consumptions and ensuring distinct operations in unstable networks. Furthermore, surge protection is built-in, offering a compact solution. AF contactors have a block type design, can be easily extended with add-on auxiliary contact blocks and an additional wide range of accessories.
Minimum Order Quantity
1 piece
Customs Tariff Number
8536490099
Data Sheet, Technical Information
1SBC100214C0202 - Main catalog Motor protection and control Manual motor starters, contactors and overload relays (PDF) - Edition 2024
Data Sheet, Technical Information (Part 2)
Contactors and Overload relays guide
Instructions and Manuals
Operating instruction, Contactor, AF(S)116, AF140, AF(S)146
CAD Dimensional Drawing
Information - 2D and 3D files for CAD systems
Product Net Width
90 mm
Product Net Depth / Length
126 mm
Product Net Height
150 mm
Product Net Weight
1.3 kg
Number of Main Contacts NO
3
Number of Main Contacts NC
0
Number of Auxiliary Contacts NO
0
Number of Auxiliary Contacts NC
0
Number of Poles
3P
Rated Operational Voltage
Main Circuit 1000 V
Rated Frequency (f)
Main Circuit 50 / 60 Hz
Conventional Free-air Thermal Current (Ith)
acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 225 A
Rated Operational Current AC-1 (Ie)
(1000 V) 40 °C 225 A | (1000 V) 60 °C 200 A | (1000 V) 70 °C 175 A | (690 V) 40 °C 225 A | (690 V) 60 °C 200 A | (690 V) 70 °C 175 A
Rated Operational Current AC-3 (Ie)
(415 V) 60 °C 146 A | (440 V) 60 °C 146 A | (500 V) 60 °C 130 A | (690 V) 60 °C 93 A | (1000 V) 60 °C 60 A | (380 / 400 V) 60 °C 146 A | (220 / 230 / 240 V) 60 °C 146 A
Rated Operational Current AC-3e (Ie)
(415 V) 60 °C 146 A | (440 V) 60 °C 146 A | (500 V) 60 °C 130 A | (690 V) 60 °C 93 A | (1000 V) 60 °C 54 A | (380 / 400 V) 60 °C 146 A | (220 / 230 / 240 V) 60 °C 146 A
Rated Operational Power AC-3 (Pe)
(415 V) 75 kW | (440 V) 90 kW | (500 V) 90 kW | (690 V) 90 kW | (380 / 400 V) 75 kW | (220 / 230 / 240 V) 45 kW
Rated Operational Power AC-3e (Pe)
(415 V) 75 kW | (440 V) 90 kW | (500 V) 90 kW | (690 V) 90 kW | (1000 V) 75 kW | (380 / 400 V) 75 kW | (220 / 230 / 240 V) 45 kW
Rated Breaking Capacity AC-3
8 x Ie AC-3
Rated Breaking Capacity AC-3e
8.5 x Ie AC-3e
Rated Making Capacity AC-3
10 x Ie AC-3
Rated Making Capacity AC-3e
12 x Ie AC-3e
Rated Short-time Withstand Current Low Voltage (Icw)
at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 1168 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 225 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 477 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 1460 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 674 A
Maximum Breaking Capacity
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 3000 A | cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 1500 A
Rated Insulation Voltage (Ui)
acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 1000 V | acc. to UL/CSA 1000 V
Rated Impulse Withstand Voltage (Uimp)
Main Circuit 8 kV
Maximum Electrical Switching Frequency
(AC-1) 300 cycles per hour | (AC-2 / AC-4) 150 cycles per hour | (AC-3) 300 cycles per hour
Mechanical Durability
5 million
Maximum Mechanical Switching Frequency
300 cycles per hour
Rated Control Circuit Voltage (Uc)
50 Hz 110 ... 120 V | 60 Hz 110 ... 120 V
Coil Consumption
Holding at Max. Rated Control Circuit Voltage 50 Hz 6 V·A | Holding at Max. Rated Control Circuit Voltage 50 Hz 2 W | Holding at Max. Rated Control Circuit Voltage 60 Hz 6 V·A | Holding at Max. Rated Control Circuit Voltage 60 Hz 2 W | Pull-in at Max. Rated Control Circuit Voltage 50 Hz 180 V·A | Pull-in at Max. Rated Control Circuit Voltage 60 Hz 180 V·A
Power Loss
at Rated Operating Conditions AC-1 per Pole 23 W | at Rated Operating Conditions AC-3 per Pole 10 W
Operate Time
Between Coil De-energization and NO Contact Opening 15 ... 20 ms | Between Coil Energization and NO Contact Closing 20 ... 35 ms
Connecting Capacity Main Circuit
Flexible 2 x 10 ... 70 mm² | Rigid Cu-Cable 1 x 10 ... 95 mm²
Connecting Capacity Auxiliary Circuit
Flexible with Ferrule 1x 0.75 ... 2.5 mm² | Flexible with Ferrule 2x 0.75 ... 2.5 mm² | Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm² | Flexible with Insulated Ferrule 2x 0.75 ... 2.5 mm² | Flexible 1x 0.75 ... 2.5 mm² | Flexible 2x 0.75 ... 2.5 mm² | Solid 1x 1 ... 4 mm² | Solid 2x 1 ... 4 mm² | Stranded 1x 1 ... 4 mm² | Stranded 2x 1 ... 4 mm²
Connecting Capacity
Flexible 1 x 10 ... 70 mm² | Flexible 2 x 10 ... 70 mm² | Rigid Cu-Cable 1 x 10 ... 95 mm²
Wire Stripping Length
Auxiliary Circuit 9 mm | Control Circuit 9 mm
Degree of Protection
acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20 | acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP00
Recommended Screw Driver
Main Circuit M6 | Control Circuit M3.5
Tightening Torque
Auxiliary Circuit 1 N·m | Cable Lug 9 N·m | Control Circuit 1 N·m | Main Circuit 8 N·m
Terminal Type
Main Circuit: Bars
Product Name
Block Contactor
Maximum Operating Voltage UL/CSA
Main Circuit 1000 V
General Use Rating UL/CSA
(1000 V AC) 200 A
Horsepower Rating UL/CSA
(200 ... 208 V AC) Three Phase 40 hp | (220 ... 240 V AC) Three Phase 50 hp | (440 ... 480 V AC) Three Phase 100 hp | (550 ... 600 V AC) Three Phase 125 hp
Tightening Torque UL/CSA
Auxiliary Circuit 9 in·lb | Control Circuit 9 in·lb | Main Circuit 71 in·lb
Full Load Amps Motor Use
(200 ... 208 V AC) Three Phase 120 A | (220 ... 240 V AC) Three Phase 130 A | (440 ... 480 V AC) Three Phase 124 A | (550 ... 600 V AC) Three Phase 125 A
Ambient Air Temperature
Close to Contactor Fitted with Thermal O/L Relay (0.85 ... 1.1 Uc) -25 ... 55 °C | Close to Contactor without Thermal O/L Relay (0.85 ... 1.1 Uc) -40 ... 70 °C | Close to Contactor for Storage -40 ... 70 °C
Maximum Operating Altitude Permissible
Without Derating 3000 m
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
REACH Declaration
REACH - Letter of Confirmation for block contactors, contactor relays, installation contactors, mini contactors, mini contactor relays, thermal overload relays, electronic overload relays and related accessories
RoHS Information
RoHS II declaration for block contactors, installation contactors, mini contactors, mini contactor relays, thermal overload relays, electronic overload relays and related accessories
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration for Contactors
WEEE B2C / B2B
Business To Business
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
ABB EcoSolutions
Yes
ABB Site Meeting Group Waste To Landfill Target
Non-hazardous waste is sent to a landfill, where there is no alternative option available within 100km of a facility
End Of Life Disassembling Instructions
End-of-life instruction - AF(S)116(B)-**(RT) to AF(S)205(B)-**(RT)
Environmental Product Declaration - EPD
Environmental Product Declaration, AF(S)116-AF(S)146 (SE) Contactors
Improved Energy Efficiency for Customers
Product Efficiency - Product requires less energy to operate compared to similar product on market or older products from the same line
Recyclability Rate of the Product acc. to EN45555
Design for Closing Resource Loops - Standard EN45555 - 87.8 %
Sustainable Material Content in Product (wt. %)
Recycled Metal - 37 %
A2L Certificate – UL
UL Certificate of Compliance A2L, Contactor, AF116 - AF146
Declaration of Conformity - CE
CE Declaration of Conformity - Contactor - AF116...AF370
Declaration of Conformity - UKCA
UK Declaration of Conformity - Contactors >100A
UL Certificate
cULus Certificate, Contactor, AF116-30...AF146-30, AFS116-30...AFS146-30
Package Level 1 Units
box 1 piece
Package Level 1 Width
207 mm
Package Level 1 Depth / Length
216 mm
Package Level 1 Height
150 mm
Package Level 1 Gross Weight
1.5 kg
Package Level 1 EAN
7320500560839
Object Classification Code
Q
ETIM 7
EC000066 - Power contactor, AC switching
ETIM 8
EC000066 - Power contactor, AC switching
ETIM 9
EC000066 - Power contactor, AC switching
eClass
V11.0 : 27371003
UNSPSC
39121529
IDEA Granular Category Code (IGCC)
4758 >> Iec Contactors
AF technology with integrated surge protection delivers faster operation times and reduced panel energy consumption, improving plant efficiency and reliability in busy automation environments. Feature → Business Impact → Application: The built-in surge protection and AF design minimize nuisance tripping and panel wear, reducing downtime and maintenance costs in conveyor lines, pumps, and fans. Application: motor control sections in automated manufacturing lines see fewer faults and quicker fault clearance. Feature → Business Impact → Application: 3-pole main circuit with 1000 V rating enables robust switching for higher power motors, improving uptime in heavy duty drives up to 75 kW at 400 V AC (AC-3). Application: steel mills, packaging systems, and material handling. Feature → Business Impact → Application: Coil voltage 110–120 V at 50/60 Hz supports common control circuits while maintaining compatibility with existing control cabinets, reducing engineering changes. Application: retrofit projects and new panel builds. Feature → Business Impact → Application: Add-on auxiliary contact blocks provide scalable control interfaces, enabling staged automation without replacing the base device. Application: modular control panels and expansion-ready motor starters. Feature → Business Impact → Application: Integrated protection and compact footprint lead to smaller enclosures and simpler wiring, lowering installation time and total cost of ownership. Application: OEM panel builders and site engineers. Feature → Business Impact → Application: RoHS, REACH, WEEE, and EPD credentials support compliance with modern sustainability programs, aiding procurement and regulatory reporting. Application: environmentally responsible manufacturing and end-of-life planning.

Get a Quick Quote for a ABB 1SFL467002R4200

Chat with us on WhatsApp - fast responses guaranteed

Need to speak with someone? We'll call you back within 2 hours during business hours

Interested in ABB 1SFL467002R4200? Enquire Now

FAQs

This block contactor accepts flexible main circuit wiring from 2 x 10 to 70 mm² and rigid Cu cables 1 x 10 to 95 mm². It uses a block design and supports add-on auxiliary contact blocks. Coil terminals are IP20 protected, while main terminals are IP00, simplifying panel integration and reducing wiring complexity in control cabinets.
For AC-1 operation at 1000 V, the device handles up to 225 A at 40 °C, 200 A at 60 °C, and 175 A at 70 °C. For AC-3 operation, ratings are 146 A across several voltages (including 415–690 V and 1000 V variants). This supports motor starts and switching in high-demand applications with clear performance margins.
Yes. The AF technology provides faster operation and built-in surge protection, reducing energy waste and panel losses. The 3P design with 75 kW maximum AC-3 power at common industrial voltages makes it suitable for conveyors, pumps, and fans, while its compact footprint eases integration into modern, energy-efficient automation architectures.
The product carries CE Declaration of Conformity, UKCA marking, and UL/CSA listings, plus RoHS and REACH compliance. An UL A2L certificate supports low-emission performance in compliant electrical installations. These certifications facilitate global deployment and simplify procurement for regulated industries.
Environmental credentials include an Environmental Product Declaration (EPD) for AF116–AF146 contactors, a recyclability rate of 87.8% per EN45555, and recycled metal content around 37%. The device is RoHS compliant, REACH registered, and aligned with WEEE guidelines, supporting sustainable manufacturing, end-of-life planning, and responsible sourcing.