ABB 1SFL467002R4300 Block Contactor - UL/CSA 1000 V

Part Number: 1SFL467002R4300
Manufacturer
ABB
Part number
1SFL467002R4300

Quick Summary

ABB 1SFL467002R4300 Block Contactor is a robust three-pole device designed for motor control in industrial automation. It addresses nuisance tripping in unstable networks and minimizes energy waste from inefficient switching, keeping machines running. UL/CSA and CE certifications accompany IP20 coil protection for safe, compliant operation in diverse facilities. The AF technology provides fast operation, reduced panel energy use, and straightforward extension with auxiliary contact blocks. This makes it suitable for high-demand applications up to 75 kW and plant-wide motor protection strategies. With its 1000 V main circuit rating and 9 mm auxiliary wiring options, it integrates smoothly into existing control panels. Engineers appreciate the compact footprint and standard CAD drawings for quick, error-free implementation.

Product Information

Extended Description

1SFL467002R4300 ABB: The AF146-30-00B-43 is a 3 pole - 1000 V IEC or 600 V UL contactor with Main Circuit Bars, controlling motors up to 75 kW / 400 V AC (AC-3) or 100 hp / 480 V UL and switching power circuits up to 225 A (AC-1) or 200 A UL general use. Thanks to the AF technology, the contactor has a control voltage range (220-240 V 50/60 Hz),faster operation time, reducing panel energy consumptions and ensuring distinct operations in unstable networks. Furthermore, surge protection is built-in, offering a compact solution. AF contactors have a block type design, can be easily extended with add-on auxiliary contact blocks and an additional wide range of accessories.
Minimum Order Quantity
1 piece
Customs Tariff Number
8536490099
Data Sheet, Technical Information
1SBC100214C0202 - Main catalog Motor protection and control Manual motor starters, contactors and overload relays (PDF) - Edition 2024
Data Sheet, Technical Information (Part 2)
Contactors and Overload relays guide
Instructions and Manuals
Operating instruction, Contactor, AF(S)116, AF140, AF(S)146
CAD Dimensional Drawing
Information - 2D and 3D files for CAD systems
Product Net Width
90 mm
Product Net Depth / Length
126 mm
Product Net Height
150 mm
Product Net Weight
1.3 kg
Number of Main Contacts NO
3
Number of Main Contacts NC
0
Number of Auxiliary Contacts NO
0
Number of Auxiliary Contacts NC
0
Number of Poles
3P
Rated Operational Voltage
Main Circuit 1000 V
Rated Frequency (f)
Main Circuit 50 / 60 Hz
Conventional Free-air Thermal Current (Ith)
acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 225 A
Rated Operational Current AC-1 (Ie)
(1000 V) 40 °C 225 A | (1000 V) 60 °C 200 A | (1000 V) 70 °C 175 A | (690 V) 40 °C 225 A | (690 V) 60 °C 200 A | (690 V) 70 °C 175 A
Rated Operational Current AC-3 (Ie)
(415 V) 60 °C 146 A | (440 V) 60 °C 146 A | (500 V) 60 °C 130 A | (690 V) 60 °C 93 A | (1000 V) 60 °C 60 A | (380 / 400 V) 60 °C 146 A | (220 / 230 / 240 V) 60 °C 146 A
Rated Operational Current AC-3e (Ie)
(415 V) 60 °C 146 A | (440 V) 60 °C 146 A | (500 V) 60 °C 130 A | (690 V) 60 °C 93 A | (1000 V) 60 °C 54 A | (380 / 400 V) 60 °C 146 A | (220 / 230 / 240 V) 60 °C 146 A
Rated Operational Power AC-3 (Pe)
(415 V) 75 kW | (440 V) 90 kW | (500 V) 90 kW | (690 V) 90 kW | (380 / 400 V) 75 kW | (220 / 230 / 240 V) 45 kW
Rated Operational Power AC-3e (Pe)
(415 V) 75 kW | (440 V) 90 kW | (500 V) 90 kW | (690 V) 90 kW | (1000 V) 75 kW | (380 / 400 V) 75 kW | (220 / 230 / 240 V) 45 kW
Rated Breaking Capacity AC-3
8 x Ie AC-3
Rated Breaking Capacity AC-3e
8.5 x Ie AC-3e
Rated Making Capacity AC-3
10 x Ie AC-3
Rated Making Capacity AC-3e
12 x Ie AC-3e
Rated Short-time Withstand Current Low Voltage (Icw)
at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 1168 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 225 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 477 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 1460 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 674 A
Maximum Breaking Capacity
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 3000 A | cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 1500 A
Rated Insulation Voltage (Ui)
acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 1000 V | acc. to UL/CSA 1000 V
Rated Impulse Withstand Voltage (Uimp)
Main Circuit 8 kV
Maximum Electrical Switching Frequency
(AC-1) 300 cycles per hour | (AC-2 / AC-4) 150 cycles per hour | (AC-3) 300 cycles per hour
Mechanical Durability
5 million
Maximum Mechanical Switching Frequency
300 cycles per hour
Rated Control Circuit Voltage (Uc)
50 Hz 220 ... 240 V | 60 Hz 220 ... 240 V
Coil Consumption
Holding at Max. Rated Control Circuit Voltage 50 Hz 8 V·A | Holding at Max. Rated Control Circuit Voltage 50 Hz 2.5 W | Holding at Max. Rated Control Circuit Voltage 60 Hz 8 V·A | Holding at Max. Rated Control Circuit Voltage 60 Hz 2.5 W | Pull-in at Max. Rated Control Circuit Voltage 50 Hz 130 V·A | Pull-in at Max. Rated Control Circuit Voltage 60 Hz 130 V·A
Power Loss
at Rated Operating Conditions AC-1 per Pole 23 W | at Rated Operating Conditions AC-3 per Pole 10 W
Operate Time
Between Coil De-energization and NO Contact Opening 15 ... 20 ms | Between Coil Energization and NO Contact Closing 20 ... 35 ms
Connecting Capacity Main Circuit
Flexible 2 x 10 ... 70 mm² | Rigid Cu-Cable 1 x 10 ... 95 mm²
Connecting Capacity Auxiliary Circuit
Flexible with Ferrule 1x 0.75 ... 2.5 mm² | Flexible with Ferrule 2x 0.75 ... 2.5 mm² | Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm² | Flexible with Insulated Ferrule 2x 0.75 ... 2.5 mm² | Flexible 1x 0.75 ... 2.5 mm² | Flexible 2x 0.75 ... 2.5 mm² | Solid 1x 1 ... 4 mm² | Solid 2x 1 ... 4 mm² | Stranded 1x 1 ... 4 mm² | Stranded 2x 1 ... 4 mm²
Connecting Capacity
Flexible 1 x 10 ... 70 mm² | Flexible 2 x 10 ... 70 mm² | Rigid Cu-Cable 1 x 10 ... 95 mm²
Wire Stripping Length
Auxiliary Circuit 9 mm | Control Circuit 9 mm
Degree of Protection
acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20 | acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP00
Recommended Screw Driver
Main Circuit M6 | Control Circuit M3.5
Tightening Torque
Auxiliary Circuit 1 N·m | Cable Lug 9 N·m | Control Circuit 1 N·m | Main Circuit 8 N·m
Terminal Type
Main Circuit: Bars
Product Name
Block Contactor
Maximum Operating Voltage UL/CSA
Main Circuit 1000 V
General Use Rating UL/CSA
(1000 V AC) 200 A
Horsepower Rating UL/CSA
(200 ... 208 V AC) Three Phase 40 hp | (220 ... 240 V AC) Three Phase 50 hp | (440 ... 480 V AC) Three Phase 100 hp | (550 ... 600 V AC) Three Phase 125 hp
Tightening Torque UL/CSA
Auxiliary Circuit 9 in·lb | Control Circuit 9 in·lb | Main Circuit 71 in·lb
Full Load Amps Motor Use
(200 ... 208 V AC) Three Phase 120 A | (220 ... 240 V AC) Three Phase 130 A | (440 ... 480 V AC) Three Phase 124 A | (550 ... 600 V AC) Three Phase 125 A
Ambient Air Temperature
Close to Contactor Fitted with Thermal O/L Relay (0.85 ... 1.1 Uc) -25 ... 55 °C | Close to Contactor without Thermal O/L Relay (0.85 ... 1.1 Uc) -40 ... 70 °C | Close to Contactor for Storage -40 ... 70 °C
Maximum Operating Altitude Permissible
Without Derating 3000 m
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
REACH Declaration
REACH - Letter of Confirmation for block contactors, contactor relays, installation contactors, mini contactors, mini contactor relays, thermal overload relays, electronic overload relays and related accessories
RoHS Information
RoHS II declaration for block contactors, installation contactors, mini contactors, mini contactor relays, thermal overload relays, electronic overload relays and related accessories
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration for Contactors
WEEE B2C / B2B
Business To Business
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
ABB EcoSolutions
Yes
ABB Site Meeting Group Waste To Landfill Target
Non-hazardous waste is sent to a landfill, where there is no alternative option available within 100km of a facility
End Of Life Disassembling Instructions
End-of-life instruction - AF(S)116(B)-**(RT) to AF(S)205(B)-**(RT)
Environmental Product Declaration - EPD
Environmental Product Declaration, AF(S)116-AF(S)146 (SE) Contactors
Improved Energy Efficiency for Customers
Product Efficiency - Product requires less energy to operate compared to similar product on market or older products from the same line
Recyclability Rate of the Product acc. to EN45555
Design for Closing Resource Loops - Standard EN45555 - 87.8 %
Sustainable Material Content in Product (wt. %)
Recycled Metal - 37 %
A2L Certificate – UL
UL Certificate of Compliance A2L, Contactor, AF116 - AF146
Declaration of Conformity - CE
CE Declaration of Conformity - Contactor - AF116...AF370
Declaration of Conformity - UKCA
UK Declaration of Conformity - Contactors >100A
UL Certificate
cULus Certificate, Contactor, AF116-30...AF146-30, AFS116-30...AFS146-30
Package Level 1 Units
box 1 piece
Package Level 1 Width
207 mm
Package Level 1 Depth / Length
216 mm
Package Level 1 Height
150 mm
Package Level 1 Gross Weight
1.5 kg
Package Level 1 EAN
7320500560877
Object Classification Code
Q
ETIM 7
EC000066 - Power contactor, AC switching
ETIM 8
EC000066 - Power contactor, AC switching
ETIM 9
EC000066 - Power contactor, AC switching
eClass
V11.0 : 27371003
UNSPSC
39121529
IDEA Granular Category Code (IGCC)
4758 >> Iec Contactors
Feature: AF technology with built‑in surge protection delivers faster coil response and reduced switching transients. Impact: lowers energy waste and panel heat, improving overall efficiency and reliability in networks prone to voltage fluctuations. Application: ideal for motor control in conveyors, pumps, and fans across industrial automation environments. Feature: Three-pole design with 1000 V main circuit rating enables direct control of demanding motors up to 75 kW. Impact: supports higher power density and simplifies panel layouts by eliminating external contactors. Application: primary motor starters in material handling, water treatment, and process automation lines. Feature: Rated operational currents across AC-1 and AC-3, and AC-3e, at 40–70 °C, ensure dependable performance in varied ambient temperatures. Impact: reduces downtime due to overheating or overcurrent and extends service life. Application: equipment operating in hot plants or unconditioned environments. Feature: Modular architecture compatible with add‑on auxiliary contact blocks for scalable control. Impact: enables interlocking, status feedback, and expanded logic without replacing the base unit. Application: machine safety circuits, sequencing, and PLC I/O expansion projects. Feature: Energy-efficient coil and low power loss, including hold and pull-in values, minimize heat in control cabinets. Impact: lowers energy costs and improves thermal management in large installations. Application: continuous energization of control circuits in multi‑pack automation setups. Feature: Flexible wiring options for main and auxiliary circuits and clearly defined torque and terminations. Impact: reduces wiring time, supports mixed conductor types, and ensures reliable connections. Application: panel builders retrofitting legacy systems or designing new installations with diverse wiring standards. Feature: Certifications and environmental compliance, including UL/CSA and CE, plus RoHS and REACH; protective IP ratings IP20 on coil and IP00 on main terminals. Impact: ensures global market acceptance and durable operation in dusty environments. Application: projects deployed across multiple regions requiring standardized safety and sustainability.

Get a Quick Quote for a ABB 1SFL467002R4300

Chat with us on WhatsApp - fast responses guaranteed

Need to speak with someone? We'll call you back within 2 hours during business hours

Interested in ABB 1SFL467002R4300? Enquire Now

FAQs

The device supports Flexible main circuit connections of 2 x 10-70 mm² and rigid Cu-Cable 1 x 10-95 mm². Auxiliary circuits accept Flexible with Ferrule 0.75-2.5 mm² or solid/stranded 1-4 mm². Wire stripping length for auxiliary and control circuits is 9 mm. Tightening torques are 8 N·m for main, 1 N·m for auxiliary and control circuits, with M6 fittings for the main circuit.
Rated operational power and current for AC-3 include up to 146 A at 690 V and up to 75 kW at applicable voltages, with AC-3e ratings at higher multiples. The unit is designed for AC-3 duty in motor control applications, providing robust breaking/making and reliable cycling in 415–690 V three‑phase systems.
Yes. It is rated for ambient temperatures from -25 °C to 55 °C with a design that accommodates up to 70 °C in certain configurations. The device maintains performance with rated insulation and protection ratings, reducing the risk of nuisance trips in hot industrial spaces.
The 1SFL467002R4300 carries UL/CSA and CE certifications, plus RoHS and REACH declarations. Its protection ratings include IP20 on coil terminals and IP00 on main terminals, with documented ETIM and EN classifications supporting global procurement and compliance.
Expect reduced downtime due to AF fast-operating coils and built‑in surge protection, lower energy use from optimized coil consumption, and easier scalability with add-on auxiliary blocks. The rugged construction, long mechanical life, and modular design translate to lower maintenance costs and faster project payback in high‑volume automation environments.