ABB 2CDS233001R0324 Miniature Circuit Breaker - SH200T 3P 32A C
Part Number: 2CDS233001R0324
Quick Summary
ABB Miniature Circuit Breaker SH200T protects electrical circuits in homes and light commercial installations. Nuisance trips and inadequate overload protection can disrupt operations and increase maintenance costs. This range complies with IEC/EN 60898-1, CE declarations, and IP ratings while offering RoHS/REACH compliance for safe, sustainable installations. Designed for DIN rail mounting with cage terminals, it delivers reliable protection with a compact form factor suitable for 400 V systems and 3P configurations.
Product Information
Extended Description
2CDS233001R0324 ABB: Compact Home SH200T miniature circuit breakers are current limiting. They have two different tripping mechanisms, the delayed thermal tripping mechanism for overload protection and the electromechanic tripping mechanism for short circuit protection. They are available in different characteristics (B,C), configurations (1P,1P+N,2P,3P,3P+N,4P), breaking capacities (up to 3 kA at 230/400 V AC) and rated currents (up to 40 A). All MCBs of the product range SH200T comply with IEC/EN 60898-1, allowing the use for residential applications.
Environmental Product Declaration - EPD
EPD HOME MCB 0.5A to 63A | PEP ABBG-00339-V01.01-EN.pdf
Tripping Characteristic
C
Rated Operational Voltage
acc. to IEC 60898-1 400 V
Operational Voltage
Maximum (Incl. Tolerance) 440 V AC | Minimum 12 V AC
Rated Insulation Voltage (Ui)
acc. to IEC/EN 60664-1 440 V
Rated Impulse Withstand Voltage (Uimp)
4 kV | at 2000 m 5 kV | at Sea Level 6.2 kV
Dielectric Test Voltage
50/60 Hz-1 min: 2 kV
Input Voltage Type
AC
Rated Current (In)
32 A
Rated Short-Circuit Capacity
(AC) 3 kA | (400 V AC) 3 kA | (400 V) 3 kA
Rated Conditional Short-Circuit Current (Inc)
(230 V) 3 kA | (400 V) 3 kA
Rated Frequency (f)
50 / 60 Hz
Power Loss
11.1 W | at Rated Operating Conditions per Pole 3.7 W
Power Supply Connection
Arbitrary
Contact Position Indication
ON / OFF
Energy Limiting Class
3
Electrical Endurance
10000 AC cycle
Mechanical Endurance
20000 cycle
Number of Protected Poles
3
Number of Poles
3P
Overvoltage Category
III
Tightening Torque
2 N·m
Actuator Type
Toggle
Screw Terminal Type
Cage Terminal
Actuator Marking
I / O
Actuator Material
Insulation Group II, Black, Sealable
Housing Material
Insulation Group II, RAL 7035
Mounting on DIN Rail
TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715 | TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
Mounting Position
any
Recommended Screw Driver
Pozidriv 2
Accessories Available
No
Connecting Capacity
Conductor 25 / 25 mm² | Flexible with Ferrule 0.75 ... 16 mm² | Flexible 0.75 ... 16 mm² | Rigid 0.75 ... 25 mm² | Stranded 0.75 ... 25 mm²
Installation Size
acc. to DIN 43880 1
Terminal Type
Screw Terminals
RoHS Information
2CDK400030D0201
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
RoHS Date
0335
REACH Declaration
Declaration regarding the REACH-Regulation
REACH Information
True - contains substances > 0.1 mass percentage
REACH Date
20240821
Conflict Minerals Reporting Template (CMRT)
Conflict Minerals Reporting Template
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
WEEE B2C / B2B
Business To Business
Ambient Air Temperature
Operation -25 ... +55 °C | Storage -40 ... +70 °C
Reference Ambient Air Temperature
30 °C
Degree of Protection
IP20 | Enclosure with Cover IP40
Pollution Degree
2
Environmental Conditions
28 cycles | with 55 °C / 90-96 % | and 25 °C / 95-100 %
Resistance to Vibrations
20 Cycles with Load 0.8 In: 5g 5 ... 150 ... 5 Hz
Resistance to Shock acc. to IEC 60068-2-27
25g 2 shocks 13 ms
Environmental Information
2CDK400030D0201
Width in Number of Modular Spacings
3.0
Product Net Width
52.5 mm
Product Net Height
85 mm
Product Net Depth / Length
69 mm
Product Net Weight
0.375 kg
Pole Net Weight
0.125 kg
Built-In Depth (t2)
69 mm
Package Level 1 Units
carton 1 piece
Package Level 1 Gross Weight
0.39 kg
Declaration of Conformity - CE
EU Declaration of Conformity SH200_SH200M_SH200T_SH200L
Instructions and Manuals
MCB - general mounting instruction
Data Sheet, Technical Information
Compact Home Protection and comfort system for your home
ETIM 8
EC000042 - Miniature circuit breaker (MCB)
ETIM 9
EC000042 - Miniature circuit breaker (MCB)
UNSPSC
39121603
eClass
V11.0 : 27141901
IDEA Granular Category Code (IGCC)
4897 >> Miniature circuit breakers
Object Classification Code
F
Standards
IEC/EN 60898-1
Certification Agency
EN | IEC
Current protection is achieved with a dual tripping mechanism: delayed thermal tripping for overload and electromechanical tripping for short circuits. This combination reduces nuisance trips while safely isolating faults, extending the life of connected equipment and downstream devices. In practical terms, you gain reliable protection in home or small business panels with minimal maintenance. The 3P 32 A C characteristic on 400 V AC enables selective coordination across three-phase networks, helping avoid unnecessary shutdowns in other circuits during faults and improving uptime for critical loads such as pumps, lighting, and control gear. Compact, DIN-rail-ready design (TH35-15) with a 52.5 mm width and 85 mm height simplifies panel layout; cage terminals and a wide conductor range (0.75 to 25 mm²) support diverse wiring schemes and ferrule-compatible terminations, reducing installation time. Energy Limiting Class 3 reduces let-through energy, protecting downstream devices and lowering energy losses during faults. With electrical endurance of 10,000 AC cycles and mechanical endurance of 20,000 cycles, the device withstands frequent operation in demanding environments. RoHS and REACH compliance, along with WEEE category alignment, ensures sustainable, future-ready installations and easier regulatory reporting. Field-verified compatibility with 3P configurations, cage terminals, and DIN rail mounting supports straightforward integration into existing electrical panels and ABB ECO-solution ecosystems.
Get a Quick Quote for a ABB 2CDS233001R0324
Chat with us on WhatsApp - fast responses guaranteed
Need to speak with someone? We'll call you back within 2 hours during business hours
Interested in ABB 2CDS233001R0324?
Enquire Now
FAQs
The SH200T supports DIN rail mounting on TH35-15 or TH35-7.5 rails and uses screw terminals or cage terminals. It accepts conductors from 0.75 to 25 mm², with ferrules, enabling quick, reliable wiring in compact panels.
This device uses a C-type trip characteristic with a rated current of 32 A and a rated operational voltage of 400 V AC, providing balanced overload and short-circuit protection for three-phase circuits.
Yes. The 3P configuration supports 3-phase power distribution in homes and small offices, delivering coordinated protection across three live conductors with reliable fault isolation.
It complies with IEC/EN 60898-1, carries CE declarations, and supports RoHS, REACH, and WEEE requirements, ensuring safety, sustainability, and regulatory alignment.
It offers 10,000 electrical life cycles and 20,000 mechanical cycles, reducing maintenance downtime. Energy-limiting Class 3 helps minimize let-through energy during faults, contributing to safer, more efficient operation.