Voltage monitoring relay CM-ESS.1S protects single-phase control circuits from undervoltage and overvoltage. It reduces nuisance trips and unplanned downtime in critical automation lines. CE and UL/CSA certifications back European and North American deployments, with IP50 housing that withstands typical factory environments. The solution integrates seamlessly with screw terminals and DIN-rail mounting, delivering reliable protection while enabling straightforward diagnostics. By supporting open-circuit measuring and adjustable hysteresis, it gives you precision control without overengineering, supporting predictable performance and safer machine operation. This brings tangible business value to panel builders and maintenance teams by improving uptime, safety, and regulatory compliance. It scales across equipment fleets, simplifying spec alignment with OEMs and internal standards.

Product Information

Extended Description

1SVR730831R0300 ABB: The CM-ESS.1S is a single-functional voltage monitoring relay from the CM single-phase monitors range. This monitoring relay operates with a rated control supply voltage of 110 - 130 V AC and has a 1 c/o (SPDT) output contact rated at 250 V / 4 A. It provides a RMS measuring principle for DC and AC voltages with 4 measuring ranges: 3-30 V, 3-60 A, 30-300 V and 60-600 V and works according to the open-circuit principle. The CM-ESS.1S is configurable for over- or undervoltage monitoring, the hysteresis is adjustable within a range of 3 to 30 % of the threshold value. A sealable transparent cover for protection against unauthorized changes is available as accessory. The device offers screw connection technology with double-chamber cage connection terminals.
EAN
4016779852180
Minimum Order Quantity
1 piece
Customs Tariff Number
85364900
Data Sheet, Technical Information
Data sheet - CM-ESS.1P; CM-ESS.1S Voltage monitoring relays, single-phase AC/DC
Instructions and Manuals
Instruction Sheet / Manual - CM-ExS Single-phase voltage monitoring relays | Installation instructions - CM-ExS Single-phase voltage monitoring relays
CAD Dimensional Drawing
Information - 2D and 3D files for CAD systems
Product Net Width
22.5 mm
Product Net Height
85.6 mm
Product Net Depth / Length
103.7 mm
Product Net Weight
0.164 kg
Function
Over- or undervoltage monitoring
Measuring Range
3 ... 30 V | 6 ... 60 V | 30 ... 300 V | 60 ... 600 V
Rated Control Supply Voltage (Us)
110 ... 130 V AC
Output
1 c/o (SPDT) contact
Terminal Type
Screw Terminals
Rated Operational Current AC-12 (Ie)
(230 V) 4 A
Rated Operational Current AC-15 (Ie)
(230 V) 3 A
Rated Operational Current DC-12 (Ie)
(24 V) 4 A
Rated Operational Current DC-13 (Ie)
(24 V) 2 A
Minimum Switching Capacity
24 V | 10 mA
Rated Impulse Withstand Voltage (Uimp)
Measuring Circuit / Output Circuit 6 kV | Output Circuit 1 / Output Circuit 2 4 kV | Supply Circuit / Measuring Circuit 6 kV | Supply Circuit / Output Circuit 4 kV
Rated Insulation Voltage (Ui)
Measuring Circuit / Output Circuit 600 V | Output Circuit 1 / Output Circuit 2 250 V | Supply Circuit / Measuring Circuit 600 V | Supply Circuit / Output Circuit 250 V
Degree of Protection
Housing IP50 | Terminals IP20
Overvoltage Category
III
Pollution Degree
3
Short-Circuit Protective Devices
Output Circuit NC - F Type Fuses 6 A | Output Circuit NO - F Type Fuses 10 A
Electrical Durability
AC-12 100000 cycle
Mechanical Durability
Nr. Operations 30000000 cycle
Connecting Capacity
Flexible with Ferrule 1x 0.5 ... 2.5 mm² | Flexible with Ferrule 2x 0.5 ... 1.5 mm² | Flexible with Insulated Ferrule 1x 0.5 ... 2.5 mm² | Flexible with Insulated Ferrule 2x 0.5 ... 1.5 mm² | Flexible 1x 0.5 ... 2.5 mm² | Flexible 2x 0.5 ... 1.5 mm² | Rigid 1x 0.5 ... 4 mm² | Rigid 2x 0.5 ... 2.5 mm²
Tightening Torque
0.6 ... 0.8 N·m
Wire Stripping Length
8 mm
Recommended Screw Driver
0.8 x 4 | 4.5 | Pozidriv 1
Mounting Position
1 ... 6
Mounting on DIN Rail
TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715 | TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
Standards
CAN/CSA C22.2 No.14 | IEC/EN 63000 | IEC/EN 60255-27 | IEC/EN 61000-6-2 | IEC/EN 61000-6-3 | UL 508
Maximum Operating Voltage UL/CSA
Output Circuit 300 V AC
Contact Rating UL/CSA
B300
Connecting Capacity UL/CSA
Flexible 1x 18-14 AWG | Flexible 2x 18-16 AWG | Rigid 1x 20-12 AWG | Rigid 2x 20-14 AWG
Tightening Torque UL/CSA
7.08 in·lb
Pilot Duty UL/CSA
B300
Flammability According to UL94
V-0
Ambient Air Temperature
Operation -20 ... +60 °C | Storage -40 ... +85 °C
Maximum Operating Altitude Permissible
Without Derating 2000 m
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
REACH Declaration
REACh Info for Electronic Relays and Controls
RoHS Information
RoHS Declaration of conformity for Electronic Relays and Controls
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration for Electronic Relays and Controls
CB Certificate
CB_DK-28255-UL
CQC Certificate
CQC Certificate, Relays, CM-SRS.., CM-SFS.., CM-ESS..,CM-EFS.., CM-TCS.., Made in Germany
cULus Certificate
cULus508_20120203-E140448
Declaration of Conformity - CCC
CCC Certificate, Relays, CM-SRS.., CM-SFS.., CM-ESS..,CM-EFS.., CM-TCS.., Made in Germany
Declaration of Conformity - CE
EU Declaration of Conformity - CM-ExS.xxx, CM-SxS.xxx Single-phase current and voltage monitoring relays
Declaration of Conformity - UKCA
UK Declaration of Conformity - CM-ExS.xxx, CM-SxS.xxx Single-phase current and voltage monitoring relays
DNV GL Certificate
DVN Certificate - Voltage monitoring relays CM-EFS.x and CM-ESS.x with screw or push-in terminals
EAC Certificate
EAC Certificate - Measuring and monitoring relays CM-xxS.xxx and CM-xxN.xxx range in the new housing
Package Level 1 Units
box 1 piece
Package Level 1 Width
97 mm
Package Level 1 Depth / Length
30 mm
Package Level 1 Height
109 mm
Package Level 1 Gross Weight
0.186 kg
Package Level 1 EAN
4016779852180
Object Classification Code
B
ETIM 7
EC001438 - Voltage monitoring relay
ETIM 8
EC001438 - Voltage monitoring relay
ETIM 9
EC001438 - Voltage monitoring relay
eClass
V11.0 : 27371801
UNSPSC
39122332
E-Number (Finland)
2712245
E-Number (Norway)
4188080
E-Number (Sweden)
3860621
Voltage monitoring relies on four measuring ranges (3-30 V, 6-60 V, 30-300 V, 60-600 V) to cover diverse supply conditions. This flexibility translates to fewer misdetections and more stable protection across different installations, from simple machines to multi‑voltage panels. The open‑circuit measuring principle ensures the output reacts only to true voltage deviations, reducing false trips and protecting sensitive loads. A 1 c/o SPDT contact rated at 250 V / 4 A provides a straightforward interface to PLCs or safety relays, simplifying wiring and panel space. The device features screw terminals and DIN rail mounting (TH35-15 or TH35-7.5), enabling quick retrofits and robust, maintenance-friendly connections. Housing IP50 with operation from -20 to +60 C supports harsh factory environments, while CE and UL/CSA certifications streamline global compliance. Durable AC‑12 operation (100000 cycles) and strong mechanical endurance translate to lower lifecycle costs and higher uptime.

Get a Quick Quote for a ABB 1SVR730831R0300

Chat with us on WhatsApp - fast responses guaranteed

Need to speak with someone? We'll call you back within 2 hours during business hours

Interested in ABB 1SVR730831R0300? Enquire Now

FAQs

Yes. The device is designed for DIN rail mounting on TH35-15 or TH35-7.5 rails and uses screw terminals suitable for wires ferruled 0.5–2.5 mm², plus flexible/ferrule variants, enabling fast, reliable panel installs.
It monitors four ranges: 3-30 V, 6-60 V, 30-300 V, 60-600 V, and requires a control supply of 110-130 V AC. The RMS measuring principle supports accurate sensing for both AC and DC components in single‑phase circuits.
Yes. With 1 c/o SPDT contact rated at 250 V / 4 A, it interfaces directly with PLCs or contactors for signaling and interlocking, making it suitable for motor protection and drive control in conveyors and packaging lines.
The CM-ESS.1S carries CE and UL/CSA certifications, plus CCC and other declarations. This broad certification footprint supports compliance in European, North American, and other international markets.
With AC-12 durability rated at 100000 cycles and robust mechanical durability, the device minimizes replacement frequency. Easy diagnostics, documented manuals, and standard wiring reduce maintenance time and support faster ROI in new builds and retrofits.