ABB 1SFL487102R1322 Contactor - UL/CSA 1000V CE
Part Number: 1SFL487102R1322
Quick Summary
ABB 1SFL487102R1322 Contactor is a four-pole device for motor control up to 90 kW at 400 V AC. It’s engineered to tolerate wide control-voltage variations, reducing panel energy use and preventing trips in networks with fluctuations. The AF technology provides built-in surge protection and a broad control-circuit range, enabling operation from 100 to 250 V AC or DC and easy extension with auxiliary blocks. With CE and UL/CSA certifications, plus UKCA, RoHS and REACH declarations, this cont actor supports global deployment. The compact form factor and pre-mounted main circuit bars simplify installation while preserving safety and reliability in demanding industrial environments.
Product Information
Extended Description
1SFL487102R1322 ABB: The AF190-40-22-13 is a 4 pole - 1000 V IEC or 600 V UL contactor with pre-mounted auxiliary contacts and Main Circuit Bars, controlling motors up to 90 kW / 400 V AC (AC-3) / and switching power circuits up to 275 A (AC-1) or 230 A UL general use. Thanks to the AF technology, the contactor has a wide control voltage range (100-250 V 50/60 Hz and DC), managing large control voltage variations, reducing panel energy consumptions and ensuring distinct operations in unstable networks. Furthermore, surge protection is built-in, offering a compact solution. AF contactors have a block type design, can be easily extended with add-on auxiliary contact blocks and an additional wide range of accessories.
Minimum Order Quantity
1 piece
Customs Tariff Number
85364900
Data Sheet, Technical Information
1SBC100214C0202 - Main catalog Motor protection and control Manual motor starters, contactors and overload relays (PDF) - Edition 2024
Data Sheet, Technical Information (Part 2)
Contactors and Overload relays guide
Instructions and Manuals
Operating instruction, Contactor, AF(S)190 ... AF(S)370
CAD Dimensional Drawing
Information - 2D and 3D files for CAD systems
Dimension Diagram
Dimension Drawing. Contactor,AF190,AF205
Product Net Width
140 mm
Product Net Depth / Length
153 mm
Product Net Height
196 mm
Product Net Weight
3.3 kg
Number of Main Contacts NO
4
Number of Main Contacts NC
0
Number of Auxiliary Contacts NO
2
Number of Auxiliary Contacts NC
2
Number of Poles
4P
Rated Operational Voltage
Main Circuit 1000 V
Rated Frequency (f)
Main Circuit 60 Hz
Conventional Free-air Thermal Current (Ith)
acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 275 A
Rated Operational Current AC-1 (Ie)
(1000 V) 40 °C 250 A | (1000 V) 55 °C 225 A | (1000 V) 60 °C 225 A | (1000 V) 70 °C 185 A | (690 V) 40 °C 275 A | (690 V) 55 °C 250 A | (690 V) 60 °C 250 A | (690 V) 70 °C 200 A
Rated Operational Current AC-3 (Ie)
(415 V) 55 °C 190 A | (440 V) 55 °C 190 A | (380 / 400 V) 55 °C 190 A | (220 / 230 / 240 V) 55 °C 190 A
Rated Operational Power AC-3 (Pe)
(415 V) 90 kW | (440 V) 110 kW | (380 / 400 V) 90 kW | (220 / 230 / 240 V) 55 kW
Rated Breaking Capacity AC-3
8 x Ie AC-3
Rated Making Capacity AC-3
10 x Ie AC-3
Short-Circuit Protective Devices
gG Type Fuses 355 A
Rated Short-time Withstand Current Low Voltage (Icw)
at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 1520 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 275 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 621 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 1900 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 878 A
Maximum Breaking Capacity
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 3300 A
Rated Insulation Voltage (Ui)
acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 1000 V | acc. to UL/CSA 1000 V
Rated Impulse Withstand Voltage (Uimp)
Main Circuit 8 kV
Maximum Electrical Switching Frequency
(AC-1) 300 cycles per hour
Mechanical Durability
5 million
Maximum Mechanical Switching Frequency
300 cycles per hour
Coil Operating Limits
(acc. to IEC 60947-4-1) 0.85 x Uc Min. ... 1.1 x Uc Max. (at θ ≤ 70 °C)
Rated Control Circuit Voltage (Uc)
50 Hz 100 ... 250 V | 60 Hz 100 ... 250 V | DC Operation 100 ... 250 V
Coil Consumption
Holding at Max. Rated Control Circuit Voltage 50 Hz 7 V·A | Holding at Max. Rated Control Circuit Voltage 60 Hz 7 V·A | Holding at Max. Rated Control Circuit Voltage DC 2.5 W | Pull-in at Max. Rated Control Circuit Voltage 50 Hz 220 V·A | Pull-in at Max. Rated Control Circuit Voltage 60 Hz 220 V·A | Pull-in at Max. Rated Control Circuit Voltage DC 190 W
Power Loss
15 W | at Rated Operating Conditions per Pole 15 W
Operate Time
Between Coil De-energization and NO Contact Opening 45 ... 80 ms | Between Coil Energization and NO Contact Closing 25 ... 60 ms
Connecting Capacity Main Circuit
Flexible 2 x 50 ... 95 mm² | Rigid Al-Cable 1 x 95 ... 185 mm² | Rigid Cu-Cable 2 x 50 ... 120 mm²
Connecting Capacity Auxiliary Circuit
Flexible with Ferrule 2x 0.75 ... 2.5 mm² | Flexible with Insulated Ferrule 2x 0.75 ... 2.5 mm² | Flexible 2x0.75 ... 2.5 mm² | Solid 2 x 1 ... 4 mm² | Stranded 1 x 1 .... 4 mm²
Degree of Protection
acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20 | acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP00
Tightening Torque
Cable Lug 18 N·m | Main Circuit 14 ... 31 N·m
Terminal Type
Main Circuit: Bars
Product Name
Block Contactor
Maximum Operating Voltage UL/CSA
Main Circuit 1000 V
General Use Rating UL/CSA
(1000 V AC) 250 A
Horsepower Rating UL/CSA
(200 ... 208 V AC) Three Phase 20 Hp | (200 V AC) Three Phase 50 hp | (208 V AC) Three Phase 50 hp | (220 ... 240 V AC) Three Phase 25 Hp | (220 ... 240 V AC) Three Phase 60 hp | (440 ... 480 V AC) Three Phase 60 Hp | (440 ... 480 V AC) Three Phase 125 hp | (550 ... 600 V AC) Three Phase 75 Hp | (550 ... 600 V AC) Three Phase 150 hp
Ambient Air Temperature
Close to Contactor Fitted with Thermal O/L Relay (0.85 ... 1.1 Uc) -25 ... 50 °C | Close to Contactor without Thermal O/L Relay (0.85 ... 1.1 Uc) -40 ... 70 °C | Close to Contactor for Storage -40 ... 70 °C
Maximum Operating Altitude Permissible
Without Derating 3000 m
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
REACH Declaration
REACH - Letter of Confirmation for block contactors, contactor relays, installation contactors, mini contactors, mini contactor relays, thermal overload relays, electronic overload relays and related accessories
RoHS Information
RoHS II declaration for block contactors, installation contactors, mini contactors, mini contactor relays, thermal overload relays, electronic overload relays and related accessories
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration for Contactors
WEEE B2C / B2B
Business To Business
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
ABB EcoSolutions
Yes
ABB Site Meeting Group Waste To Landfill Target
Non-hazardous waste is sent to a landfill, where there is no alternative option available within 100km of a facility
End Of Life Disassembling Instructions
End-of-life instruction - AF(S)116(B)-**(RT) to AF(S)205(B)-**(RT)
Environmental Product Declaration - EPD
Environmental Product Declaration, AF190-AF205 (SE) Contactors
Improved Energy Efficiency for Customers
Product Efficiency - Product requires less energy to operate compared to similar product on market or older products from the same line
Recyclability Rate of the Product acc. to EN45555
Design for Closing Resource Loops - Standard EN45555 - 79.2 %
Sustainable Material Content in Product (wt. %)
Recycled Metal - 35 %
ABS Certificate
ABS Approval, Contactor, AF116 ... AF370 (Sweden)
BV Certificate
BV Certificate, Contactor, AF116-30 ... AF370-30...AF116-40...AF370-40
CB Certificate
SEMKO_SE-77322
CQC Certificate
CQC Certificate, AC Contactor, AF190-*-*-*, AF205-*-*-*, AF190B-*-*-*, AF205B-*-*-*, AFS190-30-*-*, AFS205-30-*-*, Made in Sweden
Declaration of Conformity - CCC
CCC Declaration of Conformity, AC Contactor, AF190-*-*-*, AF205-*-*-*, AF190B-*-*-*, AF205B-*-*-*, AFS190-30-*-*, AFS205-30-*-*, Made in Sweden
Declaration of Conformity - CE
CE Declaration of Conformity - Contactor - AF116B...RT to AF370B...RT
Declaration of Conformity - UKCA
UK Declaration of Conformity - Contactors >100A
EAC Certificate
9AKK107046A8618
LR Certificate
Lloyds register Certificate, Contactor, AF116-30 ... AF370-30, AF116-40...AF370-40
PRS Certificate
PRS Certificate - AF116...AF1650
RINA Certificate
RINA Certificate, AF95, AF110, AF145, AF185, AF210, AF260, AF300, AF400, AF460, AF580, AF750, AF1250, AF1350, AF1650, AF2050, AF2650, AF116, AF140, AF146, AF190, AF205, AF265, AF305, AF370
RMRS Certificate
9AKK107045A6978
UL Certificate
cULus Certificate, Contactor, AF190-40, AF205-40 (4-pole)
Package Level 1 Units
box 1 piece
Package Level 1 Width
166 mm
Package Level 1 Depth / Length
238 mm
Package Level 1 Height
180 mm
Package Level 1 Gross Weight
3.9 kg
Package Level 1 EAN
7320500504284
Object Classification Code
Q
ETIM 7
EC000066 - Power contactor, AC switching
ETIM 8
EC000066 - Power contactor, AC switching
ETIM 9
EC000066 - Power contactor, AC switching
eClass
V11.0 : 27371003
UNSPSC
39121529
IDEA Granular Category Code (IGCC)
4758 >> Iec Contactors
E-Number (Finland)
3707187
Feature AF technology and wide control voltage range → Business Impact Enables reliable motor control across fluctuating supply conditions, reducing nuisance trips and energy waste in industrial panels. Application suited to machine builders and panel miners seeking robust performance in variable networks. The design accepts 100–250 V AC/DC signals and remains stable under voltage swings, lowering commissioning time and energy footprint. Feature Built-in surge protection and compact block design → Business Impact Improves protection against transient spikes while saving cabinet space and reducing the need for additional surge devices. Application ideal for compact control panels in automotive, packaging, and material handling lines. Feature Pre-mounted main circuit bars and IP20 coil terminals → Business Impact Simplifies assembly and wiring, cutting installation time by standardizing connections. Application benefits include faster certified wiring and easier field service. Feature 4 NO main contacts with 2 NO and 2 NC auxiliary contacts → Business Impact Enhances interlocking, signaling, and control logic without external add-ons. Application suitable for motor start circuits with integrated signaling. Feature Rated electrical data and mechanical durability → Business Impact Delivers predictable long-term performance with Ie up to 250 A (AC-1) and 190 A (AC-3) at 400–440 V, and 5 million mechanical cycles. Application supports high-reliability applications in continuous operation environments. Feature Compatibility with main circuit bars, flexible 2 x 50–95 mm² and rigid Al/Cu options → Business Impact Provides flexible wiring and secure terminating options, reducing installation complexity. Application enables fast integration with diverse harnesses and cables in control panels.
Get a Quick Quote for a ABB 1SFL487102R1322
Chat with us on WhatsApp - fast responses guaranteed
Need to speak with someone? We'll call you back within 2 hours during business hours
Interested in ABB 1SFL487102R1322?
Enquire Now
FAQs
The AF190-40-22-13 is a 4-pole cont actor rated for main circuit voltage up to 1000 V and 60 Hz. It provides AC-3 current up to 190 A (at 415–440–380–400 V) and AC-1 up to 250 A, enabling motor control up to 90 kW. It also features 8 x Ie short‑circuit capacity and a 4 NO main contact configuration with 2 NO/2 NC auxiliaries.
Yes. It is rated for AC-3 motor loads with Ie of 190 A at 400 V (55 °C). It can deliver up to 90 kW at 415–440 V, making it suitable for common drives and motor applications in European networks. The device uses 4 NO main contacts and includes built-in auxiliary contacts for interlocking and signaling.
The coil supports a broad control range of 100–250 V for both AC (50/60 Hz) and DC operation. Coil currents vary with voltage and mode, including pull-in and holding values (e.g., 190 W pull-in at rated voltage and 7 W holding at rated voltage), enabling stable operation with wide supply tolerances.
The AF190-40-22-13 carries CE and UL/CSA certifications, and UKCA markings, along with RoHS and REACH declarations. Additional certifications include EAC, BV, ABS, Lloyd’s, and UL listings for specific variants. These align with global compliance requirements for industrial equipment and enable broad deployment.
It features pre-mounted main circuit bars, compact 140 mm width, 153 mm depth, and 196 mm height, and a 3.3 kg weight for easy handling. Terminal connections include IP20 coil terminals and IP00 main terminals, with specified tightening torques and compatible cable cross-sections, reducing wiring time and ensuring robust, code-compliant installations.