ABB AF265-40-22-12 Contactor - 1000 V IEC 60947-4-1
Part Number: 1SFL547102R1222
Quick Summary
ABB AF265-40-22-12 Contactor is a four-pole motor switch for 400 V drives and industrial equipment. In unstable networks, voltage variation wastes energy and undermines reliability; AF technology tolerates a wide control voltage range (48–130 V), reducing panel energy consumption, heat generation, and erratic operation. It carries CE and UL/CSA approvals, plus UKCA and EAC listings to support global deployment. Designed for easy panel integration, pre-mounted auxiliary contacts (NO/NC) and optional add-on blocks enable scalable motor protection and control. This combination lowers total cost of ownership, simplifies commissioning, and offers robust performance in demanding industrial environments.
Product Information
Extended Description
1SFL547102R1222 ABB: The AF265-40-22-12 is a 4 pole - 1000 V IEC or 600 V UL contactor with pre-mounted auxiliary contacts and Main Circuit Bars, controlling motors up to 132 kW / 400 V AC (AC-3) / and switching power circuits up to 400 A (AC-1) or 300 A UL general use. Thanks to the AF technology, the contactor has a wide control voltage range (48-130 V 50/60 Hz and DC), managing large control voltage variations, reducing panel energy consumptions and ensuring distinct operations in unstable networks. Furthermore, surge protection is built-in, offering a compact solution. AF contactors have a block type design, can be easily extended with add-on auxiliary contact blocks and an additional wide range of accessories.
Minimum Order Quantity
1 piece
Customs Tariff Number
85364900
Data Sheet, Technical Information
1SBC100214C0202 - Main catalog Motor protection and control Manual motor starters, contactors and overload relays (PDF) - Edition 2024
Data Sheet, Technical Information (Part 2)
Contactors and Overload relays guide
Instructions and Manuals
Operating instruction, Contactor, AF(S)190 ... AF(S)370
CAD Dimensional Drawing
Information - 2D and 3D files for CAD systems
Dimension Diagram
Dimension Drawing. Contactor,AF265,AF305,AF370
Product Net Width
184 mm
Product Net Depth / Length
180 mm
Product Net Height
225 mm
Product Net Weight
5.7 kg
Number of Main Contacts NO
4
Number of Main Contacts NC
0
Number of Auxiliary Contacts NO
2
Number of Auxiliary Contacts NC
2
Number of Poles
4P
Rated Operational Voltage
Main Circuit 1000 V
Rated Frequency (f)
Main Circuit 60 Hz
Conventional Free-air Thermal Current (Ith)
acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 400 A
Rated Operational Current AC-1 (Ie)
(1000 V) 40 °C 350 A | (1000 V) 60 °C 300 A | (1000 V) 70 °C 240 A | (690 V) 40 °C 400 A | (690 V) 60 °C 350 A | (690 V) 70 °C 290 A
Rated Operational Current AC-3 (Ie)
(415 V) 55 °C 265 A | (440 V) 55 °C 265 A | (500 V) 55 °C 250 A | (690 V) 55 °C 250 A | (380 / 400 V) 55 °C 265 A | (220 / 230 / 240 V) 55 °C 265 A
Rated Operational Power AC-3 (Pe)
(415 V) 132 kW | (440 V) 160 kW | (380 / 400 V) 132 kW | (220 / 230 / 240 V) 75 kW
Rated Breaking Capacity AC-3
8 x Ie AC-3
Rated Making Capacity AC-3
10 x Ie AC-3
Short-Circuit Protective Devices
gG Type Fuses 630 A
Rated Short-time Withstand Current Low Voltage (Icw)
at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 2120 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 400 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 865 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 2650 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 1224 A
Maximum Breaking Capacity
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 3800 A
Rated Insulation Voltage (Ui)
acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 1000 V | acc. to UL/CSA 1000 V
Rated Impulse Withstand Voltage (Uimp)
Main Circuit 8 kV
Maximum Electrical Switching Frequency
(AC-1) 300 cycles per hour
Mechanical Durability
5 million
Maximum Mechanical Switching Frequency
300 cycles per hour
Coil Operating Limits
(acc. to IEC 60947-4-1) 0.85 x Uc Min. ... 1.1 x Uc Max. (at θ ≤ 70 °C)
Rated Control Circuit Voltage (Uc)
50 Hz 48 ... 130 V | 60 Hz 48 ... 130 V | DC Operation 48 ... 130 V
Coil Consumption
Holding at Max. Rated Control Circuit Voltage 50 Hz 17 V·A | Holding at Max. Rated Control Circuit Voltage 60 Hz 17 V·A | Holding at Max. Rated Control Circuit Voltage DC 2.5 W | Pull-in at Max. Rated Control Circuit Voltage 50 Hz 180 V·A | Pull-in at Max. Rated Control Circuit Voltage 60 Hz 180 V·A | Pull-in at Max. Rated Control Circuit Voltage DC 150 W
Power Loss
32 W | at Rated Operating Conditions per Pole 32 W
Operate Time
Between Coil De-energization and NO Contact Opening 45 ... 80 ms | Between Coil Energization and NO Contact Closing 30 ... 60 ms
Connecting Capacity Main Circuit
Flexible 2 x 70 ... 185 mm² | Rigid Al-Cable 1 x 185 ... 240 mm² | Rigid Cu-Cable 2 x 70 ... 185 mm²
Connecting Capacity Auxiliary Circuit
Flexible with Ferrule 2x 0.75 ... 2.5 mm² | Flexible with Insulated Ferrule 2x 0.75 ... 2.5 mm² | Flexible 2x0.75 ... 2.5 mm² | Solid 2 x 1 ... 4 mm² | Stranded 1 x 1 .... 4 mm²
Degree of Protection
acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20 | acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP00
Tightening Torque
Cable Lug 28 N·m | Main Circuit 22 ... 43 N·m
Terminal Type
Main Circuit: Bars
Product Name
Block Contactor
NEMA Size
5
Horsepower Rating NEMA
(200 V AC) Three Phase 75 Hp | (230 V AC) Three Phase 100 Hp | (460 V AC) Three Phase 200 Hp | (575 V AC) Three Phase 200 Hp
Maximum Operating Voltage UL/CSA
Main Circuit 1000 V
General Use Rating UL/CSA
(1000 V AC) 350 A
Horsepower Rating UL/CSA
(200 ... 208 V AC) Three Phase 40 Hp | (200 V AC) Three Phase 75 hp | (208 V AC) Three Phase 75 hp | (220 ... 240 V AC) Three Phase 40 Hp | (220 ... 240 V AC) Three Phase 100 hp | (440 ... 480 V AC) Three Phase 100 Hp | (440 ... 480 V AC) Three Phase 200 hp | (550 ... 600 V AC) Three Phase 125 Hp | (550 ... 600 V AC) Three Phase 250 hp
Ambient Air Temperature
Close to Contactor Fitted with Thermal O/L Relay (0.85 ... 1.1 Uc) -25 ... 50 °C | Close to Contactor without Thermal O/L Relay (0.85 ... 1.1 Uc) -40 ... 70 °C | Close to Contactor for Storage -40 ... 70 °C
Maximum Operating Altitude Permissible
Without Derating 3000 m
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
REACH Declaration
REACH - Letter of Confirmation for block contactors, contactor relays, installation contactors, mini contactors, mini contactor relays, thermal overload relays, electronic overload relays and related accessories
RoHS Information
RoHS II declaration for block contactors, installation contactors, mini contactors, mini contactor relays, thermal overload relays, electronic overload relays and related accessories
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration for Contactors
WEEE B2C / B2B
Business To Business
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
ABB EcoSolutions
Yes
ABB Site Meeting Group Waste To Landfill Target
Non-hazardous waste is sent to a landfill, where there is no alternative option available within 100km of a facility
End Of Life Disassembling Instructions
End-of-life instruction - AF(S)265(B)-**(RT) to AF(S)370(B)-**(RT)
Environmental Product Declaration - EPD
Environmental Product Declaration, Contactors, AF(S)265-AF(S)370 (SE)
Improved Energy Efficiency for Customers
Product Efficiency - Product considered more energy-efficient compared to similar product on market or older products from the same line
Recyclability Rate of the Product acc. to EN45555
Design for Closing Resource Loops - Standard EN45555 - 76.3 %
Sustainable Material Content in Product (wt. %)
Recycled Metal - 33 %
A2L Certificate – UL
UL Certificate of Compliance A2L, Contactor, AF190 - AF370
ABS Certificate
ABS Approval, Contactor, AF116 ... AF370 (Sweden)
BV Certificate
BV Certificate, Contactor, AF116-30 ... AF370-30...AF116-40...AF370-40
CB Certificate
SEMKO_SE-73326
CQC Certificate
CQC Certificate, AC Contactor, AF265-*-*-*,AF305-*-*-*,AF370-*-*-*,AF265B-*-*-*,AF305B-*-*-*,AF370B-*-*-*, Made in Sweden
Declaration of Conformity - CCC
CCC Declaration of Conformity, AC Contactor, AF265-*-*-*,AF305-*-*-*,AF370-*-*-*,AF265B-*-*-*,AF305B-*-*-*,AF370B-*-*-*, Made in Sweden
Declaration of Conformity - CE
CE Declaration of Conformity - Contactor - AF116...AF370
Declaration of Conformity - UKCA
UK Declaration of Conformity - Contactors >100A
EAC Certificate
9AKK107046A8618
KC Certificate
KC Certificate, Contactor, AF265-40 (Sweden)
LR Certificate
Lloyds register Certificate, Contactor, AF116-30 ... AF370-30, AF116-40...AF370-40
PRS Certificate
PRS Certificate - AF116...AF1650
RINA Certificate
RINA Certificate, AF95, AF110, AF145, AF185, AF210, AF260, AF300, AF400, AF460, AF580, AF750, AF1250, AF1350, AF1650, AF2050, AF2650, AF116, AF140, AF146, AF190, AF205, AF265, AF305, AF370
RMRS Certificate
9AKK107045A6978
UL Certificate
cULus Certificate, Contactor, AF265-40, AF305-40, AF370-40 (4-pole)
Package Level 1 Units
box 1 piece
Package Level 1 Width
212 mm
Package Level 1 Depth / Length
262 mm
Package Level 1 Height
212 mm
Package Level 1 Gross Weight
6.4 kg
Package Level 1 EAN
7320500505144
Object Classification Code
Q
ETIM 7
EC000066 - Power contactor, AC switching
ETIM 8
EC000066 - Power contactor, AC switching
ETIM 9
EC000066 - Power contactor, AC switching
eClass
V11.0 : 27371003
UNSPSC
39121529
IDEA Granular Category Code (IGCC)
4758 >> Iec Contactors
E-Number (Finland)
3707224
Feature: AF technology provides a wide control voltage range (48–130 V) for a more stable control signal across fluctuating networks. Business Impact: Reduces energy waste and panel heating, improving overall machine efficiency. Application: Suitable for variable-speed drives and standard motor starters in manufacturing lines. Feature: Built-in surge protection and high insulation margin enhance reliability in harsh environments. Business Impact: Minimizes nuisance tripping and unplanned downtime, lowering maintenance costs. Application: Critical in conveyors and processing equipment with rapidly changing loads. Feature: Pre-mounted auxiliary contacts and main circuit bars simplify installation. Business Impact: Faster commissioning, compact panel layouts, and easier field servicing. Application: Ideal for control cabinets requiring clean, modular wiring. Feature: AF265 series allows easy expansion with add-on auxiliary blocks. Business Impact: Scalable protection for future plant upgrades and change management. Application: Pharmaceutical, food & beverage, and automotive assembly lines needing flexible configurations. Feature: High power rating supports motors up to 132 kW (AC-3) at 400 V. Business Impact: Reduces the number of devices required, saving space and reducing system complexity. Application: Heavy-duty pumps and large fans in HVAC and process industries. Feature: Coil operating limits (0.85–1.1 Uc) and broad ambient tolerance support dependable operation. Business Impact: Maintains performance under temperature swings and continuous duty. Application: Equipment housed in diverse installations from control rooms to outdoor enclosures. Feature: Comprehensive certifications (CE, UL/CSA, UKCA, EAC) enable global procurement. Business Impact: Streamlines supplier audits and international projects. Application: Global OEM deployments with stringent regulatory requirements.
Get a Quick Quote for a ABB 1SFL547102R1222
Chat with us on WhatsApp - fast responses guaranteed
Need to speak with someone? We'll call you back within 2 hours during business hours
Interested in ABB 1SFL547102R1222?
Enquire Now
FAQs
The AF265-40-22-12 is ideal for four-pole motor control in 400 V AC drives, conveyors, pumps, and machine tools. Its pre-mounted auxiliary contacts and main circuit bars simplify panel integration, while the AF technology supports voltage variation tolerance, enabling reliable operation in imperfect networks and reducing energy waste.
Key specs include a main circuit rated up to 1000 V and AC-3 power switching up to 132 kW, with Ie around 265 A at 415–690 V. The coil accepts 48–130 V AC or DC, with characteristic pull-in and hold values (about 180 VA pull-in, 17 VA hold at rated voltage). These features support robust motor starting and control.
Yes. The AF265-40-22-12 carries CE and UL/CSA approvals and is listed with UKCA and EAC where applicable, supporting global deployment and supplier qualification across multinational projects in sectors like manufacturing, water treatment, and packaging.
Installation is accelerated by pre-mounted main circuits and auxiliary contacts, reducing wiring time and panel footprint. The device’s modularity allows add-on contact blocks, enabling future expansion without reworking cabinets. The combination of high reliability and reduced downtime translates into lower lifecycle costs and faster project payback.
Absolutely. The AF265-40-22-12 supports add-on auxiliary blocks and accessories, enabling tailored protection schemes for different loads. This flexibility is valuable for scalable automation projects, helping to align protection levels with evolving motor loads, switching frequencies, and energy-management goals.