ABB 2TFC000662R1001 Moulded Case CB - IEC 60947-2

Manufacturer
ABB
Part number
2TFC000662R1001

Quick Summary

ABB 2TFC000662R1001 Moulded Case CB protects low-voltage distribution in industrial automation panels. Engineers often struggle with balancing reliable fault protection against space constraints and installation complexity. This device aligns with CE certification, IEC 60947-2 standards, and RoHS/REACH compliance to support regulatory and environmental requirements. For panel builders and maintenance teams, it translates to faster commissioning, predictable performance, and lower lifecycle costs while maintaining electrical protection & circuit control excellence in demanding environments.

Product Information

Extended Description

2TFC000662R1001 ABB: C.BREAKER TMAX XT2L 160 FIXED THREE-POLE WITH FRONT TERMINALS AND SOLID-STATE RELEASE IN AC EKIP C Dip LSIG R 63 A
ABB EcoSolutions
Yes
ABB Site Meeting Group Waste To Landfill Target
UL 2799 Zero Waste To Landfill Validation available
End Of Life Disassembling Instructions
Disassembly instructions Tmax XT XT2 ELT
Environmental Product Declaration - EPD
EPD Tmax XT XT2 ELT (CN)
Recyclability Rate of the Product acc. to EN45555
Design for Closing Resource Loops - Standard EN45555 - 55.7 %
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
Document availability on demand
Environmental Information
Product Environmental Information Tmax XT
Customs Tariff Number
85362000
Product Net Width
90 mm
Product Net Height
130 mm
Product Net Depth / Length
82.5 mm
Product Net Weight
1.2 kg
Product Name
Moulded Case Circuit Breaker
Product Type
CB
Version
F
Current Type
AC
Electrical Durability
8000 cycle | 120 cycles per hour
Mechanical Durability
25000 cycle | 240 cycles per hour
Number of Poles
3P
Power Loss
at Rated Operating Conditions per Pole 1.70 W
Rated Current (In)
63 A
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
690 V AC | 500 V DC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 150 kA | (230 V AC) 150 kA | (240 V AC) 150 kA | (380 V AC) 120 kA | (415 V AC) 120 kA | (440 V AC) 100 kA | (500 V AC) 60 kA | (525 V AC) 36 kA | (690 V AC) 15 kA | (250 V DC) 2 Poles in Series 85 kA | (500 V DC) 3 Poles in Series 85 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 150 kA | (230 V AC) 150 kA | (240 V AC) 150 kA | (380 V AC) 120 kA | (415 V AC) 120 kA | (440 V AC) 100 kA | (500 V AC) 60 kA | (525 V AC) 36 kA | (690 V AC) 18 kA | (250 V DC) 2 Poles in Series 85 kA | (500 V DC) 3 Poles in Series 85 kA
Rated Uninterrupted Current (Iu)
160 A
Release
Ekip C Dip LSIG
Release Type
EL
Short-Circuit Performance Level
L
Standards
IEC 60947-2 | GB/T 14028.2
Sub-type
XT2
Terminal Connection Type
Fixed Circuit-Breakers
Data Sheet, Technical Information
SACE Tmax XT IEC Low voltage molded case circuit-breakers Catalog | SACE Tmax XT IEC TECHNICAL CHARACTERISTICS Low voltage molded case circuit-breakers
Declaration of Conformity - CE
EC Declaration of Conformity Tmax XT2
Instructions and Manuals
Installation Instructions XT2 | Release assembly XT2-XT4 | Ekip C Dip LSI, Ekip C Dip LSIG and LIG XT2-XT4
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
The 3P fixed breaker with front terminals and Ekip C Dip LSIG release delivers compact installation and precise tripping, reducing panel footprint and downtime. Business impact: simplified wiring and faster fault isolation in control cabinets, boosting overall installation efficiency and safety in automation lines. Applications: motor control centers and panel feeders where reliable AC protection is essential. The device supports high fault current with Ics up to 150 kA and Icu up to 150 kA across multiple voltages, providing robust protection in 230–240 V and up to 690 V systems, which translates to reduced downtime and equipment damage. The unit operates at 690 V AC and 500 V DC with rated insulation 1000 V, ensuring compatibility with modern industrial controls and energy-efficient designs. Durability metrics show electrical life up to 8000 cycles and mechanical life up to 25000 cycles, delivering predictable performance and longer service life in high-usage environments. In terms of compliance and sustainability, it carries RoHS and REACH declarations, maintains IEC 60947-2 compliance, and aligns with WEEE guidelines, while ESG-focused features include End-of-Life disassembly instructions and a designed recyclability rate per EN45555. Compatibility notes: fixed-circuit-breaker footprint (90 mm width, 130 mm height, 82.5 mm depth) supports standard DIN enclosures, and front-terminal access simplifies field retrofit. For procurement, the Customs tariff 85362000 and product weight of 1.2 kg aid logistics planning in large projects.

Get a Quick Quote for a ABB 2TFC000662R1001

Chat with us on WhatsApp - fast responses guaranteed

Need to speak with someone? We'll call you back within 2 hours during business hours

Interested in ABB 2TFC000662R1001? Enquire Now

FAQs

This 3P fixed circuit breaker uses front terminals for straightforward wiring and mounting in standard DIN rail or panel enclosures. Verify the 90 mm width and 130 mm height fit your enclosure, then secure with appropriate mounting hardware. Its LSIG release type supports quick, reliable tripping, while the 690 V AC rated operational voltage aligns with common industrial control panels. Always follow the installation instructions to ensure correct torque on terminals and proper cooling clearance.
The device offers a rated current of 63 A, and short-circuit breaking capacities (Ics/Icu) up to 150 kA depending on the system voltage, with a rated insulation voltage of 1000 V and rated operational voltage of 690 V AC / 500 V DC. These ratings support reliable fault interruption across a broad range of low-voltage applications, minimizing arc energy, equipment damage, and downtime during faults.
Yes. The XT2-based Tmax design, including the Ekip C Dip LSIG release, supports motor feeders and control circuit protection in industrial panels. With 3P configuration, fixed terminals, and robust Ics/Icu ratings, it provides reliable motor protection against short circuits while enabling straightforward installation and maintenance in motor control centers and automation cabinets.
The unit complies with IEC 60947-2 and GB/T 14028.2 standards, and it carries CE declarations, RoHS, and REACH compliance. It also aligns with WEEE Category 5 for waste electrical and electronic equipment. End-of-Life disassembly instructions are provided, supporting responsible disposal and recycling in line with ABB EcoSolutions.
With electrical life up to 8000 cycles and mechanical life up to 25000 cycles, the breaker offers durable, long-term protection with reduced maintenance frequency. Its front-terminal design and LSIG release simplify diagnostics and replacement, contributing to lower maintenance time and labor costs while maintaining high system availability in production lines.