ABB 2TFH100011R1001 Moulded Case Circuit Breaker - B-Curve

Part Number: 2TFH100011R1001
Manufacturer
ABB
Part number
2TFH100011R1001

Quick Summary

ABB 2TFH100011R1001 Moulded Case Circuit Breaker provides reliable overload protection for industrial power distribution panels. The device helps engineers prevent cascading faults by quickly isolating faults in low-voltage systems. It meets IEC 60947-2 and CE conformity, with RoHS and REACH declarations supporting sustainable procurement. For panel builders and machine integrators, Tmax XT compatibility, front-extended terminals, and a 3P, 160 A design simplify installation and maintenance, delivering safer, more efficient electrical protection in demanding manufacturing environments.

Product Information

Extended Description

2TFH100011R1001 ABB: XT1B160 TMD160/1600 FEF 3P
Environmental Product Declaration - EPD
NoDecNee
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
Environmental Information
Breakers - Packaging disposal information
Customs Tariff Number
85362000
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Version
F
Current Type
AC/DC
Electrical Durability
8000 cycle | 120 cycles per hour
Mechanical Durability
25000 cycle | 240 cycles per hour
Number of Poles
3P
Power Loss
at Rated Operating Conditions per Pole 15 W
Rated Current (In)
160 A
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
800 V
Rated Operational Voltage
690 V AC | 500 V DC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 25 kA | (230 V AC) 25 kA | (240 V AC) 25 kA | (380 V AC) 18 kA | (415 V AC) 18 kA | (440 V AC) 11.5 kA | (500 V AC) 8 kA | (525 V AC) 6 kA | (690 V AC) 3 kA | (250 V DC) 2 Poles in Series 18 kA | (500 V DC) 3 Poles in Series 18 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 25 kA | (230 V AC) 25 kA | (240 V AC) 25 kA | (380 V AC) 18 kA | (415 V AC) 18 kA | (440 V AC) 15 kA | (500 V AC) 8 kA | (525 V AC) 6 kA | (690 V AC) 3 kA | (250 V DC) 2 Poles in Series 18 kA | (500 V DC) 3 Poles in Series 18 kA
Rated Uninterrupted Current (Iu)
160 A
Release
TMD
Release Type
TM
Remarks
ATLAS
Short-Circuit Performance Level
B
Standards
IEC60947-2 | GB/T 14028.2
Sub-type
XT1
Terminal Connection Type
Front Extended
Data Sheet, Technical Information
SACE Tmax XT IEC Low voltage molded case circuit-breakers Catalog | SACE Tmax XT IEC TECHNICAL CHARACTERISTICS Low voltage molded case circuit-breakers
Declaration of Conformity - CE
EC Declaration of Conformity Tmax XT1
Instructions and Manuals
Installation instructions XT1
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
Feature: Rated current of 160 A enables precise protection for standard 3-phase loads without nuisance trips, reducing unplanned downtime. Benefit: Improves line availability and equipment longevity, supporting predictable production schedules in manufacturing and process industries. Application: Suitable for low-voltage control panels and distribution boards where compact, reliable protection is essential. Feature: Three-pole configuration (3P) ensures simultaneous protection across all phases, enabling balanced fault isolation. Benefit: Improves system safety and reliability in motor drives and automation architectures. Application: Ideal for machine control panels and energy distribution networks in packaging, automotive, and material handling sectors. Feature: Rated operational voltage of 690 V AC / 500 V DC and rated insulation voltage of 800 V allow compatibility with mixed-voltage installations. Benefit: Simplifies panel design and reduces component count while maintaining robust clearance and insulation margins. Application: Suitable for mixed-electrical environments and multi-voltage architectures. Feature: Rated impulse withstand voltage of 8 kV and short-circuit capacities up to 25 kA (Ics/Icu) deliver strong transient and fault performance. Benefit: Minimizes damage during surges and short circuits, lowering repair costs and downtime. Application: Critical for facilities exposed to electrical storms or industrial motor startups. Feature: Front extended terminals and Tmax XT family compatibility streamline installation and future upgrades. Benefit: Reduces wiring time and makes service access easier, lowering installation costs. Application: Preferred in retrofit projects and modular panel builds. Feature: Compliance with IEC 60947-2, RoHS, and REACH ensures regulatory alignment and sustainable procurement. Benefit: Supports audits and green initiatives while maintaining safety standards. Application: Widely used across global manufacturing and energy sectors where strict compliance is required.

Get a Quick Quote for a ABB 2TFH100011R1001

Chat with us on WhatsApp - fast responses guaranteed

Need to speak with someone? We'll call you back within 2 hours during business hours

Interested in ABB 2TFH100011R1001? Enquire Now

FAQs

The breaker is designed as a 3P unit with front extended terminals and is fully compatible with SACE Tmax XT assemblies. Its 160 A rating and 690 V AC / 500 V DC operation align with common low‑voltage panels, enabling straightforward retrofits and panel upgrades without additional adapters or rewiring. Compatibility with standard busbar layouts supports fast commissioning.
Key ratings include In = 160 A, Ui = 800 V, Uimp = 8 kV, Uo = 690 V AC / 500 V DC, and Ics/Icu up to 25 kA depending on voltage. It is a 3P device with a 3P configuration, RoHS/REACH compliant, and IEC 60947-2 standard. These specs ensure robust fault interruption, safe operation, and cross‑voltage applicability.
Yes. With 3P protection, 160 A rating, and 25 kA fault current capability, it suits motors and conveyors in process and packaging lines. The 690 V AC / 500 V DC operation broadens use across control cabinets, while front‑extended terminals simplify wiring in space‑constrained installations.
The device complies with IEC 60947-2 and is CE conformity documented via the EC Declaration of Conformity for Tmax XT. It is RoHS and REACH compliant, with CMRT and WEEE considerations in line with ABB Sace circuit breakers. These certifications support regulatory audits and sustainable procurement.
Expect reliable interruption performance with 25 kA Ics/Icu ratings and a predictable lifecycle given 8000 electrical cycles. The 15 W power loss per pole lowers thermal stress compared with higher‑loss alternatives, contributing to energy efficiency and reduced cooling costs during extended operation. Front terminals also ease maintenance and future expansions.