ABB 2TFH100031R1001 MCCB - IEC60947-2 / 8 kV Uimp

Part Number: 2TFH100031R1001
Manufacturer
ABB
Part number
2TFH100031R1001

Quick Summary

Moulded Case Circuit Breaker protects industrial automation panels from overcurrent, ensuring safe, continuous operation. Engineers often wrestle with nuisance tripping, inconsistent trip curves, and regulatory risk when aging equipment pushes reliability beyond limits. This ABB Tmax XT family device delivers CE conformity, RoHS compliance, and CMRT reporting, under IEC60947-2 standards for modern panel installations. With a 160 A rating, 4P configuration, high breaking capacity, and front-ext Extended terminals, it provides robust protection while simplifying wiring and maintenance. The combination of compact footprint and low power loss per pole supports energy efficiency targets and reduces cooling needs in compact plants.

Product Information

Extended Description

2TFH100031R1001 ABB: XT1B160 TMD160/1600 FEF 4P N =100%
Environmental Product Declaration - EPD
NoDecNee
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
Environmental Information
Breakers - Packaging disposal information
Customs Tariff Number
85362000
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Version
F
Current Type
AC/DC
Electrical Durability
8000 cycle | 120 cycles per hour
Mechanical Durability
25000 cycle | 240 cycles per hour
Number of Poles
4P
Power Loss
at Rated Operating Conditions per Pole 15 W
Rated Current (In)
160 A
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
800 V
Rated Operational Voltage
690 V AC | 500 V DC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 25 kA | (230 V AC) 25 kA | (240 V AC) 25 kA | (380 V AC) 18 kA | (415 V AC) 18 kA | (440 V AC) 11.5 kA | (500 V AC) 8 kA | (525 V AC) 6 kA | (690 V AC) 3 kA | (250 V DC) 2 Poles in Series 18 kA | (500 V DC) 3 Poles in Series 18 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 25 kA | (230 V AC) 25 kA | (240 V AC) 25 kA | (380 V AC) 18 kA | (415 V AC) 18 kA | (440 V AC) 15 kA | (500 V AC) 8 kA | (525 V AC) 6 kA | (690 V AC) 3 kA | (250 V DC) 2 Poles in Series 18 kA | (500 V DC) 3 Poles in Series 18 kA
Rated Uninterrupted Current (Iu)
160 A
Release
TMD
Release Type
TM
Short-Circuit Performance Level
B
Standards
IEC60947-2 | GB/T 14028.2
Sub-type
XT1
Terminal Connection Type
Front Extended
Data Sheet, Technical Information
SACE Tmax XT IEC Low voltage molded case circuit-breakers Catalog | SACE Tmax XT IEC TECHNICAL CHARACTERISTICS Low voltage molded case circuit-breakers
Declaration of Conformity - CE
EC Declaration of Conformity Tmax XT1
Instructions and Manuals
Installation instructions XT1
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
Feature: 4P MCCB with 160 A rated current delivers reliable distribution protection and legal compliance for panel boards. Business Impact: Minimizes downtime from faults and aligns with standard industrial practices for machine safety. Application: Use in switchgear assemblies and control panels in manufacturing lines. Feature: 690 VAC / 500 V DC rated operational voltage with 800 V rated insulation voltage provides flexible coexistence with mixed energy systems. Business Impact: Enables safe operation across AC/DC networks without swapping devices. Application: Electrical rooms and automation cabinets handling mixed-voltage drives. Feature: Short-circuit performance up to 25 kA Ics/Icu across multiple voltage ranges ensures safe interruption under fault conditions. Business Impact: Reduces fault cascade risk, protecting motors and drives while meeting OEM commissioning requirements. Application: High-energy motor feeders and processing lines. Feature: 8 kV impulse withstand (Uimp) and RoHS/CE compliance offer robust surge protection and regulatory peace of mind. Business Impact: Supports reliability in harsh industrial environments and simplifies regulatory audits. Application: Data centers, packaging lines, and process automation. Feature: Release TM/TMD with front extended terminals facilitates precise, simple tripping and easier wiring during installation. Business Impact: Lowers commissioning time and improves serviceability. Application: New builds and retrofits in compact plant spaces. Feature: 8000 electrical cycles and 25000 mechanical cycles indicate durable lifecycle performance with predictable maintenance. Business Impact: Lower maintenance costs and longer service intervals. Application: Continuous production facilities and critical process lines. Feature: Power loss of 15 W per pole reduces heat and cooling load. Business Impact: Improves energy efficiency and enables denser panel layouts. Application: High-density switchboards and modular plant architectures.

Get a Quick Quote for a ABB 2TFH100031R1001

Chat with us on WhatsApp - fast responses guaranteed

Need to speak with someone? We'll call you back within 2 hours during business hours

Interested in ABB 2TFH100031R1001? Enquire Now

FAQs

Yes. This 4P molded case circuit breaker uses Front Extended terminals, simplifying wiring in tight panel spaces and enabling straightforward replacement in existing ABB Tmax XT installations without major cabinet alterations.
It features a rated current of 160 A, rated insulation voltage of 800 V, and rated operational voltage of 690 VAC / 500 V DC. It provides up to 25 kA short-circuit-breaking capacity (Ics/Icu) at common voltages, ensuring safe interruption under fault conditions.
Yes. With AC/DC current capability and an 800 V insulation rating, the device supports mixed networks commonly found in modern factories, conveyors, and automation panels, reducing the need for multiple components.
The device adheres to IEC60947-2, with a CE Declaration of Conformity, RoHS compliance, and CMRT reporting. It also aligns with GB/T 14028.2 for related markets, aiding regulatory compliance and procurement traceability.
Durability specs show 8000 electrical cycles and 25000 mechanical cycles, along with a 15 W per-pole power loss. Together, these reduce maintenance frequency, improve reliability, and support lower total cost of ownership in continuous manufacturing environments.