ABB 1SVR730850R2100 liquid level monitoring relay protects pumps and tanks by detecting conductive-fluid levels. Engineers frequently struggle with dry-run damage and overflow when level sensing is unreliable. This device carries CE and UKCA marks, and is validated for UL/CSA and CCC certifications, ensuring global regulatory compliance and safer operation. With front-face potentiometers for sensitivity, three electrodes, and accessible screw terminals, installation is straightforward, maintenance predictable, and future-proof for expanding systems. The CM-ENS.13S family monitors levels according to open-circuit principle, offering adjustable ranges from 5 to 100 kΩ and compatibility with 110-130 VAC or 220-240 VAC supplies. This combination delivers reliable dry-run prevention, overflow protection, and energy-efficient pump control across industrial water/wastewater, chemical processing, and food/beverage lines.
Product Information
Extended Description
1SVR730850R2100 ABB: The CM-ENS.13S belongs to the CM liquid level monitoring relay range. It operates with a rated control supply voltage of 110-130 V AC and 220-240 V AC and has a 1 c/o (SPDT) output with contacts rated at 250 V / 4 A. It monitors liquid levels of conductive fluids and protects pumps against dry running or tanks against overflow and works according to the open-circuit principle. The sensitivity can be selected via front-face potentiometers. Several electrodes and a sealable transparent cover for protection against unauthorized changes are available as accessory. The device offers screw connection technology with double-chamber cage connection terminals.
EAN
4013614502903
Minimum Order Quantity
1 piece
Customs Tariff Number
85364900
Data Sheet, Technical Information
Data sheet - Liquid level monitoring relays CM-ENS.1x
Instructions and Manuals
Instruction sheet - CM-ENS.xxx Liquid level monitoring relays | Installation instructions - CM-ENS.xxx Liquid level monitoring relays
CAD Dimensional Drawing
Information - 2D and 3D files for CAD systems
Product Net Width
22.5 mm
Product Net Height
85.6 mm
Product Net Depth / Length
103.7 mm
Product Net Weight
0.153 kg
Function
Filling or draining monitoring
Number of Electrodes
3
Measuring Range
5 ... 100 kΩ
Rated Control Supply Voltage (Us)
110 ... 130 V AC | 220 ... 240 V AC
Rated Frequency (f)
Supply Circuit 50/60 Hz
Output
1 c/o (SPDT) contact
Terminal Type
Screw Terminals
Rated Operational Current AC-12 (Ie)
(230 V) 4 A
Rated Operational Current AC-15 (Ie)
(230 V) 3 A
Rated Operational Current DC-12 (Ie)
(24 V) 4 A
Rated Operational Current DC-13 (Ie)
(24 V) 2 A
Minimum Switching Capacity
12 V | 10 mA
Rated Impulse Withstand Voltage (Uimp)
Measuring Circuit / Output Circuit 4 kV | Output Circuit 1 / Output Circuit 2 4 kV | Supply Circuit / Measuring Circuit 4 kV | Supply Circuit / Output Circuit 4 kV
Rated Insulation Voltage (Ui)
Measuring Circuit / Output Circuit 300 V | Output Circuit 1 / Output Circuit 2 300 V | Supply Circuit / Measuring Circuit 300 V | Supply Circuit / Output Circuit 300 V
Degree of Protection
Housing IP50 | Terminals IP20
Overvoltage Category
III
Pollution Degree
3
Short-Circuit Protective Devices
Output Circuit NC - F Type Fuses 6 A | Output Circuit NO - F Type Fuses 10 A
Electrical Durability
AC-12 100000 cycle
Mechanical Durability
Nr. Operations 1000000 cycle
Connecting Capacity
Flexible with Ferrule 1x 0.5 ... 2.5 mm² | Flexible with Ferrule 2x 0.5 ... 1.5 mm² | Flexible with Insulated Ferrule 1x 0.5 ... 2.5 mm² | Flexible with Insulated Ferrule 2x 0.5 ... 1.5 mm² | Flexible 1x 0.5 ... 2.5 mm² | Flexible 2x 0.5 ... 1.5 mm² | Rigid 1x 0.5 ... 4 mm² | Rigid 2x 0.5 ... 2.5 mm²
Tightening Torque
0.6 ... 0.8 N·m | Control Circuit 0.9 N·m | Main Circuit 1 N·m
Wire Stripping Length
8 mm | Main Circuit 10 mm
Recommended Screw Driver
0.8 x 4 | 4.5 | Pozidriv 1
Mounting Position
1 ... 5 | 1 ... 6
Mounting on DIN Rail
TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715 | TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
Standards
CAN/CSA C22.2 No.14 | IEC/EN 63000 | IEC/EN 60255-27 | IEC/EN 61000-6-2 | IEC/EN 61000-6-3 | UL 508
Maximum Operating Voltage UL/CSA
Output Circuit 300 V AC
Contact Rating UL/CSA
B300
Connecting Capacity UL/CSA
Flexible 1x 18-14 AWG | Flexible 2x 18-16 AWG | Rigid 1x 20-12 AWG | Rigid 2x 20-14 AWG
Tightening Torque UL/CSA
7.08 in·lb
Pilot Duty UL/CSA
B300
Ambient Air Temperature
Operation -25 ... +60 °C | Storage -40 ... +85 °C
Maximum Operating Altitude Permissible
Without Derating 2000 m
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
REACH Declaration
REACh Info for Electronic Relays and Controls
RoHS Information
RoHS Declaration of conformity for Electronic Relays and Controls
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
SCIP
83a2b4a3-7120-40ca-88b9-8013bdf8df1c Germany (DE)
Simplified SCIP
cde3089b-27d1-40a9-85e3-9aefaa4b7682 Sweden (SE) | 42aecf98-4abe-44c7-bf08-11d499af6e1b Sweden (SE) | c3b75eef-97d9-431c-9c69-032f1caefa41 Estonia (EE) | 183e81a5-73b8-44ae-86b2-9e372f6ef687 Norway (NO) | fee96707-edc1-404d-92c2-406b1aa2ab56 Poland (PL) | 7547ba63-f382-4633-880b-efb08c0207d1 Greece (GR) | e3c17b15-1de8-44c3-bbb1-e18541e3aa44 Portugal (PT) | 68bf7ebe-5a75-4ef3-9089-934b05d883b0 Netherlands (NL) | 3725f11e-bd11-4e51-820b-7faf17e13f78 Bulgaria (BG) | 2929a0aa-3186-4108-8828-abee875530c1 Hungary (HU) | 3db16d1e-41f2-4c4e-bd5c-382a30fbd6ee Belgium (BE) | faa0d55c-d86d-4a54-964e-c1af4899a2cb Germany (DE) | 39baf8c1-a04a-4118-91d8-edfc4f2f8ee1 France (FR) | 80fb5050-c41d-4895-8d9a-111734612b26 Germany (DE) | 37c98d24-387b-4549-8346-45104cd204a2 Spain (ES) | 3c15b366-4771-417e-b1d1-f428bc10e51c Hungary (HU) | 9b106e89-fa53-4487-af25-126fa28ef4d9 Croatia (HR) | 80338b87-f66b-47e6-8521-c7a55377ca08 France (FR) | 71bfecaf-3fd0-46bf-b90c-c6eabb2c1af9 Czech Republic (CZ) | 4563b62b-7b0a-4ec6-b28f-165689fa652a Germany (DE) | 7d327f1f-b2b5-4099-a15c-0e3bc1873ef1 Denmark (DK) | d5f4e8ba-5736-4a0c-ab6c-fc6003f6b9ef Poland (PL) | a83186cf-a49f-4e18-807a-70ed5c135ed9 Belgium (BE) | 1410fee5-0247-455e-b13e-dda5b9441ffa Poland (PL) | dd51bb59-423a-4e25-ab9e-f35e32619517 Italy (IT) | 60053b7f-5272-4565-9093-16b4c3f796a7 Germany (DE) | b74457d3-165f-4d46-9618-86707e7653d8 Finland (FI)
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration for Electronic Relays and Controls
CQC Certificate
CQC Certificate, Liquid Level Monitoring Relays, CM-ENS.xxx, Made in Germany
cULus Certificate
cULus508_20150627-E140448
Declaration of Conformity - CCC
CCC Declaration of Conformity, Liquid Level Monitoring Relays, CM-ENS.xxx, Made in Germany
Declaration of Conformity - CE
EU Declaration of Conformity - CM-ENS.xxx Liquid level monitoring relay
Declaration of Conformity - UKCA
UK Declaration of Conformity - CM-ENS.xxx Liquid level monitoring relay
DNV GL Certificate
DNV GL Certificate - CM-ENS.xxx Liquid level monitoring relays
Package Level 1 Units
box 1 piece
Package Level 1 Width
97 mm
Package Level 1 Depth / Length
30 mm
Package Level 1 Height
109 mm
Package Level 1 Gross Weight
0.177 kg
Package Level 1 EAN
4013614502903
Object Classification Code
B
ETIM 7
EC001447 - (Fill) level monitoring relay
ETIM 8
EC001447 - (Fill) level monitoring relay
ETIM 9
EC001447 - (Fill) level monitoring relay
eClass
V11.0 : 27371813
UNSPSC
39122331
E-Number (Finland)
2712569
E-Number (Norway)
4189436
Feature: 1 c/o SPDT contact rated at 250 V / 4 A; Business Impact: Enables direct pump control and reliable dry-run protection, reducing controller complexity and downtime. Application: Pump skids and level-based automation in water treatment, chemical processing, and processing lines. Feature: Adjustable measuring range 5 to 100 kΩ with front-face potentiometers; Business Impact: Tailors sensitivity to conductivity and tank design, minimizing false triggers and waste. Application: Conductive-fluid tanks, sumps, and open basins. Feature: Dual rated supply 110-130 VAC or 220-240 VAC; Business Impact: Regional adaptability lowers wiring changes and accelerates global deployments. Application: Facilities spanning multiple voltage regions. Feature: Three electrodes with a sealable protective cover; Business Impact: Robust sensing with tamper resistance and easy maintenance. Application: Harsh environments requiring reliable electrode arrangements. Feature: Screw terminals with double-chamber cage connections; Business Impact: Secure, vibration-resistant wiring and straightforward termination. Application: DIN-rail mounted control panels and compact installations. Feature: Housing IP50, terminals IP20, ambient -25 to +60 C; Business Impact: High environmental tolerance reduces unplanned downtime and supports safe operation. Application: Industrial automation, warehouses, and process plants. Feature: Comprehensive standards and certifications; Business Impact: Facilitates regulatory compliance, supplier approvals, and audit readiness. Application: Global manufacturing ecosystems seeking dependable electronic relays for liquid level monitoring.
Get a Quick Quote for a ABB 1SVR730850R2100
Chat with us on WhatsApp - fast responses guaranteed
Need to speak with someone? We'll call you back within 2 hours during business hours
Interested in ABB 1SVR730850R2100?
Enquire Now
FAQs
ABB 1SVR730850R2100 is designed for DIN rail mounting using TH35-15 or TH35-7.5 profiles. It supports screw-terminal connections for flexible wiring and includes front-face potentiometers to adjust sensitivity without opening the housing. This combination simplifies panel layouts and reduces installation time while maintaining secure, vibration-resistant terminations in busy electrical cabinets. Suitable for global projects, it aligns with IP50 housing and 3-electrode configurations.
CM-ENS.13S uses an open-circuit sensing principle and a 1 c/o SPDT output rated 250 V at 4 A, enabling direct pump control and reliable dry-run protection. The adjustable 5–100 kΩ range and three-electrode configuration let you tailor sensitivity for various conductive fluids, while screw terminals and double-chamber terminals deliver secure wiring in industrial cabinets.
This device carries CE and UKCA markings for Europe, UL/CSA for North America, CCC for China, and DNV GL in its certification suite, along with RoHS and REACH declarations. These certifications support regulatory compliance, safety certification, and supply-chain acceptance, reducing time-to-market for global deployments and ensuring performance under UL 508 and IEC 61000-series environmental standards. They also align with CCC and SCIP traceability requirements for responsible sourcing.
The CM-ENS.13S offers screw-terminal wiring, front-face sensitivity adjustment, and a sealable cover to guard against tampering, all supporting quick commissioning and easy ongoing maintenance. DIN-rail mounting options and supplied electrodes simplify installation in compact panels, while the open-circuit sensing method minimizes fouling-related drift. Accessories like additional electrodes extend life in harsh environments.
Operating from 110–130 V AC or 220–240 V AC, the CM-ENS.13S supports your regional mains without rewiring, with a 50/60 Hz supply and SPDT output rated up to 4 A. It handles ambient temperatures from -25 to +60 C and up to 2000 m altitude. Ensure IP50 housing, IP20 terminals, and appropriate fusing per system design.