ABB 1SVR550871R9500 CM-PVE Phase Monitoring Relay - UL 508
Part Number: 1SVR550871R9500
Quick Summary
CM-PVE phase monitoring relay 1SVR550871R9500 provides reliable phase loss and over/undervoltage monitoring for three-phase mains in industrial plants. Many facilities struggle with unseen phase faults that trigger costly downtime, motor damage, or erratic protection trips. This device offers fixed thresholds for phase loss detection and voltage monitoring with precise timing, including startup and tripping delays of 500 ms, supporting predictable protective actions. UL 508 listing, CE and UKCA declarations ensure compliance with global electrical safety standards, while can be integrated with CAN/CSA and IEC-based control schemes. By simplifying monitoring in control panels and on DIN rails, it improves uptime and reduces spurious trips, enabling safer panel designs and easier maintenance. The solution aligns with ABB CM monitoring ecosystems, delivering reliable protection with scalable installation options and documented conformance.
Product Information
Extended Description
1SVR550871R9500 ABB: The CM-PVE relay is from the CM three-phase monitors range. This relay operates with a rated control supply voltage / three-phase measuring voltage of 320-460 V AC and has a 1 n/o output (closed circuit principle) with contacts rated at 250 V / 4 A. The CM-PVE monitors the phase loss, overvoltage and undervoltage. The corresponding threshold values are fixed. The relay is suitable for monitoring of three phase mains.
EAN
4013614348112
Minimum Order Quantity
1 piece
Customs Tariff Number
85364900
Data Sheet, Technical Information
Data sheet - CM-PVE Three-phase monitoring relays
Instructions and Manuals
Instruction Sheet / Manual - CM-PBE, CM-PFE, CM-PFE.2, CM-PVE Three-phase sequence monitoring relay
CAD Dimensional Drawing
Information - 2D and 3D files for CAD systems
Product Net Width
22.5 mm
Product Net Height
78 mm
Product Net Depth / Length
78.5 mm
Product Net Weight
0.066 kg
Function
Phase failure detection | Over- and undervoltage monitoring
Sub-Function
Phase loss
Sub-Function 2
02 Over- and undervoltage (fixed)
Measuring Range
(L-L) 320 ... 460 V AC
Time Range
500 ms start-up delay | 500 ms tripping delay
Rated Control Supply Voltage (Us)
(L-L) 320 ... 460 V AC
Rated Frequency (f)
Supply Circuit 50/60 Hz
Output
1 n/o contact
Terminal Type
Screw Terminals
Rated Operational Current AC-12 (Ie)
(230 V) 4 A
Rated Operational Current AC-15 (Ie)
(230 V) 3 A
Rated Operational Current DC-12 (Ie)
(24 V) 4 A
Rated Operational Current DC-13 (Ie)
(24 V) 2 A
Rated Impulse Withstand Voltage (Uimp)
Input Circuit 4 kV
Rated Insulation Voltage (Ui)
Input Circuit / Output Circuit 400 V
Degree of Protection
Housing IP50 | Terminals IP20
Overvoltage Category
III
Pollution Degree
3
Short-Circuit Protective Devices
Output Circuit NC - F Type Fuses 10 A | Output Circuit NO - F Type Fuses 10 A
Connecting Capacity
Flexible with Ferrule 2x 0.75 ... 1.5 mm² | Flexible 2x 1 ... 1.5 mm² | Rigid 2x 0.75 ... 1.5 mm²
Tightening Torque
0.6 ... 0.8 N·m
Wire Stripping Length
10 mm
Mounting Position
1 ... 6
Mounting on DIN Rail
TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715 | TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
Standards
CAN/CSA C22.2 No.14 | IEC/EN 63000 | IEC/EN 61000-6-2 | IEC/EN 61000-6-3 | UL 508
Maximum Operating Voltage UL/CSA
Output Circuit 250 V AC
Contact Rating UL/CSA
B300
Connecting Capacity UL/CSA
Flexible with Ferrule 2x 18-16 AWG | Flexible 2x 18-16 AWG | Rigid 2x 18-16 AWG
Tightening Torque UL/CSA
7.08 in·lb
Pilot Duty UL/CSA
B300
Ambient Air Temperature
Operation -20 ... +60 °C | Storage -40 ... +85 °C
Maximum Operating Altitude Permissible
Without Derating 2000 m
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
REACH Declaration
REACh Info for Electronic Relays and Controls
RoHS Information
RoHS Declaration of conformity for Electronic Relays and Controls
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
SCIP
b54e6567-6570-4d39-a8a5-f838e1bef0ba Germany (DE)
Simplified SCIP
45d9b8fd-d63b-464b-af0e-6d8510e96106 Bulgaria (BG) | ce7e14e7-f204-4f37-ae70-abb118ab834f Poland (PL) | a507493a-8d0a-4b11-95d7-82491c703169 Denmark (DK) | c36e9b36-7a4c-475b-894a-c86c2bf8b259 Germany (DE) | 2ee9291b-9c7a-4bef-806b-ce151badf916 Czech Republic (CZ) | 473c0df2-cb24-47a5-b894-0ece5c25a90f Italy (IT) | cbd7c5d1-2a87-4e11-aedd-ee9954e5ede6 Germany (DE) | acbb8cad-1ae8-45dd-9f3a-f238b03629ca Netherlands (NL) | f7ee0835-eae1-4348-aa2c-cf73360cf163 Finland (FI) | 0e625803-148b-47dc-b279-2b7c10db1f33 France (FR) | 299b8529-a702-44ac-a124-cbd83de7f43e Greece (GR) | 15f15a42-8ee7-423f-a58d-10d6367e6dfe Sweden (SE) | 14cd1d68-94fc-4c24-8ab0-26de7f91d2b8 Portugal (PT) | bbbf4a82-c153-4fc7-9493-05d79c186d08 Norway (NO) | c8869a5d-95c0-4931-b530-e209cafd1206 Croatia (HR) | 7dd10c17-c5e5-47e3-acb0-a877c2e5ccb3 Sweden (SE) | b729ec2d-7d3a-4386-b74d-d6494b35ad01 Poland (PL) | 083d8915-610a-46e0-a73e-3fb7f0b36135 Estonia (EE) | ca746fb1-5ff1-4e2c-925f-9a733658b0f9 Hungary (HU) | 5dbd6902-f306-4629-a52f-cb6abb7f2505 Spain (ES) | 1b7d7bb8-ac89-42cb-9f37-dc1b801bdc9b Belgium (BE) | 1cb3535d-f620-47cb-8779-2dde7a965634 Hungary (HU) | 7b36b382-d2c5-47ad-a93b-583235655d88 Belgium (BE) | f97957f2-cb19-4d6b-9e1a-0f41b2c6b673 France (FR) | 296c7fbf-bd21-4516-a744-7ad17a1cfadc Germany (DE) | 565b04d9-2123-43e1-9531-ffd2bb8eb079 Germany (DE) | 10a9f03a-cbca-4549-932c-3e71981c2818 Poland (PL)
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration for Electronic Relays and Controls
CB Certificate
CB_DK-8880
CCC Certificate
CCC Certificate - Measuring and Monitoring Relays CM-E range
CQC Certificate
CQC Certificate, Electronic Measuring and Monitoring Relays, CM-PFE, CM-PVE, CM-PBE, CM-MSE, CM-ENE MAX, CM-ENE MIN, Made in Bulgaria
cUL Certificate
cUL508_E140448
Declaration of Conformity - CCC
CCC Declaration of Conformity, Electronic Measuring and Monitoring Relays, CM-PFE, CM-PVE, CM-PBE, CM-MSE, CM-ENE MAX, CM-ENE MIN, Made in Bulgaria
Declaration of Conformity - CE
EU Declaration of Conformity - CM-PBE, CM-PVE Three-phase monitoring relay
Declaration of Conformity - UKCA
UK Declaration of Conformity - CM-PBE, CM-PVE Three-phase monitoring relay
UL Certificate
UL Certificate (UL 508) - CT-E, CT-S range time relays, CM and C51x range measuring and monitoring relays , C57x and C67xx range safety relays, CC-U range analog signal converters with relay output
Package Level 1 Units
box 1 piece
Package Level 1 Width
23 mm
Package Level 1 Depth / Length
82 mm
Package Level 1 Height
82 mm
Package Level 1 Gross Weight
0.078 kg
Package Level 1 EAN
4013614348112
Object Classification Code
B
ETIM 7
EC001441 - Phase monitoring relay
ETIM 8
EC001441 - Phase monitoring relay
ETIM 9
EC001441 - Phase monitoring relay
eClass
V11.0 : 27371803
UNSPSC
39122332
E-Number (Finland)
2712602
E-Number (Norway)
4187171
Feature: Measuring range (L-L) 320-460 VAC. Business Impact: Ensures compatibility with most three-phase systems, reducing false trips and enabling accurate protection. Application: Three-phase feeders and motors in industrial plants. Feature: 1 normally open contact (NC/NO configuration via wiring). Business Impact: Simple integration with PLCs and interlocks, improving protective logic without complex wiring. Application: Motor starters and panel protection circuits. Feature: Time range with 500 ms startup delay and 500 ms tripping delay. Business Impact: Minimizes nuisance trips during startup transients, increasing process stability. Application: Variable load profiles and soft-start machinery. Feature: Rated currents AC-12 (230 V) 4 A and AC-15 (230 V) 3 A; DC-12 (24 V) 4 A; DC-13 (24 V) 2 A. Business Impact: Clear, specified load capabilities for control circuits, reducing oversizing and wiring complexity. Application: Control relays and sequencing in automation panels. Feature: Terminal type screw terminals; compatible with flexible and rigid conductors; mounting on TH35 DIN rails. Business Impact: Efficient, vibration-resistant mounting with robust terminations; simplifies field retrofit and panel fabrication. Application: DIN-rail mounted protection relays in MCCs and switchgear. Feature: Housing IP50; operating temperature -20 to +60 °C; mounting options TH35-15 or TH35-7.5. Business Impact: Rugged performance in harsh environments with proven protection and flexible installation. Application: Harsh factory floors and control cabinets. Feature: Certifications and standards (UL 508, CE, UKCA; CAN/CSA; IEC/EN 63000; RoHS/REACH). Business Impact: Global compliance reduces qualification risk and speeds time-to-operate. Application: Global manufacturing environments requiring regulatory conformity.
Get a Quick Quote for a ABB 1SVR550871R9500
Chat with us on WhatsApp - fast responses guaranteed
Need to speak with someone? We'll call you back within 2 hours during business hours
Interested in ABB 1SVR550871R9500?
Enquire Now
FAQs
Yes. The CM-PVE is designed for TH35 DIN-rail mounting with screw terminals. It supports flexible with ferrule 2x 0.75 to 1.5 mm², flexible 2x 1 to 1.5 mm², or rigid 2x 0.75 to 1.5 mm² conductors, enabling quick, secure wiring in control panels.
It monitors (L-L) 320–460 VAC with a 1 N/O output, rated control supply voltage of 320–460 VAC, and 50/60 Hz nominal. It includes startup and tripping delays of 500 ms, with rated currents AC-12 4 A and AC-15 3 A at 230 V, suitable for motor protection schemes.
Ideal for three-phase power protection in motor control centers, process lines, and distribution panels. It quickly detects phase loss and voltage irregularities, triggering protective actions to prevent motor stalls, overheating, and abnormal shutdowns, while maintaining stable process operations.
The CM-PVE carries UL 508 listing, CE and UKCA declarations, plus CQC, CCC certifications, and RoHS/REACH compliance. These certifications support global deployment in regulated environments and simplify supplier qualification and panel approval processes.
Fixed thresholds and non-adjustable parameters reduce field calibration needs, lowering maintenance costs. Early fault detection minimizes downtime and equipment damage, improving uptime and predictability in critical lines. Long-term reliability and standard-compliant installation further reduce lifecycle costs.