ABB 1SVR730885R3300 Three-phase monitoring relay - UL/CSA B300

Part Number: 1SVR730885R3300
Manufacturer
ABB
Part number
1SVR730885R3300

Quick Summary

CM-MPS.21S three-phase monitoring relay provides comprehensive phase monitoring for electrical power systems. It protects against over- and undervoltage, phase failure, unbalance, and an interrupted neutral, helping you prevent unexpected downtime. This device carries CE, UL/CSA, and cULus certifications to support global panel approvals while offering robust IP50 housing. Its DIN-rail mounting and screw-terminal design simplify installation in compact control cabinets. By combining precise protection with a small footprint, the CM-MPS.21S scales with your power-monitoring strategy and reduces wiring complexity across multiple machines and lines.

Product Information

Extended Description

1SVR730885R3300 ABB: The CM-MPS.21S is a multifunctional relay from the CM three-phase monitors range. It operates with a rated control supply voltage / three-phase measuring voltage of 180-280 V AC 50/60 Hz and has a 2 c/o (SPDT) output with contacts rated at 250 V / 4 A. This relay is also suitable to monitor single-phase mains. It monitors all phase parameters such as over/undervoltage, phase unbalance, phase failure as well as an interrupted neutral. The corresponding threshold values are adjustable. Phase sequence monitoring as well as an ON or OFF tripping delay are selectable. The tripping delay is adjustable over a range of instantaneous to 30 s (0, 0.1-30 s). A sealable transparent cover for protection against unauthorized changes is available as accessory. The device offers screw connection technology with double-chamber cage connection terminals.
Country of Origin
Germany (DE)
Lead Time
0 day
Made To Order
No
Warranty Return
Product under warranty must be returned
Product Sales Status
Active
Quote Only
No
Stocked At Warehouses
AETAD009EXPU
Country of Origin
Germany (DE)
Lead Time
0 day
Made To Order
No
Warranty Return
Product under warranty must be returned
Product Sales Status
Active
Quote Only
No
Stocked At Warehouses
BRABB008EXPU
Country of Origin
Germany (DE)
Lead Time
0 day
Made To Order
No
Warranty Return
Product under warranty must be returned
Product Sales Status
Active
Quote Only
No
Stocked At Warehouses
CHSEC006EXPU
Lead Time
160 day
Warranty Return
Product under warranty must be returned
Stocked At Warehouses
CZABB004EXPU
Country of Origin
Germany (DE)
Made To Order
No
Product Sales Status
Active
Quote Only
No
Country of Origin
Germany (DE)
Lead Time
28 day
Made To Order
No
Product Sales Status
Active
Quote Only
No
Stocked At Warehouses
CZABB006EXPU
Warranty Return
Product under warranty must be returned
EAN
4016779851893
Minimum Order Quantity
1 piece
Customs Tariff Number
85364900
Data Sheet, Technical Information
Data sheet - CM-MPS.21, CM-MPS.41 Multifunctional three-phase monitoring relays with screw or push-in terminals
Instructions and Manuals
Instruction Sheet / Manual - CM-MPx, CM-PxS Three-phase monitoring relays | Installation instructions - CM-MPx, CM-PxS Three-phase monitoring relays
CAD Dimensional Drawing
Information - 2D and 3D files for CAD systems
Product Net Width
22.5 mm
Product Net Height
85.6 mm
Product Net Depth / Length
103.7 mm
Product Net Weight
0.146 kg
Function
Over- and undervoltage monitoring | Phase failure detection | Phase unbalance detection | Phase sequence monitoring | Interrupted neutral monitoring
Measuring Range
(L-N) 180 ... 280 V AC
Time Range
≤ 200 ms start-up delay | 0 s or 0.1 ... 30 s tripping delay (ON or OFF)
Rated Control Supply Voltage (Us)
(L-N) 180 ... 280 V AC
Rated Frequency (f)
Supply Circuit 50/60 Hz
Output
2 c/o (SPDT) contacts
Terminal Type
Screw Terminals
Rated Operational Current AC-12 (Ie)
(230 V) 4 A
Rated Operational Current AC-15 (Ie)
(230 V) 3 A
Rated Operational Current DC-12 (Ie)
(24 V) 4 A
Rated Operational Current DC-13 (Ie)
(24 V) 2 A
Minimum Switching Capacity
24 V | 10 mA
Rated Impulse Withstand Voltage (Uimp)
Input Circuit 6 kV | Output Circuit 4 kV
Rated Insulation Voltage (Ui)
Input Circuit / Output Circuit 600 V | Output Circuit 1 / Output Circuit 2 300 V
Degree of Protection
Housing IP50 | Terminals IP20
Overvoltage Category
III
Pollution Degree
3
Short-Circuit Protective Devices
Output Circuit NC - F Type Fuses 6 A | Output Circuit NO - F Type Fuses 10 A
Electrical Durability
AC-12 100000 cycle
Mechanical Durability
Nr. Operations 30000000 cycle
Connecting Capacity
Flexible with Ferrule 1x 0.5 ... 2.5 mm² | Flexible with Ferrule 2x 0.5 ... 1.5 mm² | Flexible with Insulated Ferrule 1x 0.5 ... 2.5 mm² | Flexible with Insulated Ferrule 2x 0.5 ... 1.5 mm² | Flexible 1x 0.5 ... 2.5 mm² | Flexible 2x 0.5 ... 1.5 mm² | Rigid 1x 0.5 ... 4 mm² | Rigid 2x 0.5 ... 2.5 mm²
Tightening Torque
0.6 ... 0.8 N·m
Wire Stripping Length
8 mm
Recommended Screw Driver
4.5 | 0.8 x 4 | Pozidriv 1
Mounting Position
1 ... 6
Mounting on DIN Rail
TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715 | TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715
Standards
CAN/CSA C22.2 No.14 | IEC/EN 63000 | IEC/EN 60255-27 | IEC/EN 61000-6-2 | IEC/EN 61000-6-3 | UL 508
Maximum Operating Voltage UL/CSA
Output Circuit 300 V AC
Contact Rating UL/CSA
B300
Connecting Capacity UL/CSA
Flexible 1x 18-14 AWG | Flexible 2x 18-16 AWG | Rigid 2x 20-14 AWG | Rigid 1x 20-12 AWG
Tightening Torque UL/CSA
7.08 in·lb
Pilot Duty UL/CSA
B300
Flammability According to UL94
V-0
Ambient Air Temperature
Operation -25 ... +60 °C | Storage -40 ... +85 °C
Maximum Operating Altitude Permissible
Without Derating 2000 m
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
REACH Declaration
REACh Info for Electronic Relays and Controls
RoHS Information
RoHS Declaration of conformity for Electronic Relays and Controls
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
SCIP
eca471ea-b2ec-42a3-a10d-98ecd0c53f85 Germany (DE)
Simplified SCIP
10940a4a-e940-4cb4-ab1a-14fa0ca5d858 Finland (FI) | 6c9668f9-700c-4253-94bb-447f49479950 Bulgaria (BG) | 2a085096-4e94-4ec3-beed-fa4546cd11ce Germany (DE) | d775775a-b045-470e-b14d-d02a1569f386 France (FR) | 3baf56c9-183b-4af5-96dd-f295b02b612b Belgium (BE) | 6f35dfe6-5cb0-4ceb-804f-cd0f88553cf1 Hungary (HU) | 908b5687-8ae8-4dec-a612-c87d194295e1 Portugal (PT) | 9812ee27-0ec8-4d3b-9af7-ec11d2c0e745 Spain (ES) | 6b52f8db-a754-4834-bd77-f23da8c521dc Sweden (SE) | ced1c277-2ab0-476e-9009-69c57b1c56ec France (FR) | 387fe0a5-5087-4437-900a-1e56e10080e5 Belgium (BE) | cc119799-5e6b-4c26-91df-e2720ad644a7 Hungary (HU) | fba9cca7-aa0c-42d8-9355-255eb8c0c279 Germany (DE) | 1a5edcf2-b120-4c20-93a6-74da1d7751dd Poland (PL) | 54db8fa0-c077-481a-9271-59fdbeae141b Denmark (DK) | 989a969e-61ba-4676-8324-a392a41454a1 Czech Republic (CZ) | 9fb297f2-f95a-4142-b180-799094d1462d Germany (DE) | c8742e04-7769-46c7-aa2a-386a3b27ad0b Netherlands (NL) | 70a40233-c45e-4bb3-a847-1e303a6ace18 Germany (DE) | 1e5d7778-a702-4565-bdaf-9cd6988e05a2 Italy (IT) | 9ecb932a-f3b1-4f09-9b92-55ddc37bbc08 Croatia (HR) | 075ab626-1a3a-44bb-a7cf-115b7e8d66ad Norway (NO) | 69e65afe-7e9e-4d2a-9e87-354fb67d26ba Poland (PL) | 3c53ecec-aa37-4f52-94a3-16643936547b Estonia (EE) | 20c0b904-4dc3-4f79-bf25-8466e75c6d63 Poland (PL) | c35e213a-4a38-4ad2-b45c-f5e3b8472e04 Sweden (SE) | edf05874-9a61-4c68-8689-9f052b0ef195 Greece (GR)
Toxic Substances Control Act - TSCA
Toxic Substances Control Act (TSCA) declaration for Electronic Relays and Controls
CB Certificate
CB_DK-27947-UL
CQC Certificate
CQC Certificate, Electronic Measuring and Monitoring Relays, CM-MPS.., CM-PVS.., CM-PSS..,CM-PAS.., CM-UFS.., CM-MPN.., Made in Germany
cULus Certificate
cULus508_20120829-E140448
Declaration of Conformity - CCC
CCC Certificate, Electronic Measuring and Monitoring Relays, CM-MPS.., CM-PVS.., CM-PSS..,CM-PAS.., CM-MPN.., Made in Germany
Declaration of Conformity - CE
EU Declaration of Conformity - CM-xxS.xxx, CM-xxN.xxx Three-phase monitoring relays
Declaration of Conformity - UKCA
UK Declaration of Conformity - CM-xxS.xxx, CM-xxN.xxx Three-phase monitoring relays
DNV GL Certificate
DNV GL Certificate - CM-MPx.xxx, CM-PAS.xxx, CM-PSS.xxx,CM-PVS.xxx, and CM-PFS.x Three-phase monitoring relays with screw or push-in terminals
Package Level 1 Units
box 1 piece
Package Level 1 Width
97 mm
Package Level 1 Depth / Length
30 mm
Package Level 1 Height
109 mm
Package Level 1 Gross Weight
0.171 kg
Package Level 1 EAN
4016779851893
Object Classification Code
B
ETIM 7
EC001441 - Phase monitoring relay
ETIM 8
EC001441 - Phase monitoring relay
ETIM 9
EC001441 - Phase monitoring relay
eClass
V11.0 : 27371803
UNSPSC
39122332
E-Number (Finland)
2712272
E-Number (Norway)
4188132
E-Number (Sweden)
3860590
Feature → Business Impact → Application: Measuring range of 180-280 V AC with 50/60 Hz supply ensures accurate detection across typical European and international mains, reducing nuisance trips and enabling stable machine operation in panel setups. This translates to higher line uptime and lower maintenance costs for automation skids. Feature → 2 c/o SPDT contacts supports direct control logic and signaling without additional relays, cutting component count and wiring time in motor control centers and machine panels. Feature → Adjustable threshold values and selectable ON/OFF delays (0 to 0.1-30 s) allow fine-tuning to match application dynamics, minimizing false trips in processes with varying load profiles. Feature → Phase sequence monitoring, phase unbalance, and interrupted neutral detection deliver comprehensive protection for three-phase systems, helping meet stringent electrical standards in manufacturing lines. Feature → Screw terminal connections and double-chamber cage terminals offer secure, vibration-resistant wiring suitable for DIN rails and compact enclosures, expediting installation and service. Feature → IP50 housing with DIN-rail mounting supports safe, compliant installation in rugged industrial environments, while temperature range from -25 to +60 °C ensures reliable operation in factories and data centers. Certification coverage including CE, UL/CSA, and cULus, plus RoHS and REACH compliance, simplifies cross-border procurement and regulatory adherence for global OEMs and integrators.

Get a Quick Quote for a ABB 1SVR730885R3300

Chat with us on WhatsApp - fast responses guaranteed

Need to speak with someone? We'll call you back within 2 hours during business hours

Interested in ABB 1SVR730885R3300? Enquire Now

FAQs

CM-MPS.21S mounts on DIN rails TH35-7.5 or TH35-15 and uses screw terminals with double-chamber cage construction for secure, vibration-resistant wiring. Stripping length is 8 mm, and tightening torque is 0.6-0.8 N·m, enabling quick, reliable setup in standard control cabinets.
Measuring range is (L-N) 180-280 V AC with 50/60 Hz supply. It provides 2 c/o SPDT outputs with a rated current of 4 A at 230 V AC (I_e AC-12) and 3 A (I_e AC-15). This supports direct control of small relays or signaling devices without extra relays and reduces panel wiring.
Yes. It monitors over/undervoltage, phase failure, phase unbalance, phase sequence, and interrupted neutral, making it ideal for machine control panels, power distribution, and industrial drives where reliable protection prevents unplanned downtime.
The relay is CE-marked and UL/CSA certified, with cULus and UKCA references in its documentation. It also complies with RoHS and REACH, and features IPC64-equivalent insulation ratings. This enables streamlined procurement and regulatory compliance across Europe, North America, and other markets.
The device is designed for long life with high electrical and mechanical durability. It offers a warranty with standard returns for warranty-related issues and is compatible with spare parts and accessories (e.g., sealable covers). The measurable ROI comes from reduced downtime, lower relay counts, and simplified wiring in control panels.