ABB 1SVR427055R2000 Power Supply - CE/UKCA Certified

Part Number: 1SVR427055R2000
Manufacturer
ABB
Part number
1SVR427055R2000

Quick Summary

ABB 1SVR427055R2000 power supply delivers 48 VDC at 10 A for three-phase panel applications. Installers often contend with space constraints, heat exposure, and wiring complexity in automation cabinets. This unit carries CE and UKCA declarations along with UL 508 safety certification, supporting global compliance with a single, robust solution. With a compact DIN-rail footprint, a 480 W rating, and a wide input range of 3x400-500 VAC (and 480-820 V DC), it streamlines panel design while delivering reliable, low-maintenance power to PLCs, drives, and sensors.

Product Information

Extended Description

1SVR427055R2000 ABB: CP-T 48/10.0 Power supply In: 3x400-500VAC Out: 48VDC/10.0A
Minimum Order Quantity
1 piece
Customs Tariff Number
85044095
Data Sheet, Technical Information
Data sheet - CP-T 48/10.0 Primary switch mode power supply
Instructions and Manuals
Instruction Sheet / Manual - CP-T 24/20.0 and CP-T 48/10.0
Product Net Width
150 mm
Product Net Height
131 mm
Product Net Depth / Length
119 mm
Product Net Weight
1.657 kg
Package Level 1 Width
200 mm
Package Level 1 Depth / Length
190 mm
Package Level 1 Height
190 mm
Package Level 1 Gross Weight
1.922 kg
Package Level 1 EAN
4016779662406
Package Level 1 Units
box 1 piece
Function
Switch mode power supply
Number of Phases
3
Rated Input Voltage (UIN)
3x 400 ... 500 V AC
Input Voltage (Uin)
3 x 340 ... 575 V AC | 480 ... 820 V DC
Rated Frequency (f)
50 Hz
Rated Frequency Limits
47 ... 63 Hz
Characteristic of Output
U/I characterisitc curve or Hiccup-mode selectable
Rated Output Power
480 W
Output Power
480 W
Rated Output Voltage
48 V DC
Output Voltage (Uout)
48 V DC
Rated Output Current
10 A
Output Current
10 A
Rated Impulse Withstand Voltage (Uimp)
Input Circuit / Output Circuit 6 kV | Input Circuit / PE 4 kV | Input Circuit / Relay Contact 4 kV | Output Circuit / PE 0.8 kV
Rated Insulation Voltage (Ui)
Input Circuit / Output Circuit 500 V | Input Circuit / PE 500 V | Input Circuit / Relay Contact 500 V | Output Circuit / PE 60 V
Degree of Protection
Housing IP20 | Terminals IP20
Pollution Degree
2
Connecting Capacity Input Circuit
Flexible with Ferrule 0.2 ... 4 mm² | Rigid 0.2 ... 6 mm²
Connecting Capacity Output Circuit
Flexible with Ferrule 0.2 ... 4 mm² | Rigid 0.2 ... 6 mm²
Tightening Torque
Input Circuit 1 N·m | Output Circuit 0.6 N·m
Wire Stripping Length
Auxiliary Circuit 8 mm | Input Circuit 8 mm | Output Circuit 8 mm
Recommended Screw Driver
PH2
Minimum Mounting Distance
Electrical Conductive Board, Horizontal 25 mm | Electrical Conductive Board, Vertical 25 mm | Other Device Same Type, Horizontal 25 mm | Other Device Same Type, Vertical 25 mm
Mounting Position
1
Mounting on DIN Rail
TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715 | TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
Standards
ANSI/ISA-12.12 | CAN/CSA C22.2 No.107.1 | CAN/CSA C22.2 No.213 | CAN/CSA C22.2 No.60950 | IEC/EN 63000 | IEC 60950-1 | IEC/EN 61000-6-2 | IEC/EN 61000-6-3 | UL 508 | UL 60950
Connecting Capacity Input Circuit UL/CSA
Rigid 24-10 AWG
Connecting Capacity Output Circuit UL/CSA
Rigid 24-10 AWG
Tightening Torque UL/CSA
Input Circuit 9 in·lb | Output Circuit 5.5 in·lb
Electrostatic Discharge (ESD Immunity) acc. to IEC 61000-4-2
Level 4 Air Discharge 15 kV | Level 4 Contact Discharge 8 kV
Radiated Electromagnetic Field Immunity acc. to IEC 61000-4-3
Level 3 10 V/m
Electrical Fast Transient (Burst Immunity) acc. to IEC 61000-4-4
Level 4 Power Supply Port Signal 4 kV
Surge Immunity acc. to IEC 61000-4-5
Level 3 Line-to-Line 2 kV | Level 4 Line-to-Line 4 kV
Conducted Disturbances Immunity acc. to IEC 61000-4-6
Level 3 10 V
Electromagnetic Compatibility (EMC)
Immunity - Class B | Emission - Environment B
Ambient Air Temperature
Operation -30 ... +70 °C | Storage -40 ... +85 °C
Maximum Operating Altitude Permissible
5000 m
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
REACH Declaration
REACh Info for Power Supplies
RoHS Information
RoHS Declaration of conformity for Power Supplies
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration for Power Supplies
WEEE B2C / B2B
Business To Business
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
cUL Certificate
cUL508_E174460
cUR Certificate
cUR60950_E196145 | cUR_ANSI_E317914
Declaration of Conformity - CE
EU Declaration of conformity - CP-T 48/10.0 and CP-T 24/20.0 Power supply units
Declaration of Conformity - UKCA
UK Declaration of conformity - CP-T 48/10.0 and CP-T 24/20.0 Power supply units
UL Certificate
UL Certificate (UL 508) - CP-C, CP-D, CP-E, CP-S, and CP-T range power supply units, CP-ASI power supply units and DC/DC converter, CP-B range buffer modules and extension module, CC-E and CC-U range analog signal converters
UR Certificate
UR Certificate (UL 60950) - CP-C, CP-D, CP-E, CP-S, CP-T range power supply units, CP-A range accessories, and CP-ASI power supply units and DC/DC converter | UR Certificate (ANSI/ISA-12.12) - CP-D, CP-T range power supply units
Object Classification Code
T
ETIM 7
EC002540 - DC-power supply
ETIM 8
EC002540 - DC-power supply
ETIM 9
EC002540 - DC-power supply
eClass
V11.0 : 27040701
UNSPSC
39121004
E-Number (Finland)
2712072
E-Number (Norway)
6609475
E-Number (Sweden)
5218720
Three-phase input compatibility simplifies site wiring and reduces transformer needs, delivering a cleaner bill of materials for control cabinets and OEM panel builders. The 48 VDC, 10 A output (480 W) provides a stable power rail for PLCs, servo drives, and peripheral electronics, improving uptime and reducing dropout risk in production lines. The switch-mode topology with selectable U/I curve or hiccup-mode protects loads and simplifies fault handling, enabling automatic recovery and minimal maintenance. IP20 enclosure with TH35 DIN-rail mounting (TH35-15 or TH35-7.5) makes installation straightforward and safe in standard control panels while supporting dense panel layouts. Certifications including CE, UKCA, and UL 508 reduce regional compliance burdens for global deployments across Europe, the UK, and North America. The unit’s compact dimensions (150 mm W x 131 mm H x 119 mm D) and weight (1.657 kg) further simplify cabinet design and logistics.

Get a Quick Quote for a ABB 1SVR427055R2000

Chat with us on WhatsApp - fast responses guaranteed

Need to speak with someone? We'll call you back within 2 hours during business hours

Interested in ABB 1SVR427055R2000? Enquire Now

FAQs

This unit is designed for DIN-rail mounting on TH35 rails, compatible with TH35-15 and TH35-7.5 profiles. The compact footprint and IP20 enclosure simplify installation in standard control cabinets and minimize space while maintaining safe, accessible wiring for maintenance and future upgrades.
Rated input is 3x 400 to 500 V AC with a frequency of 50 Hz (47–63 Hz range). The device accepts an input range of 3x340 to 575 V AC and 480 to 820 V DC, and provides a 48 V DC output at up to 10 A (480 W). These specs support diverse global grids and peak-load scenarios in automation panels.
The 1SVR427055R2000 carries CE and UKCA declarations, along with UL 508 certification and UL/CSA listings (cUL/cUR as applicable). This combination supports compliant deployment across Europe, the UK, and North America, reducing certification timelines for global projects.
Yes. The unit operates from -30 °C to +70 °C and withstands altitudes up to 5000 m, making it suitable for challenging environments often found in factories and remote installations. Its IP20 protection and robust construction further enhance reliability in harsh settings.
The module’s 480 W output with a 48 VDC rail supports reliable operation for PLCs, drives, and sensors, while its switch-mode topology provides protection against short-circuits and overload with a hiccup-mode option for automatic recovery. Its compact size, DIN-rail mounting, and broad input tolerance reduce wiring changes during upgrades and simplify spare-part inventories, lowering total cost of ownership.