ABB AF750-30-22-68 Block Contactor - 1000 V IEC/UL

Part Number: 1SFL637001R6822
Manufacturer
ABB
Part number
1SFL637001R6822

Quick Summary

ABB AF750-30-22-68 block contactor enables robust motor control in automation applications. It addresses panel uptime by delivering stable operation despite voltage fluctuations and load variations. With built-in surge protection and a wide control voltage range of 24–60 V DC, it minimizes panel energy waste and reduces wiring complexity. This device is certified for CE and UL/CSA listings, and it features IP20 coil terminals with IP00 main terminals, underscoring reliability in harsh industrial environments. Coupled with RoHS and REACH compliance, it supports sustainable, compliant installations. As a versatile, extendable solution, it integrates easily with add-on auxiliary blocks and standard ABB AF accessories, delivering long-term cost savings and simpler maintenance.

Product Information

Extended Description

1SFL637001R6822 ABB: The AF750-30-22-68 is a 3 pole - 1000 V IEC or 600 V UL contactor with pre-mounted auxiliary contacts and Main Circuit Bars, controlling motors up to 400 kW / 400 V AC (AC-3) or 600 hp / 480 V UL and switching power circuits up to 1050 A (AC-1) or 900 A UL general use. Thanks to the AF technology, the contactor has a wide control voltage range (24-60 V DC), managing large control voltage variations, reducing panel energy consumptions and ensuring distinct operations in unstable networks. Furthermore, surge protection is built-in, offering a compact solution. AF contactors have a block type design, can be easily extended with add-on auxiliary contact blocks and an additional wide range of accessories.
Country of Origin
India (IN)
Made To Order
No
Product Sales Status
Active
Quote Only
No
Stocked At Warehouses
INABB010EXPU
Warranty Return
Product under warranty must be returned
Minimum Order Quantity
1 piece
Customs Tariff Number
85364900
Data Sheet, Technical Information
1SBC100214C0202 - Main catalog Motor protection and control Manual motor starters, contactors and overload relays (PDF) - Edition 2024
Data Sheet, Technical Information (Part 2)
Contactors and Overload relays guide
Instructions and Manuals
1SFC380023-en
CAD Dimensional Drawing
Information - 2D and 3D files for CAD systems
Dimension Diagram
53540919-60
Product Net Width
210 mm
Product Net Depth / Length
242 mm
Product Net Height
283 mm
Product Net Weight
13.6 kg
Number of Main Contacts NO
3
Number of Main Contacts NC
0
Number of Auxiliary Contacts NO
2
Number of Auxiliary Contacts NC
2
Number of Poles
3P
Rated Operational Voltage
Main Circuit 1000 V
Rated Frequency (f)
Main Circuit 50 / 60 Hz
Conventional Free-air Thermal Current (Ith)
acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 1050 A
Rated Operational Current AC-1 (Ie)
(1000 V) 40 °C 1000 A | (1000 V) 55 °C 875 A | (1000 V) 70 °C 720 A | (690 V) 40 °C 1050 A | (690 V) 55 °C 875 A | (690 V) 70 °C 720 A
Rated Operational Current AC-3 (Ie)
(415 V) 55 °C 750 A | (440 V) 55 °C 750 A | (500 V) 55 °C 750 A | (690 V) 55 °C 650 A | (1000 V) 55 °C 300 A | (380 / 400 V) 55 °C 750 A | (220 / 230 / 240 V) 55 °C 750 A
Rated Operational Current DC-1 (Ie)
(110 V) 1-Pole, 40 °C 1050 A | (110 V) 2 Poles in Series, 40 °C 1050 A | (220 V) 3 Poles in Series, 40 °C 1050 A | (600 V) 3 Poles in Series, 40 °C 1050 A | (850 V) 3 Poles in Series, 40 °C 1050 A
Rated Operational Current DC-3 (Ie)
(110 V) 1-Pole, 40 °C 1050 A | (110 V) 2 Poles in Series, 40 °C 1050 A | (220 V) 3 Poles in Series, 40 °C 1050 A | (600 V) 3 Poles in Series, 40 °C 1050 A
Rated Operational Current DC-5 (Ie)
(110 V) 1-Pole, 40 °C 1050 A | (110 V) 2 Poles in Series, 40 °C 1050 A | (220 V) 3 Poles in Series, 40 °C 1050 A | (600 V) 3 Poles in Series, 40 °C 1050 A
Rated Operational Power AC-3 (Pe)
(415 V) 425 kW | (440 V) 450 kW | (500 V) 520 kW | (690 V) 600 kW | (1000 V) 400 kW | (380 / 400 V) 400 kW | (220 / 230 / 240 V) 220 kW
Rated Breaking Capacity AC-3
8 x Ie AC-3
Rated Making Capacity AC-3
10 x Ie AC-3
Short-Circuit Protective Devices
gG Type Fuses 1000 A
Rated Short-time Withstand Current Low Voltage (Icw)
at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 6400 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 1300 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 3500 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 7000 A | at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 4500 A
Maximum Breaking Capacity
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 7500 A | cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 7000 A
Rated Insulation Voltage (Ui)
acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 1000 V | acc. to UL/CSA 600 V
Rated Impulse Withstand Voltage (Uimp)
Main Circuit 8 kV
Maximum Electrical Switching Frequency
(AC-1) 300 cycles per hour | (AC-2 / AC-4) 60 cycles per hour | (AC-3) 300 cycles per hour
Mechanical Durability
3 million
Maximum Mechanical Switching Frequency
300 cycles per hour
Coil Operating Limits
(acc. to IEC 60947-4-1) 0.85 x Uc Min. ... 1.1 x Uc Max. (at θ ≤ 70 °C)
Rated Control Circuit Voltage (Uc)
DC Operation 24 ... 60 V
Coil Consumption
Holding at Max. Rated Control Circuit Voltage 50 Hz 12 V·A | Holding at Max. Rated Control Circuit Voltage 60 Hz 12 V·A | Holding at Max. Rated Control Circuit Voltage DC 5.5 V·A | Pull-in at Max. Rated Control Circuit Voltage 50 Hz 780 V·A | Pull-in at Max. Rated Control Circuit Voltage 60 Hz 780 V·A | Pull-in at Max. Rated Control Circuit Voltage DC 785 V·A
Power Loss
at Rated Operating Conditions per Pole 50 W
Operate Time
Between Coil De-energization and NC Contact Closing 50 ... 70 ms | Between Coil De-energization and NO Contact Opening 53 ... 73 ms | Between Coil Energization and NC Contact Opening 45 ... 115 ms | Between Coil Energization and NO Contact Closing 50 ... 120 ms
Connecting Capacity Main Circuit
Bar 52 mm² | Rigid Al-Cable 300 mm² | Rigid Cu-Cable 300 mm²
Connecting Capacity Auxiliary Circuit
Flexible with Ferrule 2x 0.75 ... 2.5 mm² | Flexible with Insulated Ferrule 2x 0.75 ... 2.5 mm² | Flexible 1x0.75 ... 2.5 mm² | Solid 2 x 1 ... 4 mm² | Stranded 2 x 1 .... 4 mm²
Connecting Capacity
Bar 52 mm² | Rigid Al-Cable 3x185 mm² | Rigid Cu-Cable 300 mm²
Degree of Protection
acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20 | acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP00
Tightening Torque
Cable Lug 45 N·m | Main Circuit 45 N·m
Terminal Type
Main Circuit: Bars
Product Name
Block Contactor
NEMA Size
7
Horsepower Rating NEMA
(230 V AC) Three Phase 300 Hp | (460 V AC) Three Phase 600 Hp | (575 V AC) Three Phase 600 Hp
Maximum Operating Voltage UL/CSA
Main Circuit 1000 V
General Use Rating UL/CSA
(1000 V AC) 900 A | (600 V AC) 900 A
Horsepower Rating UL/CSA
(200 V AC) Three Phase 250 hp | (208 V AC) Three Phase 250 hp | (220 ... 240 V AC) Three Phase 300 hp | (440 ... 480 V AC) Three Phase 600 hp | (550 ... 600 V AC) Three Phase 700 hp
Full Load Amps Motor Use
(440 ... 480 V AC) Three Phase 722 A | (550 ... 600 V AC) Three Phase 672 A
Ambient Air Temperature
Close to Contactor Fitted with Thermal O/L Relay (0.85 ... 1.1 Uc) -25 ... 50 °C | Close to Contactor without Thermal O/L Relay (0.85 ... 1.1 Uc) -40 ... 70 °C | Close to Contactor for Storage -40 ... 70 °C
Maximum Operating Altitude Permissible
Without Derating 3000 m
Resistance to Shock acc. to IEC 60068-2-27
Shock Direction: A 5 g | Shock Direction: B1 5 g | Shock Direction: B2 5 g | Shock Direction: C1 5 g | Shock Direction: C2 5 g
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
REACH Declaration
REACH - Letter of Confirmation for block contactors, contactor relays, installation contactors, mini contactors, mini contactor relays, thermal overload relays, electronic overload relays and related accessories
RoHS Information
RoHS II declaration for block contactors, installation contactors, mini contactors, mini contactor relays, thermal overload relays, electronic overload relays and related accessories
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration for Contactors
WEEE B2C / B2B
Business To Business
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
End Of Life Disassembling Instructions
End-of-life instruction - AF(S)580(B)-**;AF(S)750(B)-**; AF750N7; AF1250(B)-**
Environmental Product Declaration - EPD
Environmental Product Declaration AF(S)580(F)(N), AF(S)750(F)(N), AF1250 (SE) Contactors
ABS Certificate
ABS Certificate, Contactor, AF400...AF2050 (Sweden)
BV Certificate
BV Certificate, Contactor, AF400 ... AF2850
CB Certificate
SE-82863
CCS Certificate
CCS Certificate, Contactor, AF116 to AF2850 (Sweden)
CQC Certificate
CQC Certificate, AC Contactor, AF580-30-*-*, AF750-30-*-* , AFS580-30-*-*, AFS750-30-*-*, Made in Sweden | CQC Certificate, Contactor, AF580, AF750, Made in China
CSA Certificate
306712-1
Declaration of Conformity - CCC
CCC Declaration of Conformity, AC Contactor, AF580-30-*-*, AF750-30-*-* , AFS580-30-*-*, AFS750-30-*-*, Made in Sweden | CCC Declaration of Conformity, Contactor, AF580, AF750, Made in China
Declaration of Conformity - CE
CE Declaration of Conformity - Contactor - AF400...AF2850
Declaration of Conformity - UKCA
UK Declaration of Conformity - Contactors >100A
DNV Certificate
DNV_E-10966
DNV GL Certificate
DNV Certificate, Contactor, AF400...AF2850
EAC Certificate
9AKK107046A8618
GL Certificate
GL_42988-02HH
LOVAG Certificate
SE-0151293
LR Certificate
Lloyds register Certificate, Contactor, AF400...AF2850
PRS Certificate
PRS Certificate - AF116...AF1650
RINA Certificate
RINA Certificate, AF95, AF110, AF145, AF185, AF210, AF260, AF300, AF400, AF460, AF580, AF750, AF1250, AF1350, AF1650, AF2050, AF2650, AF116, AF140, AF146, AF190, AF205, AF265, AF305, AF370
RMRS Certificate
9AKK107045A6978
UL Certificate
cULus Certificate, Contactor, AF580, AF750, AFS580, AFS750
UL Listing Card
UL_E36588
Package Level 1 Units
box 1 piece
Package Level 1 Width
280 mm
Package Level 1 Depth / Length
375 mm
Package Level 1 Height
310 mm
Package Level 1 Gross Weight
15 kg
Package Level 1 EAN
7320500222058
Object Classification Code
Q
ETIM 7
EC000066 - Power contactor, AC switching
ETIM 8
EC000066 - Power contactor, AC switching
ETIM 9
EC000066 - Power contactor, AC switching
eClass
V11.0 : 27371003
UNSPSC
39121529
IDEA Granular Category Code (IGCC)
4758 >> Iec Contactors
Feature → Business Impact → Application: The AF750-30-22-68 uses a 3-pole design capable of switching large motors up to 400 kW at 400 V AC (AC-3) with a main circuit rated up to 1000 V. This enables reliable motor starting and protection for heavy-duty conveyors, pumps, and presses in automation lines, reducing mechanical wear and downtime. The expansive main circuit rating translates to fewer components and simpler panel design, accelerating installation and commissioning in new builds or retrofits. Feature → Business Impact → Application: A wide control voltage range of 24–60 V DC provides tolerance against supply fluctuations, lowering nuisance trips and energy waste in unstable networks. This translates to improved control accuracy and energy efficiency across material handling, packaging machinery, and automated warehousing systems. Feature → Business Impact → Application: Built-in surge protection minimizes external protection devices, saving panel space and reducing component count. It supports compact control panels for machines with strict space constraints, such as robotic workcells and automated vending or sorting systems. Feature → Business Impact → Application: The device ships with pre-mounted auxiliary contacts (2 NO / 2 NC) and Main Circuit Bars, enabling fast, error-free installation and straightforward integration with existing control circuits. This accelerates commissioning in multi-motor drives, lifting systems, and cementing lines. Feature → Business Impact → Application: Its block-type design is easily extended with add-on auxiliary contact blocks and a broad accessory ecosystem, delivering scalable solutions for evolving automation needs. This is particularly valuable in OEM equipment where future expansion or reconfiguration is anticipated. Feature → Business Impact → Application: High resilience and robust ratings—AC-3 and AC-1 current capabilities, 8 x Ie breaking capacity, and 3 million mechanical cycles—provide predictability for mission-critical loads. This reduces maintenance intervals and supports long service life in heavy-duty manufacturing, process lines, and mining equipment. Feature → Business Impact → Application: Compliance with CE, UL/CSA, RoHS, REACH, and other standards ensures global installability without re-engineering; IP20/IP00 ratings on terminals and ambient operating ranges (-25 to 70 °C) support varied industrial environments. This simplifies cross-border procurement and reduces engineering handoffs for global rollouts.

Get a Quick Quote for a ABB 1SFL637001R6822

Chat with us on WhatsApp - fast responses guaranteed

Need to speak with someone? We'll call you back within 2 hours during business hours

Interested in ABB 1SFL637001R6822? Enquire Now

FAQs

Installation should use the three-pole configuration with main circuit bars for 52 mm² conductors and a coil driven by 24–60 V DC. Torque for main circuit connections is 45 N·m, and the device can be augmented with add-on auxiliary contact blocks. Ensure IP20 coil terminals and IP00 main terminals are properly enclosed and that mounting aligns with the 210 mm width, 242 mm depth, and 283 mm height footprint.
For AC-3, the contactor supports up to 750 A at voltages such as 415–690 V (varies by configuration), with a rated power handling of up to 600 kW at 690 V. AC-1 ratings at 1000 V allow up to 1050 A in some configurations. It offers an 8 x Ie rated breaking capacity and 10 x Ie making capacity, ensuring robust performance under motor starting and switching conditions.
Yes. With a 3-pole design and a main circuit rated up to 1000 V, it handles motors up to 400 kW at 400 V AC (AC-3) and heavy loads used in conveyors, pumps, and automated material handling systems. The wide coil range, built-in surge protection, and compatibility with accessories make it a reliable choice for demanding drive applications.
The AF750-30-22-68 carries CE and UL/CSA (cULus) listings, RoHS and REACH compliance, and UKCA where applicable. It also features environmental and industry certifications such as CCC/CB certificates in various regions, ensuring suitability for diverse regulatory environments and international procurement.
Mechanical durability is rated at around 3 million cycles, with modular design that supports easy replacement or extension via auxiliary blocks. The built-in surge protection and pre-mounted components reduce panel space and wiring time, contributing to lower maintenance costs and faster ROI in continuous-operation facilities such as packaging lines and process automation.