ABB 2TFH100029R1001 Moulded Case Circuit Breaker - 4P XT1
Part Number: 2TFH100029R1001
Quick Summary
ABB 2TFH100029R1001 Moulded Case Circuit Breaker provides reliable overcurrent protection for industrial panels. In tight spaces and demanding duty cycles, engineers need predictable trips, compact installation, and long service life. This device carries CE conformity with IEC60947-2 and GB/T 14028.2, plus RoHS and REACH declarations for regulated environments. As part of the SACE Tmax XT family, it integrates with ABB protection systems to simplify panel design, reduce spare parts, and lower maintenance costs. For safety-critical applications in factories, machines, and distribution boards, it delivers dependable performance while supporting sustainable, compliant electrical protection strategies.
Product Information
Extended Description
2TFH100029R1001 ABB: XT1B160 TMD100/1000 FFC 4P
Environmental Product Declaration - EPD
NoDecNee
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
Environmental Information
Breakers - Packaging disposal information
Customs Tariff Number
85362000
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Version
F
Current Type
AC/DC
Electrical Durability
8000 cycle | 120 cycles per hour
Mechanical Durability
25000 cycle | 240 cycles per hour
Number of Poles
4P
Power Loss
at Rated Operating Conditions per Pole 7.0 W
Rated Current (In)
100 A
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
800 V
Rated Operational Voltage
690 V AC | 500 V DC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 25 kA | (230 V AC) 25 kA | (240 V AC) 25 kA | (380 V AC) 18 kA | (415 V AC) 18 kA | (440 V AC) 11.5 kA | (500 V AC) 8 kA | (525 V AC) 6 kA | (690 V AC) 3 kA | (250 V DC) 2 Poles in Series 18 kA | (500 V DC) 3 Poles in Series 18 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 25 kA | (230 V AC) 25 kA | (240 V AC) 25 kA | (380 V AC) 18 kA | (415 V AC) 18 kA | (440 V AC) 15 kA | (500 V AC) 8 kA | (525 V AC) 6 kA | (690 V AC) 3 kA | (250 V DC) 2 Poles in Series 18 kA | (500 V DC) 3 Poles in Series 18 kA
Rated Uninterrupted Current (Iu)
160 A
Release
TMD
Release Type
TM
Short-Circuit Performance Level
B
Standards
IEC60947-2 | GB/T 14028.2
Sub-type
XT1
Terminal Connection Type
Front for Copper Cables
Data Sheet, Technical Information
SACE Tmax XT IEC Low voltage molded case circuit-breakers Catalog | SACE Tmax XT IEC TECHNICAL CHARACTERISTICS Low voltage molded case circuit-breakers
Declaration of Conformity - CE
EC Declaration of Conformity Tmax XT1
Instructions and Manuals
Installation instructions XT1
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
Feature → Business Impact → Application: Four-pole XT1 molded case design provides robust protection across three-phase systems with a current rating of 100 A, supporting 690 V AC and 500 V DC operating voltages. This enables compact motor control centers and distribution panels to handle demanding loads with reliable trip performance, reducing unplanned downtime and extending equipment life. Features such as front-terminal copper cable connections simplify installation and future upgrades, shortening commissioning time and improving field service efficiency. With 8000 cycles electrical durability and 25000 cycles mechanical durability, maintenance intervals can be extended and total cost of ownership lowered in high-cycle environments such as conveyors and machine centers. The device’s power loss of 7.0 W per pole improves energy efficiency and thermal performance in crowded panel racks. Compatibility with the SACE Tmax XT ecosystem ensures consistent protection coordination and easier retrofits for legacy installations. RoHS and REACH declarations, along with CE conformity and GB/T 14028.2 compliance, mitigate regulatory risk and accelerate procurement cycles. The release options TMD/TM support quick response to short-circuit events, while the 8 kV impulse withstand voltage (Uimp) and 25 kA Ics/Icu ratings provide strong fault current resilience in modern industrial networks. Designed for front-entry connections, it reduces wiring complexity and enables faster fault isolation, supporting safer and more maintainable electrical infrastructures.
Get a Quick Quote for a ABB 2TFH100029R1001
Chat with us on WhatsApp - fast responses guaranteed
Need to speak with someone? We'll call you back within 2 hours during business hours
Interested in ABB 2TFH100029R1001?
Enquire Now
FAQs
Ensure compatible front-entry copper cable Terminals are used, tighten to manufacturer torque, and mount in a standard 4-pole MCCB slot. Verify rated voltage and current match your panel requirements (690 V AC, 100 A). Use proper labeling and ensure coordination with upstream protection devices for correct tripping levels. The XT1 sub-type supports rapid installation with ABB protection coordination for downstream devices.
Rated current is 100 A, rated operational voltage 690 V AC / 500 V DC, rated insulation voltage 800 V, Uimp 8 kV, and Ics/Icu up to 25 kA depending on voltage. It has AC/DC current type, 4P configuration, and a short-circuit performance level of B. Power loss is 7.0 W per pole, supporting efficient panel operation.
Yes. The device lists AC/DC current type, enabling use in mixed electrical environments typical of manufacturing plants and machine controls, while maintaining IEC60947-2 compliance and safe operation under commonly used industrial voltages.
It carries CE conformity with DoC, and meets IEC60947-2 and GB/T 14028.2 standards. RoHS Information and REACH Declaration are provided, along with CMRT for conflict minerals reporting and WEEE categorization for proper disposal.
Long mechanical durability (25,000 cycles) and electrical durability (8,000 cycles) reduce spare-part needs and maintenance frequency. Front-terminal installation speeds commissioning, while RoHS/REACH compliance streamlines regulatory processes, contributing to lower total cost of ownership in high-cycle, demanding environments.