ABB 2TFH100010R1001 Moulded Case Circuit Breaker - 8 kV Tmax XT
Part Number: 2TFH100010R1001
Quick Summary
ABB 2TFH100010R1001 Moulded Case Circuit Breaker is designed to protect low-voltage power circuits in control panels and machine builds. It helps prevent nuisance trips and unexpected downtime by delivering precise tripping characteristics in demanding environments. This model aligns with IEC60947-2 and GB/T 14028.2 standards, and carries CE conformity along with RoHS and CMRT declarations to support global compliance. With a 3P configuration, 125 A rating, and a flexible 690 VAC / 500 V DC operating range, it also supports cross-application deployment across AC and DC control systems. For panel builders and maintenance teams, the combination of reliability, availability, and easier sourcing adds tangible business value and smoother project execution.
Product Information
Extended Description
2TFH100010R1001 ABB: XT1B160 TMD125/1250 FEF 3P
Environmental Product Declaration - EPD
NoDecNee
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
Environmental Information
Breakers - Packaging disposal information
Customs Tariff Number
85362000
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Version
F
Current Type
AC/DC
Electrical Durability
8000 cycle | 120 cycles per hour
Mechanical Durability
25000 cycle | 240 cycles per hour
Number of Poles
3P
Power Loss
at Rated Operating Conditions per Pole 10.7 W
Rated Current (In)
125 A
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
800 V
Rated Operational Voltage
690 V AC | 500 V DC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 25 kA | (230 V AC) 25 kA | (240 V AC) 25 kA | (380 V AC) 18 kA | (415 V AC) 18 kA | (440 V AC) 11.5 kA | (500 V AC) 8 kA | (525 V AC) 6 kA | (690 V AC) 3 kA | (250 V DC) 2 Poles in Series 18 kA | (500 V DC) 3 Poles in Series 18 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 25 kA | (230 V AC) 25 kA | (240 V AC) 25 kA | (380 V AC) 18 kA | (415 V AC) 18 kA | (440 V AC) 15 kA | (500 V AC) 8 kA | (525 V AC) 6 kA | (690 V AC) 3 kA | (250 V DC) 2 Poles in Series 18 kA | (500 V DC) 3 Poles in Series 18 kA
Rated Uninterrupted Current (Iu)
160 A
Release
TMD
Release Type
TM
Remarks
ATLAS
Short-Circuit Performance Level
B
Standards
IEC60947-2 | GB/T 14028.2
Sub-type
XT1
Terminal Connection Type
Front Extended
Data Sheet, Technical Information
SACE Tmax XT IEC Low voltage molded case circuit-breakers Catalog | SACE Tmax XT IEC TECHNICAL CHARACTERISTICS Low voltage molded case circuit-breakers
Declaration of Conformity - CE
EC Declaration of Conformity Tmax XT1
Instructions and Manuals
Installation instructions XT1
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
Front Extended terminal connections simplify wiring routing in compact switchgear and control panels, reducing install time and potential termination errors while improving field reliability. The device’s 125 A rated current and 3P configuration, paired with a broad 690 VAC / 500 V DC operating range, enables a single protective solution across mixed loads, streamlining panel design and inventory. With Ics up to 25 kA and Uimp of 8 kV, the MCCB delivers robust fault interruption across varied voltages, reducing arc flash risk and improving uptime in demanding environments. The TM and TMD release options provide tailored protection for general purpose and motor-related applications, promoting proper coordination and selective tripping. Electrical durability of 8000 cycles and mechanical durability of 25000 cycles translate to longer service life, while a power loss of 10.7 W per pole supports cooler, energy-efficient operation in continuous duty panels. These features collectively support easier maintenance planning, faster commissioning, and lower total cost of ownership.
Get a Quick Quote for a ABB 2TFH100010R1001
Chat with us on WhatsApp - fast responses guaranteed
Need to speak with someone? We'll call you back within 2 hours during business hours
Interested in ABB 2TFH100010R1001?
Enquire Now
FAQs
Front Extended terminals simplify wiring in tight panels and support straightforward field assembly. Ensure correct conductor sizing and torque per ABB installation guidelines, and verify compatibility with 3P configurations to maintain proper coordination and reliable operation.
The device is rated for 125 A, operates at 690 VAC or 500 V DC, and provides 8 kV impulse withstand with 25 kA short-circuit withstand at common voltages. It supports AC/DC current type, and offers 3P protection with 160 A uninterrupted current for stable continuous operation.
It complies with IEC 60947-2 and GB/T 14028.2, includes a CE Declaration of Conformity, RoHS compliance, and CMRT reporting. WEEE categorization is also provided, aligning with global regulatory expectations for electrical protection devices.
TM and TMD releases provide distinct tripping characteristics for general protection and motor-related scenarios. This enables selective tripping and coordination within panels, reducing unnecessary outages and improving startup performance for motor loads.
Electrical durability is rated at 8000 cycles and mechanical durability at 25000 cycles, supporting longer service life with fewer replacements. A per-pole power loss of 10.7 W helps maintain cooler operation in continuous duty environments, lowering thermal stress and maintenance intervals.