ABB 1SFL487002R4200 Block Contactor - 1000 V
Part Number: 1SFL487002R4200
Quick Summary
ABB 1SFL487002R4200 Block Contactor is a 3-pole motor starter for reliable control of AC motors up to 90 kW. In real-world panels, inconsistencies in switching can create energy waste and heat, impacting uptime in modern industrial facilities. This product carries CE and UKCA declarations, UL/CSA approvals, RoHS compliance, with IP20 coil protection to ensure safe operation. Designed for easy integration with add-on auxiliary contact blocks and CAD models, it reduces installation risk, accelerates commissioning, and supports scalable automation. With AF technology and built-in surge protection, you gain faster operations and energy efficiency, lowering total cost of ownership.
Product Information
Extended Description
1SFL487002R4200 ABB: The AF190-30-00-42 is a 3 pole - 1000 V IEC or 600 V UL contactor with Main Circuit Bars, controlling motors up to 90 kW / 400 V AC (AC-3) or 125 hp / 480 V UL and switching power circuits up to 275 A (AC-1) or 250 A UL general use. Thanks to the AF technology, the contactor has a control voltage range (110-120 V 50/60 Hz),faster operation time, reducing panel energy consumptions and ensuring distinct operations in unstable networks. Furthermore, surge protection is built-in, offering a compact solution. AF contactors have a block type design, can be easily extended with add-on auxiliary contact blocks and an additional wide range of accessories.
Minimum Order Quantity
1 piece
Customs Tariff Number
8536490099
Data Sheet, Technical Information
1SBC100214C0202 - Main catalog Motor protection and control Manual motor starters, contactors and overload relays (PDF) - Edition 2024
Data Sheet, Technical Information (Part 2)
Contactors and Overload relays guide
Instructions and Manuals
Operating instruction, Contactor, AF(S)190 ... AF(S)370
CAD Dimensional Drawing
Information - 2D and 3D files for CAD systems
Product Net Width
105 mm
Product Net Depth / Length
152 mm
Product Net Height
196 mm
Product Net Weight
2.4 kg
Number of Main Contacts NO
3
Number of Main Contacts NC
0
Number of Auxiliary Contacts NO
0
Number of Auxiliary Contacts NC
0
Number of Poles
3P
Rated Operational Voltage
Main Circuit 1000 V
Rated Frequency (f)
Main Circuit 50 / 60 Hz
Conventional Free-air Thermal Current (Ith)
acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 275 A
Rated Operational Current AC-1 (Ie)
(1000 V) 40 °C 250 A | (1000 V) 60 °C 225 A | (1000 V) 70 °C 185 A | (690 V) 40 °C 275 A | (690 V) 60 °C 250 A | (690 V) 70 °C 200 A
Rated Operational Current AC-3 (Ie)
(415 V) 60 °C 190 A | (440 V) 60 °C 190 A | (500 V) 60 °C 156 A | (690 V) 60 °C 135 A | (1000 V) 60 °C 85 A | (380 / 400 V) 60 °C 190 A | (220 / 230 / 240 V) 60 °C 190 A
Rated Operational Current AC-3e (Ie)
(415 V) 60 °C 190 A | (440 V) 60 °C 190 A | (500 V) 60 °C 135 A | (690 V) 60 °C 135 A | (1000 V) 60 °C 85 A | (380 / 400 V) 60 °C 190 A | (220 / 230 / 240 V) 60 °C 190 A
Rated Operational Power AC-3 (Pe)
(415 V) 90 kW | (440 V) 110 kW | (500 V) 110 kW | (690 V) 132 kW | (1000 V) 110 kW | (380 / 400 V) 90 kW | (220 / 230 / 240 V) 55 kW
Rated Operational Power AC-3e (Pe)
(415 V) 90 kW | (440 V) 110 kW | (500 V) 110 kW | (690 V) 132 kW | (1000 V) 110 kW | (380 / 400 V) 90 kW | (220 / 230 / 240 V) 55 kW
Rated Breaking Capacity AC-3
8 x Ie AC-3
Rated Breaking Capacity AC-3e
8.5 x Ie AC-3e
Rated Making Capacity AC-3
10 x Ie AC-3
Rated Making Capacity AC-3e
12 x Ie AC-3e
Rated Short-time Withstand Current Low Voltage (Icw)
at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 1520 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 275 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 621 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 1900 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 878 A
Maximum Breaking Capacity
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 3300 A | cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 2200 A
Rated Insulation Voltage (Ui)
acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 1000 V | acc. to UL/CSA 1000 V
Rated Impulse Withstand Voltage (Uimp)
Main Circuit 8 kV
Maximum Electrical Switching Frequency
(AC-1) 300 cycles per hour | (AC-2 / AC-4) 150 cycles per hour | (AC-3) 300 cycles per hour
Mechanical Durability
5 million
Maximum Mechanical Switching Frequency
300 cycles per hour
Rated Control Circuit Voltage (Uc)
50 Hz 110 ... 120 V | 60 Hz 110 ... 120 V
Coil Consumption
Holding at Max. Rated Control Circuit Voltage 50 Hz 6 V·A | Holding at Max. Rated Control Circuit Voltage 50 Hz 2 W | Holding at Max. Rated Control Circuit Voltage 60 Hz 6 V·A | Holding at Max. Rated Control Circuit Voltage 60 Hz 2 W | Pull-in at Max. Rated Control Circuit Voltage 50 Hz 180 V·A | Pull-in at Max. Rated Control Circuit Voltage 60 Hz 180 V·A
Power Loss
at Rated Operating Conditions AC-1 per Pole 15 W | at Rated Operating Conditions AC-3 per Pole 7 W
Operate Time
Between Coil De-energization and NO Contact Opening 15 ... 30 ms | Between Coil Energization and NO Contact Closing 20 ... 35 ms
Connecting Capacity Auxiliary Circuit
Flexible with Ferrule 1x 0.75 ... 2.5 mm² | Flexible with Ferrule 2x 0.75 ... 2.5 mm² | Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm² | Flexible with Insulated Ferrule 2x 0.75 ... 2.5 mm² | Flexible 1x 0.75 ... 2.5 mm² | Flexible 2x 0.75 ... 2.5 mm² | Solid 1x 1 ... 4 mm² | Solid 2x 1 ... 4 mm² | Stranded 1x 1 ... 4 mm² | Stranded 2x 1 ... 4 mm²
Connecting Capacity
Flexible 2 x 50 ... 95 mm² | Rigid Al-Cable 1 x 95 ... 185 mm² | Rigid Cu-Cable 1 x 6 ... 150 mm²
Wire Stripping Length
Auxiliary Circuit 9 mm | Control Circuit 9 mm
Degree of Protection
acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20 | acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP00
Recommended Screw Driver
Main Circuit M8 | Control Circuit M3.5
Tightening Torque
Auxiliary Circuit 1 N·m | Cable Lug 18 N·m | Control Circuit 1 N·m | Main Circuit 14 ... 31 N·m
Terminal Type
Main Circuit: Bars
Product Name
Block Contactor
Maximum Operating Voltage UL/CSA
Main Circuit 1000 V
General Use Rating UL/CSA
(1000 V AC) 250 A
Horsepower Rating UL/CSA
(200 ... 208 V AC) Three Phase 50 hp | (220 ... 240 V AC) Three Phase 60 hp | (440 ... 480 V AC) Three Phase 125 hp | (550 ... 600 V AC) Three Phase 150 hp
Tightening Torque UL/CSA
Auxiliary Circuit 9 in·lb | Control Circuit 9 in·lb | Main Circuit 301 in·lb
Full Load Amps Motor Use
(200 ... 208 V AC) Three Phase 150 A | (220 ... 240 V AC) Three Phase 154 A | (440 ... 480 V AC) Three Phase 156 A | (550 ... 600 V AC) Three Phase 144 A
Ambient Air Temperature
Close to Contactor Fitted with Thermal O/L Relay (0.85 ... 1.1 Uc) -25 ... 55 °C | Close to Contactor without Thermal O/L Relay (0.85 ... 1.1 Uc) -40 ... 70 °C | Close to Contactor for Storage -40 ... 70 °C
Maximum Operating Altitude Permissible
Without Derating 3000 m
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
REACH Declaration
REACH - Letter of Confirmation for block contactors, contactor relays, installation contactors, mini contactors, mini contactor relays, thermal overload relays, electronic overload relays and related accessories
RoHS Information
RoHS II declaration for block contactors, installation contactors, mini contactors, mini contactor relays, thermal overload relays, electronic overload relays and related accessories
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration for Contactors
WEEE B2C / B2B
Business To Business
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
ABB EcoSolutions
Yes
ABB Site Meeting Group Waste To Landfill Target
Non-hazardous waste is sent to a landfill, where there is no alternative option available within 100km of a facility
End Of Life Disassembling Instructions
End-of-life instruction - AF(S)116(B)-**(RT) to AF(S)205(B)-**(RT)
Environmental Product Declaration - EPD
Environmental Product Declaration, AF190-AF205 (SE) Contactors
Improved Energy Efficiency for Customers
Product Efficiency - Product requires less energy to operate compared to similar product on market or older products from the same line
Recyclability Rate of the Product acc. to EN45555
Design for Closing Resource Loops - Standard EN45555 - 79.2 %
Sustainable Material Content in Product (wt. %)
Recycled Metal - 35 %
A2L Certificate – UL
UL Certificate of Compliance A2L, Contactor, AF190 - AF370
Declaration of Conformity - CE
CE Declaration of Conformity - Contactor - AF116...AF370
Declaration of Conformity - UKCA
UK Declaration of Conformity - Contactors >100A
UL Certificate
cULus Certificate, Contactor, AF190-30, AF205-30, AFS190-30, AFS205-30
Package Level 1 Units
box 1 piece
Package Level 1 Width
160 mm
Package Level 1 Depth / Length
258 mm
Package Level 1 Height
235 mm
Package Level 1 Gross Weight
3 kg
Package Level 1 EAN
7320500560907
Object Classification Code
Q
ETIM 7
EC000066 - Power contactor, AC switching
ETIM 8
EC000066 - Power contactor, AC switching
ETIM 9
EC000066 - Power contactor, AC switching
eClass
V11.0 : 27371003
UNSPSC
39121529
IDEA Granular Category Code (IGCC)
4758 >> Iec Contactors
The 3-pole main circuit design delivers robust performance for AC-1 and AC-3 duty, enabling reliable motor control with a compact footprint, which reduces panel size and wiring complexity while improving heat management. This is coupled with a 1000 V rated main circuit and a coil voltage range of 110-120 V at 50/60 Hz, delivering consistent actuation in varying supply conditions and unstable networks. The built-in surge protection minimizes nuisance trips and equipment wear, extending lifecycle for drives and pumps in demanding environments. The AF technology supports faster operate times (15-30 ms) and lower energy consumption per cycle, translating to measurable energy savings and lower maintenance costs. Compatibility with add-on auxiliary contact blocks and CAD files simplifies configuration, testing, and scalable automation in applications such as conveyors, fans, and customer-specified motor drives. Block contactor construction with main circuit bars enables straightforward integration with rigid Al/Cu cable lugs, while the IP20/ IP00 protection levels provide resilient installing and servicing in factory settings. ABB’s EcoSolutions approach emphasizes energy efficiency and recyclability, helping meet sustainability targets while maintaining high reliability. With a 90 kW equivalent performance at relevant voltages, these contactors are suitable for mid-to-large industrial motors, delivering predictable start-up behavior and long service life in demanding production lines.
Get a Quick Quote for a ABB 1SFL487002R4200
Chat with us on WhatsApp - fast responses guaranteed
Need to speak with someone? We'll call you back within 2 hours during business hours
Interested in ABB 1SFL487002R4200?
Enquire Now
FAQs
Yes. The AF190 family is designed for easy extension with add-on auxiliary contact blocks. This enables you to tailor signaling for start/stop logic, overloads, and remote monitoring while keeping the main circuit in a compact, single assembly. Ensure the chosen auxiliary blocks match coil voltage and terminal spacing to maintain compliance and reliability.
For 1000 V mains, AC-1 current is rated up to 250 A (40 °C), while AC-3 current is 190 A (60 °C) and 185 A (70 °C) depending on temperature. The unit provides practical motor-starting capability up to ~90 kW at 415 V and 110 kW at 690–1000 V, with appropriate short-time withstand and breaking capacities.
Yes. The product carries CE and UKCA declarations, UL/CSA certification, and RoHS compliance. It also aligns with EN safety standards for block contactors and includes a RoHS declaration and REACH information, making it suitable for regulated industrial environments and cross-border deployments.
The unit measures 105 mm in net width, 152 mm in net depth, and 196 mm in net height, with a net weight of 2.4 kg. This compact footprint supports dense panel layouts and simplifies cable routing, while the 3P configuration aligns with typical three-phase motor installations.
Mechanical durability is rated at 5 million operations, with operating times for coil actuation between 15 and 30 ms. Regular maintenance should focus on ensuring clean terminals, verifying torque on main circuit connections, and inspecting for heat or sign of wear. The built-in surge protection reduces contact wear and prolongs overall reliability in variable network conditions.