ABB 2TFC000664R1001 Moulded Case CB - IEC 60947-2

Manufacturer
ABB
Part number
2TFC000664R1001

Quick Summary

ABB 2TFC000664R1001 Moulded Case CB provides reliable overcurrent protection for industrial panels and machine racks. Engineers often contend with nuisance trips, limited wiring space, and maintenance challenges in high-density control cabinets. This device is CE compliant, aligns with IEC 60947-2, and supports RoHS/REACH declarations with an available EPD option. Integrating this 3P 160 A breaker reduces downtime and simplifies wiring thanks to fixed terminals and a solid-state Ekip C Dip LSIG release. Suitable for 690 V AC networks, it helps facilities meet safety and sustainability goals while delivering predictable protection for critical workloads.

Product Information

Extended Description

2TFC000664R1001 ABB: C.BREAKER TMAX XT2L 160 FIXED THREE-POLE WITH FRONT TERMINALS AND SOLID-STATE RELEASE IN AC EKIP C Dip LSIG R 160 A
ABB EcoSolutions
Yes
ABB Site Meeting Group Waste To Landfill Target
UL 2799 Zero Waste To Landfill Validation available
End Of Life Disassembling Instructions
Disassembly instructions Tmax XT XT2 ELT
Environmental Product Declaration - EPD
EPD Tmax XT XT2 ELT (CN)
Recyclability Rate of the Product acc. to EN45555
Design for Closing Resource Loops - Standard EN45555 - 55.7 %
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
Document availability on demand
Environmental Information
Product Environmental Information Tmax XT
Customs Tariff Number
85362000
Product Net Width
90 mm
Product Net Height
130 mm
Product Net Depth / Length
82.5 mm
Product Net Weight
1.2 kg
Product Name
Moulded Case Circuit Breaker
Product Type
CB
Version
F
Current Type
AC
Electrical Durability
8000 cycle | 120 cycles per hour
Mechanical Durability
25000 cycle | 240 cycles per hour
Number of Poles
3P
Power Loss
at Rated Operating Conditions per Pole 10.80 W
Rated Current (In)
160 A
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
690 V AC | 500 V DC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 150 kA | (230 V AC) 150 kA | (240 V AC) 150 kA | (380 V AC) 120 kA | (415 V AC) 120 kA | (440 V AC) 100 kA | (500 V AC) 60 kA | (525 V AC) 36 kA | (690 V AC) 15 kA | (250 V DC) 2 Poles in Series 85 kA | (500 V DC) 3 Poles in Series 85 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 150 kA | (230 V AC) 150 kA | (240 V AC) 150 kA | (380 V AC) 120 kA | (415 V AC) 120 kA | (440 V AC) 100 kA | (500 V AC) 60 kA | (525 V AC) 36 kA | (690 V AC) 18 kA | (250 V DC) 2 Poles in Series 85 kA | (500 V DC) 3 Poles in Series 85 kA
Rated Uninterrupted Current (Iu)
160 A
Release
Ekip C Dip LSIG
Release Type
EL
Short-Circuit Performance Level
L
Standards
IEC 60947-2 | GB/T 14028.2
Sub-type
XT2
Terminal Connection Type
Fixed Circuit-Breakers
Data Sheet, Technical Information
SACE Tmax XT IEC Low voltage molded case circuit-breakers Catalog | SACE Tmax XT IEC TECHNICAL CHARACTERISTICS Low voltage molded case circuit-breakers
Declaration of Conformity - CE
EC Declaration of Conformity Tmax XT2
Instructions and Manuals
Installation Instructions XT2 | Release assembly XT2-XT4 | Ekip C Dip LSI, Ekip C Dip LSIG and LIG XT2-XT4
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
Feature: Fixed three-pole design with front terminals and LSIG solid-state release — Business Impact: simplifies wiring, speeds installation, and enables reliable, predictable tripping in demanding environments — Application: panel feeders and machine control cabinets where fast, accessible wiring is essential. Feature: 160 A rated current with Ics up to 150 kA and Icu up to 85 kA (DC) — Business Impact: high fault tolerance and reduced risk of nuisance outages, improving uptime and equipment protection — Application: motor control centers and distribution boards in medium to large industrial facilities. Feature: Uimp 8 kV and Ui 1000 V with 690 V AC / 500 V DC rating — Business Impact: robust insulation and surge withstand capabilities for modern, multi-voltage systems — Application: critical power networks and mixed-voltage panels. Feature: Compact footprint (90 mm W x 130 mm H x 82.5 mm D) with 1.2 kg weight and 10.80 W per pole power loss — Business Impact: space-efficient installation and energy-conscious operation, enabling denser panels without overheating — Application: space-constrained control panels and compact switchgear assemblies. Feature: Compliance and sustainability data including IEC 60947-2, RoHS/REACH, EPD option, 55.7% recyclability per EN45555 — Business Impact: helps procurement align with regulatory and environmental targets while providing clear end-of-life handling — Application: eco-friendly programs and responsible sourcing in capital projects.

Get a Quick Quote for a ABB 2TFC000664R1001

Chat with us on WhatsApp - fast responses guaranteed

Need to speak with someone? We'll call you back within 2 hours during business hours

Interested in ABB 2TFC000664R1001? Enquire Now

FAQs

This 3P fixed circuit-breaker uses front terminals, allowing straightforward wiring and quick replacement in compatible panels. Verify panel clearance for a 90 mm wide device, ensure 690 VAC maximum voltage, and follow the installation instructions XT2-XT4 for the Ekip C Dip LSIG release. Use proper torque values and wiring practices to maintain safety and performance.
Key specs include 160 A rated current, 3 poles, 690 V AC / 500 V DC rated operational voltage, 8 kV rated impulse withstand, and 150 kA Ics with 85 kA Icu. The device complies with IEC 60947-2, RoHS/REACH, and offers front-terminal wiring and a fixed design that supports reliable short-circuit protection in industrial networks.
Yes. The 2TFC000664R1001 is designed for industrial distribution and machine control panels. Its XT2L 160 A rating, solid-state LSIG release, and fixed front-terminal configuration make it ideal for dense panels where space is at a premium and reliable protection is a must for motors and feeders.
The device is CE compliant, adheres to IEC 60947-2, and supports RoHS/REACH declarations. ABB also provides end-of-life and recycling information, including an EPD option and EN45555 recyclability data, helping you meet regulatory and sustainability targets in procurement.
Electrical durability is rated at roughly 8000 cycles and 25000 mechanical cycles, with 10.80 W power loss per pole. The front-terminal design simplifies inspection and maintenance, while the LSIG release supports reliable operation. Regular panel checks and following ABB installation guidelines optimize uptime and ROI over the breaker’s life.