ABB 1SVR560730R3403 Grid Monitoring Relay - DEWA DRRG
Part Number: 1SVR560730R3403
Quick Summary
ABB 1SVR560730R3403 grid monitoring relay provides protective supervision for grid-fed power systems in industrial plants. Engineers often struggle with undetected voltage faults and unreliable signaling that lead to unplanned downtime. This device carries CE conformity and TΓV DRRG verification for DEWA compliance, along with EN 50178, IEC/EN 63000, IEC/EN 60255-27 and IEC/EN 61000-6 series adherence, ensuring safety and electromagnetic compatibility. With flexible input ranges, DIN rail mounting, and three SPDT contacts, it simplifies panel design, reduces commissioning time, and delivers dependable protection for utilities and manufacturing sites alike.
Product Information
Extended Description
1SVR560730R3403 ABB: CM-UFD.M34 Grid feeding monitoring relay 3c/o,L-L= 0-540VAC,L-N=0-312VAC acc. DEWA standard
EAN
4013614511110
Minimum Order Quantity
1 piece
Customs Tariff Number
85364900
Data Sheet, Technical Information
Data sheet - CM-UFD.M34M and CM-UFD.M34 Grid feeding monitoring relay acc. to DEWA DRRG standard
Instructions and Manuals
Instruction Sheet / Manual - CM-UFD.M34(M) Grid feeding monitoring relay
Product Net Width
108 mm
Product Net Height
90 mm
Product Net Depth / Length
67 mm
Product Net Weight
0.304 kg
Function
Over- and undervoltage monitoring | Interrupted neutral monitoring | Over- and underfrequency monitoring | 10 minutes average value monitoring | Vector shift detection | ROCOF monitoring
Measuring Range
0 ... 540 V AC
Rated Control Supply Voltage (Us)
24 ... 240 V AC/DC
Output
3 c/o (SPDT) contacts
Terminal Type
Screw Terminals
Rated Operational Current AC-12 (Ie)
(230 V) 4 A
Rated Operational Current AC-15 (Ie)
(230 V) 3 A
Rated Operational Current DC-12 (Ie)
(24 V) 4 A
Rated Operational Current DC-13 (Ie)
(24 V) 2 A
Minimum Switching Capacity
24 V | 10 mA
Degree of Protection
Housing IP20 | Terminals IP20
Pollution Degree
3
Short-Circuit Protective Devices
Output Circuit NC - F Type Fuses 10 A | Output Circuit NO - F Type Fuses 10 A
Electrical Durability
AC-12 50000 cycle
Mechanical Durability
Nr. Operations 30000000 cycle
Connecting Capacity
Flexible with Ferrule 1x 0.25 ... 4.0 mmΒ² | Flexible with Ferrule 2x 0.25 ... 0.75 mmΒ² | Flexible with Insulated Ferrule 1x 0.25 ... 4.0 mmΒ² | Flexible with Insulated Ferrule 2x 0.25 ... 0.75 mmΒ² | Flexible 1x 0.2 ... 4.0 mmΒ² | Flexible 2x 0.2 ... 1.5 mmΒ² | Rigid 1x 0.2 ... 6.0 mmΒ² | Rigid 2x 0.2 ... 1.5 mmΒ²
Tightening Torque
0.5 ... 0.6 NΒ·m
Wire Stripping Length
8 mm
Mounting Position
1 ... 6
Mounting on DIN Rail
TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715 | TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715
Standards
EN 50178 | IEC/EN 63000 | IEC/EN 60255-27 | IEC/EN 61000-6-2 | IEC/EN 61000-6-3
Connecting Capacity UL/CSA
Flexible with Ferrule 1x 24-12 AWG | Flexible with Ferrule 2x 24-18 AWG | Flexible with Insulated Ferrule 1x 24-12 AWG | Flexible with Insulated Ferrule 2x 24-18 AWG | Flexible 1x 24-12 AWG | Flexible 2x 24-16 AWG | Rigid 1x 24-10 AWG | Rigid 2x 24-16 AWG
Tightening Torque UL/CSA
4.4 ... 5.3 inΒ·lb
Ambient Air Temperature
Operation -20 ... +60 Β°C | Storage -25 ... +50 Β°C
RoHS Information
EU Declaration of Conformity - CM-UFD.M22, CM-UFD.M31, CM-UFD.M34 Grid feeding monitoring relay
RoHS Status
Following EU Directive 2011/65/EU
Declaration of Conformity - CE
EU Declaration of Conformity - CM-UFD.M22, CM-UFD.M31, CM-UFD.M34 Grid feeding monitoring relay
TΓV Certificate
TUEV Compliance Document (DRRG standard of DEWA) - CM-UFD.M34 Grid feeding monitoring relay
Package Level 1 Units
carton 1 piece
Package Level 1 Width
121 mm
Package Level 1 Depth / Length
71 mm
Package Level 1 Height
99 mm
Package Level 1 Gross Weight
0.36 kg
Package Level 1 EAN
4013614511110
Object Classification Code
B
ETIM 7
EC001438 - Voltage monitoring relay
ETIM 8
EC001438 - Voltage monitoring relay
ETIM 9
EC001438 - Voltage monitoring relay
eClass
V11.0 : 27371801
Feature: Wide measuring range and flexible control supply. Benefit: Supports 0-540 V AC measurements with a 24-240 V AC/DC control supply, enabling installation without additional power interfaces. Application: Grid feeders, industrial mains panels, and PV installations where space is at a premium. Feature: Three SPDT contacts (3 c/o). Benefit: Simplified wiring and configurable interlocking for protective schemes, reducing cabling complexity and risk of misconnection. Application: Safe, clear signal conditioning for control systems and protection relays. Feature: Comprehensive monitoring functions. Benefit: Over- and undervoltage, interrupted neutral, frequency monitoring, 10-minute average value, vector shift and ROCOF detection improve grid stability and fault visibility. Application: Distribution panels and DER interfaces requiring fast fault isolation. Feature: DIN rail mounting options. Benefit: TH35-7.5 or TH35-15 compatibility with common enclosures, enabling fast, reliable installation and easy maintenance. Application: New builds and retrofit projects in control cabinets. Feature: Robust durability and protection. Benefit: IP20 housing with pollution degree 3 support long-term operation and reduced maintenance in typical industrial environments. Application: Factory floors, switchgear assemblies, and outdoor-adjacent cabinets. Feature: Compliance and documentation. Benefit: CE DoC, TΓV DRRG verification, and RoHS compliance streamline regulatory approval and customer audits. Application: Projects targeting DEWA standards and global safety/compliance requirements.
Get a Quick Quote for a ABB 1SVR560730R3403
Chat with us on WhatsApp - fast responses guaranteed
Need to speak with someone? We'll call you back within 2 hours during business hours
Interested in ABB 1SVR560730R3403?
Enquire Now
FAQs
Install the unit on a TH35-7.5 or TH35-15 DIN rail per IEC 60715. Use screw terminals and follow the specified wire ranges: flexible with ferrule 0.25β4.0 mmΒ², rigid 0.2β6.0 mmΒ². Stripping length should be about 8 mm. Tighten to 0.5β0.6 NΒ·m and ensure the device is securely mounted with proper clearance for cooling and accessibility.
Measuring range: 0β540 V AC. Control supply voltage: 24β240 V AC/DC. Outputs: 3 c/o SPDT contacts. Rated operational currents: AC-12 at 230 V is 4 A; AC-15 at 230 V is 3 A; DC-12 at 24 V is 4 A; DC-13 at 24 V is 2 A. Minimum switching: 24 V at 10 mA. Pretty robust for panel protection and signaling.
Yes. The product includes a CE Declaration of Conformity and TΓV DRRG certification for DEWA DRRG compliance. It also adheres to EN 50178, IEC/EN 63000, IEC/EN 60255-27, and IEC/EN 61000-6-2/3 standards, with RoHS compliance to EU Directive 2011/65/EU, ensuring regulatory alignment for utility and industrial deployments.
Ideal for grid-fed installations, DER interfaces, and distribution panels in manufacturing and utilities. It supports grid feeding monitoring, protection signaling, and compatibility with control systems via its SPDT outputs. It helps prevent islanding, improves voltage and frequency supervision, and supports integration with existing ABB or third-party automation architectures.
Designed for longevity, it offers electrical durability of around 50,000 AC-12 cycles and mechanical durability of about 30,000,000 cycles, reducing replacement frequency and downtime. The straightforward DIN-rail installation, standardized terminals, and clear documentation accelerate commissioning, delivering a favorable total cost of ownership and faster time-to-protection for critical power paths.