ABB 1SFL501074R8411 Block Contactor - CE/UL, 690V

Part Number: 1SFL501074R8411
Manufacturer
ABB
Part number
1SFL501074R8411

Quick Summary

ABB 1SFL501074R8411 Contactor is a rugged power-switching device for motor control in industrial automation. Engineers rely on it to reliably start and interrupt high-current motors in demanding environments. This block contactor ships with CE and UL certifications, plus RoHS and REACH declarations, ensuring global compliance and traceability across the supply chain. Selecting the right device often becomes a bottleneck due to voltage/current mismatches or enclosure constraints; this model combines high-rated performance with compact dimensions to reduce design risk. By consolidating ratings, auxiliary contacts, and a standard control voltage into one part, procurement and maintenance become simpler, faster, and more cost-efficient for OEMs and service teams alike.

Product Information

Extended Description

1SFL501074R8411 ABB: AX205-30-11-84 Contactor
Minimum Order Quantity
1 piece
Customs Tariff Number
85364900
Data Sheet, Technical Information
1SBC100214C0202 - Main catalog Motor protection and control Manual motor starters, contactors and overload relays (PDF) - Edition 2024
Instructions and Manuals
AX 185~205A instructions
CAD Dimensional Drawing
Information - 2D and 3D files for CAD systems
Product Net Width
111.5 mm
Product Net Depth / Length
162.3 mm
Product Net Height
196 mm
Product Net Weight
3.2 kg
Number of Main Contacts NO
3
Number of Main Contacts NC
0
Number of Auxiliary Contacts NO
1
Number of Auxiliary Contacts NC
1
Number of Poles
3P
Rated Operational Voltage
Main Circuit 1000 V
Rated Frequency (f)
Main Circuit 60 Hz
Conventional Free-air Thermal Current (Ith)
acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 250 A
Rated Operational Current AC-1 (Ie)
(690 V) 40 °C 275 A | (690 V) 55 °C 250 A | (690 V) 70 °C 180 A
Rated Operational Current AC-3 (Ie)
(415 V) 55 °C 205 A | (440 V) 55 °C 185 A | (500 V) 55 °C 170 A | (690 V) 55 °C 170 A | (380 / 400 V) 55 °C 205 A | (220 / 230 / 240 V) 55 °C 205 A
Rated Operational Power AC-3 (Pe)
(415 V) 110 kW | (440 V) 90 kW | (500 V) 110 kW | (690 V) 132 kW | (380 / 400 V) 110 kW | (220 / 230 / 240 V) 59 kW
Rated Breaking Capacity AC-3
8 x Ie AC-3
Rated Making Capacity AC-3
10 x Ie AC-3
Rated Short-time Withstand Current Low Voltage (Icw)
at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 1200 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 280 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 600 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 1800 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 800 A
Rated Insulation Voltage (Ui)
acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 690 V
Rated Impulse Withstand Voltage (Uimp)
8 kV
Maximum Electrical Switching Frequency
300 cycles per hour
Mechanical Durability
5 million
Maximum Mechanical Switching Frequency
3600 cycles per hour
Coil Operating Limits
(acc. to IEC 60947-4-1) Uc (at θ ≤ 70 °C)
Rated Control Circuit Voltage (Uc)
50 Hz 110 V | 60 Hz 110 ... 120 V
Power Loss
at Rated Operating Conditions per Pole 5 W
Degree of Protection
acc. to IEC 60529, IEC 60947-1, EN 60529 Auxiliary Terminals IP40
Terminal Type
Main Circuit: Bars
Product Name
Block Contactor
Ambient Air Temperature
Close to Contactor Fitted with Thermal O/L Relay (0.85 ... 1.1 Uc) -25 ... 55 °C | Close to Contactor without Thermal O/L Relay (0.85 ... 1.1 Uc) -40 ... 70 °C | Close to Contactor for Storage -40 ... 70 °C
Maximum Operating Altitude Permissible
Without Derating 3000 m
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
REACH Declaration
REACH - Letter of Confirmation for block contactors, contactor relays, installation contactors, mini contactors, mini contactor relays, thermal overload relays, electronic overload relays and related accessories
RoHS Information
RoHS II declaration for block contactors, installation contactors, mini contactors, mini contactor relays, thermal overload relays, electronic overload relays and related accessories
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration for Contactors
WEEE B2C / B2B
Business To Business
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
CQC Certificate
CQC Certificate, Contactor, AX185, AX205, Made in China
Declaration of Conformity - CCC
CCC Declaration of Conformity, Contactor, AX185, AX205, Made in China
Declaration of Conformity - CE
CE Declaration of conformity - Contactor - AX95...AX370
UL Certificate
cULus Certificate, Contactor, A145...A185, AX185...AX205
Package Level 1 Units
box 1 piece
Package Level 1 Width
180 mm
Package Level 1 Depth / Length
245 mm
Package Level 1 Height
175 mm
Package Level 1 Gross Weight
3.8 kg
Package Level 1 EAN
7320500500316
Object Classification Code
Q
ETIM 7
EC000066 - Power contactor, AC switching
ETIM 8
EC000066 - Power contactor, AC switching
ETIM 9
EC000066 - Power contactor, AC switching
eClass
V11.0 : 27371003
UNSPSC
39121529
IDEA Granular Category Code (IGCC)
4755 >> Contactors
Feature: Three-pole construction with 3 NO main contacts and 1 NO + 1 NC auxiliary contact. Benefit: Delivers dependable motor switching for AC-3 duty while enabling auxiliary signaling for control circuits. Application: Suitable for pumps, fans, and conveyors in factories where reliable handover between running and stopped states is critical. Feature: Rated main circuit voltage up to 1000 V and rated frequency at 60 Hz. Benefit: Supports diverse industrial power networks with proven insulation and switching performance, reducing component counts in multi-voltage installations. Application: Ideal for global equipment designed for mixed-voltage environments. Feature: I_e and P_e across voltages (AC-3 up to 205 A at 415–380/400 V, up to 170 A at higher voltages). Benefit: Accurate sizing minimizes overdimensioning and boosts energy efficiency. Application: Motor starters in packaging lines and material-handling systems. Feature: Short-time withstand and mechanical life ratings (Icw up to 1800 A for short bursts, 5 million mechanical cycles). Benefit: Improves uptime and predictability in high-cycle production lines. Application: Continuous operation in automated machining centers. Feature: Compact dimensions (111.5 mm wide, 162.3 mm deep, 196 mm high) and weight (3.2 kg). Benefit: Easier panel integration and reduced enclosure footprint. Application: OEM dashboards and control cabinets with space constraints. Feature: Control coil options (50 Hz 110 V; 60 Hz 110–120 V). Benefit: Flexible system integration with common control voltages and fast time-to-start. Application: Integrated with standard PLC/relay control schemes. Feature: Robust certifications and environmental compliance (CE, UL, RoHS, REACH, WEEE). Benefit: Rapid regulatory approval across markets and simplified supplier audits. Application: Global deployments in manufacturing, food & beverage, and automotive sectors.

Get a Quick Quote for a ABB 1SFL501074R8411

Chat with us on WhatsApp - fast responses guaranteed

Need to speak with someone? We'll call you back within 2 hours during business hours

Interested in ABB 1SFL501074R8411? Enquire Now

FAQs

Install the 3-pole mains side using the main circuit terminals (Bars) with the auxiliary contacts wired for feedback signals. Ensure the coil is supplied with the correct control voltage (50 Hz 110 V or 60 Hz 110–120 V) and verify ambient temperatures stay within -25 to 70 °C. Follow the dimensional envelope (111.5 mm width, 162.3 mm depth, 196 mm height) and use appropriate mounting hardware to maintain IP40 protection.
AC-3 ratings vary by voltage: up to 205 A at 415 V or 380/400 V, 205 A at 220/230/240 V; 185 A at 440 V; 170 A at 500–690 V. Power handling reaches up to 132 kW at upper voltage ranges. Icw values ensure short-time withstands up to 1200–1800 A depending on duration, with a rated insulation voltage of 690 V.
Yes. The 3P block contactor is designed for AC-3 duty with adequate Ie ratings and a robust impulse withstand. Its 3 NO main contacts plus a single NO/NC auxiliary contact support control schemes for motor starters in conveyors and pumps, while the 50/60 Hz coil options align with standard PLC-based control architectures.
This model includes CE and UL certifications, plus RoHS and REACH declarations, with CCC documentation available for select regions. These certifications confirm regulatory compliance, support global market access, and simplify supplier audits and chain-of-custody verification for regulated industries.
With a mechanical durability of about 5 million cycles and up to 3600 cycles per hour, the unit offers long life in high-demand lines, reducing replacement downtime. Its compact form factor and integrated auxiliary contacts lower BOM complexity, while CE/UL and RoHS/REACH compliance minimize regulatory risk and spare-part variability, contributing to lower total cost of ownership.