ABB 2TFH100003R1001 Moulded Case Circuit Breaker - 25 kA Icu

Part Number: 2TFH100003R1001
Manufacturer
ABB
Part number
2TFH100003R1001

Quick Summary

ABB 2TFH100003R1001 Moulded Case Circuit Breaker protects industrial switchgear in control panels and distribution boards. Downtime and equipment damage rise when protection devices trip unreliably under mixed AC and DC loads; this MCCB delivers fast, predictable responses. This unit meets CE conformity and IEC60947-2/GB/T 14028.2 standards, with RoHS compliance and CMRT reporting to support global procurement. Designed for the SACE Tmax XT family and front‑terminal wiring, it simplifies panel assembly, reduces wiring errors, and lowers total cost of ownership.

Product Information

Extended Description

2TFH100003R1001 ABB: XT1B160 TMD25/450 FFC 3P
Environmental Product Declaration - EPD
NoDecNee
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
Environmental Information
Breakers - Packaging disposal information
Customs Tariff Number
85362000
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Version
F
Current Type
AC/DC
Electrical Durability
8000 cycle | 120 cycles per hour
Mechanical Durability
25000 cycle | 240 cycles per hour
Number of Poles
3P
Power Loss
at Rated Operating Conditions per Pole 2 W
Rated Current (In)
25 A
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
800 V
Rated Operational Voltage
690 V AC | 500 V DC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 25 kA | (230 V AC) 25 kA | (240 V AC) 25 kA | (380 V AC) 18 kA | (415 V AC) 18 kA | (440 V AC) 11.5 kA | (500 V AC) 8 kA | (525 V AC) 6 kA | (690 V AC) 3 kA | (250 V DC) 2 Poles in Series 18 kA | (500 V DC) 3 Poles in Series 18 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 25 kA | (230 V AC) 25 kA | (240 V AC) 25 kA | (380 V AC) 18 kA | (415 V AC) 18 kA | (440 V AC) 15 kA | (500 V AC) 8 kA | (525 V AC) 6 kA | (690 V AC) 3 kA | (250 V DC) 2 Poles in Series 18 kA | (500 V DC) 3 Poles in Series 18 kA
Rated Uninterrupted Current (Iu)
160 A
Release
TMD
Release Type
TM
Remarks
ATLAS
Short-Circuit Performance Level
B
Standards
IEC60947-2 | GB/T 14028.2
Sub-type
XT1
Terminal Connection Type
Front for Copper Cables
Data Sheet, Technical Information
SACE Tmax XT IEC Low voltage molded case circuit-breakers Catalog | SACE Tmax XT IEC TECHNICAL CHARACTERISTICS Low voltage molded case circuit-breakers
Declaration of Conformity - CE
EC Declaration of Conformity Tmax XT1
Instructions and Manuals
Installation instructions XT1
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
Three‑pole XT1 molded case design with a rated current of 25 A protects 3‑phase feeders for 690 V AC and 500 V DC systems. Business impact: precise, reliable protection reduces nuisance trips and supports effective coordination with upstream devices. Application: motor feeders and distribution panels in manufacturing and process environments. Rated Ultimate Short-Circuit Breaking Capacity (Icu) of 25 kA across multiple voltages provides robust protection during severe faults. Business impact: greater safety margins and reduced risk of equipment damage. Application: large motors, transformers, and critical drives in automated lines. Front for Copper Cables terminal connections enable straightforward wiring and serviceability. Business impact: faster installations and easier maintenance in tight panel spaces. Application: new builds and retrofit projects in control cabinets. Release features TMD and Type TM for selective coordination within protection schemes. Business impact: improved selectivity, minimized outages, and simplified upstream coordination. Application: motor controllers and feeder protection in complex automation architectures. Electrical durability of 8000 cycles and mechanical durability of 25000 cycles extend lifecycle and reduce maintenance costs. Business impact: lower lifecycle cost and fewer replacements. Application: high‑duty manufacturing lines with frequent switching. RoHS compliance and CMRT reporting ensure regulatory alignment and responsible sourcing. Business impact: smoother multinational procurement and risk mitigation. Application: global projects and OEM panel builds.

Get a Quick Quote for a ABB 2TFH100003R1001

Chat with us on WhatsApp - fast responses guaranteed

Need to speak with someone? We'll call you back within 2 hours during business hours

Interested in ABB 2TFH100003R1001? Enquire Now

FAQs

Choose a panel with adequate clearance for 3P protection and ensure front‑terminal access for copper cables. Verify torque specifications and wire sizing per IEC60947‑2 guidelines, and plan for straightforward field wiring to minimize commissioning time.
Rated current is 25 A, with rated operational voltage up to 690 V AC and 500 V DC. It offers Icu up to 25 kA and Ui of 800 V, along with an 8 kV impulse withstand. Confirm compatibility with your actual bus voltage and fault current level.
Yes. The device is specified for 690 V AC operation, 3P, with high short‑circuit ratings, making it suitable for reliable protection in 3‑phase low‑voltage networks found in industrial facilities.
It adheres to IEC60947‑2 and GB/T 14028.2, with CE conformity. RoHS compliance and CMRT reporting are also provided to support global procurement and environmental responsibility.
Electrical durability is rated at 8000 cycles and mechanical durability at 25000 cycles, supporting long service life in frequent switching environments. Front‑terminal wiring also simplifies inspection and replacement tasks.