ABB 1SFL527102R1211 Contactor - UL/CE Listed, 4P
Part Number: 1SFL527102R1211
Quick Summary
AF205-40-11-12 Contactor is a four-pole power switch designed for motor control in industrial panels. In modern facilities, voltage fluctuations and control-logic variability can cause nuisance trips and wasted energy; this device is engineered to tolerate wide control voltages and provide reliable operation across fluctuating networks. The product carries CE conformity and UL/cULus listings, with coil-terminal protection rated IP20 and main-terminals protected IP00, supporting safe, compliant installations. Its modular AF technology enables easy expansion with add-on auxiliary blocks, reducing panel space and wiring complexity. For engineers and procurement teams, this combination translates to lower lifecycle costs, improved uptime, and scalable control solutions in automation projects.
Product Information
Extended Description
1SFL527102R1211 ABB: The AF205-40-11-12 is a 4 pole - 1000 V IEC or 600 V UL contactor with pre-mounted auxiliary contacts and Main Circuit Bars, controlling motors up to 110 kW / 400 V AC (AC-3) / and switching power circuits up to 350 A (AC-1) or 250 A UL general use. Thanks to the AF technology, the contactor has a wide control voltage range (48-130 V 50/60 Hz and DC), managing large control voltage variations, reducing panel energy consumptions and ensuring distinct operations in unstable networks. Furthermore, surge protection is built-in, offering a compact solution. AF contactors have a block type design, can be easily extended with add-on auxiliary contact blocks and an additional wide range of accessories.
Minimum Order Quantity
1 piece
Customs Tariff Number
85364900
Data Sheet, Technical Information
1SBC100214C0202 - Main catalog Motor protection and control Manual motor starters, contactors and overload relays (PDF) - Edition 2024
Data Sheet, Technical Information (Part 2)
Contactors and Overload relays guide
Instructions and Manuals
Operating instruction, Contactor, AF(S)190 ... AF(S)370
CAD Dimensional Drawing
Information - 2D and 3D files for CAD systems
Dimension Diagram
Dimension Drawing. Contactor,AF190,AF205
Product Net Width
140 mm
Product Net Depth / Length
152.5 mm
Product Net Height
195.6 mm
Product Net Weight
3.3 kg
Number of Main Contacts NO
4
Number of Main Contacts NC
0
Number of Auxiliary Contacts NO
1
Number of Auxiliary Contacts NC
1
Number of Poles
4P
Rated Operational Voltage
Main Circuit 1000 V
Rated Frequency (f)
Main Circuit 60 Hz
Conventional Free-air Thermal Current (Ith)
acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 350 A
Rated Operational Current AC-1 (Ie)
(1000 V) 40 °C 275 A | (1000 V) 60 °C 250 A | (1000 V) 70 °C 200 A | (690 V) 40 °C 350 A | (690 V) 60 °C 300 A | (690 V) 70 °C 240 A
Rated Operational Current AC-3 (Ie)
(415 V) 55 °C 205 A | (440 V) 55 °C 205 A | (380 / 400 V) 55 °C 205 A | (220 / 230 / 240 V) 55 °C 205 A
Rated Operational Power AC-3 (Pe)
(415 V) 110 kW | (440 V) 132 kW | (380 / 400 V) 110 kW | (220 / 230 / 240 V) 55 kW
Rated Breaking Capacity AC-3
8 x Ie AC-3
Rated Making Capacity AC-3
10 x Ie AC-3
Short-Circuit Protective Devices
gG Type Fuses 400 A
Rated Short-time Withstand Current Low Voltage (Icw)
at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 1640 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 350 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 670 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 2050 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 947 A
Maximum Breaking Capacity
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 3500 A
Rated Insulation Voltage (Ui)
acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 1000 V | acc. to UL/CSA 1000 V
Rated Impulse Withstand Voltage (Uimp)
Main Circuit 8 kV
Maximum Electrical Switching Frequency
(AC-1) 300 cycles per hour
Mechanical Durability
5 million
Maximum Mechanical Switching Frequency
300 cycles per hour
Coil Operating Limits
(acc. to IEC 60947-4-1) 0.85 x Uc Min. ... 1.1 x Uc Max. (at θ ≤ 70 °C)
Rated Control Circuit Voltage (Uc)
50 Hz 48 ... 130 V | 60 Hz 48 ... 130 V | DC Operation 48 ... 130 V
Coil Consumption
Holding at Max. Rated Control Circuit Voltage 50 Hz 4 V·A | Holding at Max. Rated Control Circuit Voltage 60 Hz 4 V·A | Holding at Max. Rated Control Circuit Voltage DC 2.5 W | Pull-in at Max. Rated Control Circuit Voltage 50 Hz 180 V·A | Pull-in at Max. Rated Control Circuit Voltage 60 Hz 180 V·A | Pull-in at Max. Rated Control Circuit Voltage DC 150 W
Power Loss
at Rated Operating Conditions per Pole 25 W
Operate Time
Between Coil De-energization and NO Contact Opening 45 ... 80 ms | Between Coil Energization and NO Contact Closing 25 ... 60 ms
Connecting Capacity Main Circuit
Flexible 1 x 6 ... 120 mm² | Rigid Cu-Cable 2 x 50 ... 120 mm²
Connecting Capacity Auxiliary Circuit
Flexible with Ferrule 2x 0.75 ... 2.5 mm² | Flexible with Insulated Ferrule 2x 0.75 ... 2.5 mm² | Flexible 2x0.75 ... 2.5 mm² | Solid 2 x 1 ... 4 mm² | Stranded 2 x 1 .... 4 mm²
Degree of Protection
acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20 | acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP00
Tightening Torque
Cable Lug 18 N·m | Main Circuit 14 ... 31 N·m
Terminal Type
Main Circuit: Bars
Product Name
Block Contactor
Maximum Operating Voltage UL/CSA
Main Circuit 1000 V
General Use Rating UL/CSA
(1000 V AC) 275 A
Horsepower Rating UL/CSA
(200 ... 208 V AC) Three Phase 30 Hp | (200 V AC) Three Phase 60 hp | (208 V AC) Three Phase 60 hp | (220 ... 240 V AC) Three Phase 30 Hp | (220 ... 240 V AC) Three Phase 75 hp | (440 ... 480 V AC) Three Phase 75 Hp | (440 ... 480 V AC) Three Phase 150 hp | (550 ... 600 V AC) Three Phase 100 Hp | (550 ... 600 V AC) Three Phase 200 hp
Ambient Air Temperature
Close to Contactor Fitted with Thermal O/L Relay (0.85 ... 1.1 Uc) -25 ... 50 °C | Close to Contactor without Thermal O/L Relay (0.85 ... 1.1 Uc) -40 ... 70 °C | Close to Contactor for Storage -40 ... 70 °C
Maximum Operating Altitude Permissible
Without Derating 3000 m
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
REACH Declaration
REACH - Letter of Confirmation for block contactors, contactor relays, installation contactors, mini contactors, mini contactor relays, thermal overload relays, electronic overload relays and related accessories
RoHS Information
RoHS II declaration for block contactors, installation contactors, mini contactors, mini contactor relays, thermal overload relays, electronic overload relays and related accessories
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration for Contactors
WEEE B2C / B2B
Business To Business
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
ABB EcoSolutions
Yes
ABB Site Meeting Group Waste To Landfill Target
Non-hazardous waste is sent to a landfill, where there is no alternative option available within 100km of a facility
End Of Life Disassembling Instructions
End-of-life instruction - AF(S)116(B)-**(RT) to AF(S)205(B)-**(RT)
Environmental Product Declaration - EPD
Environmental Product Declaration, AF190-AF205 (SE) Contactors
Improved Energy Efficiency for Customers
Product Efficiency - Product requires less energy to operate compared to similar product on market or older products from the same line
Recyclability Rate of the Product acc. to EN45555
Design for Closing Resource Loops - Standard EN45555 - 79.2 %
Sustainable Material Content in Product (wt. %)
Recycled Metal - 35 %
ABS Certificate
ABS Approval, Contactor, AF116 ... AF370 (Sweden)
BV Certificate
BV Certificate, Contactor, AF116-30 ... AF370-30...AF116-40...AF370-40
CB Certificate
SEMKO_SE-77322
CQC Certificate
CQC Certificate, AC Contactor, AF190-*-*-*, AF205-*-*-*, AF190B-*-*-*, AF205B-*-*-*, AFS190-30-*-*, AFS205-30-*-*, Made in Sweden
Declaration of Conformity - CCC
CCC Declaration of Conformity, AC Contactor, AF190-*-*-*, AF205-*-*-*, AF190B-*-*-*, AF205B-*-*-*, AFS190-30-*-*, AFS205-30-*-*, Made in Sweden
Declaration of Conformity - CE
CE Declaration of Conformity - Contactor - AF116B...RT to AF370B...RT
Declaration of Conformity - UKCA
UK Declaration of Conformity - Contactors >100A
EAC Certificate
9AKK107046A8618
LR Certificate
Lloyds register Certificate, Contactor, AF116-30 ... AF370-30, AF116-40...AF370-40
PRS Certificate
PRS Certificate - AF116...AF1650
RINA Certificate
RINA Certificate, AF95, AF110, AF145, AF185, AF210, AF260, AF300, AF400, AF460, AF580, AF750, AF1250, AF1350, AF1650, AF2050, AF2650, AF116, AF140, AF146, AF190, AF205, AF265, AF305, AF370
RMRS Certificate
9AKK107045A6978
UL Certificate
cULus Certificate, Contactor, AF190-40, AF205-40 (4-pole)
Package Level 1 Units
box 1 piece
Package Level 1 Width
166 mm
Package Level 1 Depth / Length
238 mm
Package Level 1 Height
180 mm
Package Level 1 Gross Weight
3.9 kg
Package Level 1 EAN
7320500503713
Object Classification Code
Q
ETIM 7
EC000066 - Power contactor, AC switching
ETIM 8
EC000066 - Power contactor, AC switching
ETIM 9
EC000066 - Power contactor, AC switching
eClass
V11.0 : 27371003
UNSPSC
39121529
IDEA Granular Category Code (IGCC)
4758 >> Iec Contactors
E-Number (Finland)
3707199
E-Number (Norway)
3210330
E-Number (Sweden)
3210330
Feature: Four-pole block contactor with integrated main circuit bars enables high-power motor switching up to 110 kW at typical 400 V AC-3 loads. Business Impact: Delivers robust motor control with compact footprint, reducing panel width and wiring complexity in conveyors, pumps, and fans. Application: Suitable for AC-3 duty in demanding industrial environments. Long-tail keywords: 4-pole motor contactor, high-power contactor, AF technology, main circuit bars. Feature → Business Impact → Application. Feature: Wide control circuit voltage range 48–130 V (AC/50/60 Hz) and DC operation lowers energy waste from voltage variations. Business Impact: Stable coil operation, fewer false trips, lower control energy consumption. Application: Control panels with variable supply conditions. Long-tail keywords: wide coil voltage, energy-efficient contactor, DC operation. Feature: Built-in surge protection and AF-series extendable design with add-on auxiliary blocks. Business Impact: Enhanced reliability, easier modernization, reduced replacement cycles. Application: Modular control architectures in small to mid-size panels. Long-tail keywords: surge protection, auxiliary contact blocks, modular contactor. Feature: Compact dimensions, IP20 coil terminals and IP00 main terminals with controlled torque. Business Impact: Fast, secure installation with predictable maintenance; compatibility with standard lugs and torque specs. Application: Tight panel spaces and retrofit projects. Long-tail keywords: IP20 coil terminals, IP00 main terminals, tightening torque. Feature: Mechanical durability 5 million cycles and rated insulation up to 1000 V. Business Impact: Long service life, lower maintenance costs, improved total cost of ownership. Application: Heavy-duty automation environments. Long-tail keywords: mechanical durability, insulation voltage, high-cycle contactor.
Get a Quick Quote for a ABB 1SFL527102R1211
Chat with us on WhatsApp - fast responses guaranteed
Need to speak with someone? We'll call you back within 2 hours during business hours
Interested in ABB 1SFL527102R1211?
Enquire Now
FAQs
This 4P block contactor uses main circuit bars for the primary connections and supports flexible conductor ranges up to 120 mm². Mounting should align with the device's 140 mm width, 152.5 mm depth, and 195.6 mm height, with a tightening torque of 14–31 N·m on main circuit connections and 18 N·m for cable lugs. Ensure coil terminals are wired to 48–130 V control voltage (AC or DC) and maintain IP20 protection on the coil side.
The coil provides a wide range: 48–130 V for AC at 50/60 Hz and 48–130 V for DC operation. This tolerance helps manage voltage variations in unstable networks, reducing nuisance trips and enabling a more robust control circuit without frequent panel adjustments.
AC-1 rated current at 1000 V is up to 275 A (40 °C) and down to 250 A at 60 °C, while AC-3 current is about 205 A across relevant voltages (415–440 V). Rated AC-3 power ranges from 110 kW (415 V) to 132 kW (440 V) for typical motor applications, with lower values at 220–240 V, reflecting standard IEC 60947-4-1 performance.
This contactor carries CE conformity, UL/cULus listing, and RoHS/REACH declarations. It also supports IP protection for coil terminals (IP20) and main terminals (IP00), aligning with global electrical protection and circuit control standards for safe integration in automated systems.
Long-term durability (up to 5 million mechanical cycles), built-in surge protection, and a modular AF design reduce maintenance costs and replacement intervals. The wide coil range minimizes energy waste from supply fluctuations, while compatibility with add-on auxiliary blocks supports scalable, cost-effective modernization and improved equipment uptime.