ABB 2TFH100032R1001 Moulded Case Circuit Breaker - IEC 60947-2

Part Number: 2TFH100032R1001
Manufacturer
ABB
Part number
2TFH100032R1001

Quick Summary

ABB 2TFH100032R1001 is a four-pole Moulded Case Circuit Breaker designed to protect low-voltage distribution panels in industrial environments. This device helps engineers avoid unexpected outages by delivering reliable overcurrent protection with predictable tripping. The product carries IEC 60947-2 conformity along with RoHS and REACH declarations, and CE compatibility, supporting clean regulatory reporting. Its compact 4P footprint, front-terminal copper connections, and 125 A rating align with modern panel design, delivering ease of installation, reduced labor costs, and improved lifecycle reliability for drives, motors, and power distribution projects.

Product Information

Extended Description

2TFH100032R1001 ABB: XT1B160 TMD125/1250 FFC 4P N=100%
Environmental Product Declaration - EPD
NoDecNee
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
Environmental Information
Breakers - Packaging disposal information
Customs Tariff Number
85362000
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Version
F
Current Type
AC/DC
Electrical Durability
8000 cycle | 120 cycles per hour
Mechanical Durability
25000 cycle | 240 cycles per hour
Number of Poles
4P
Power Loss
at Rated Operating Conditions per Pole 10.7 W
Rated Current (In)
125 A
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
800 V
Rated Operational Voltage
690 V AC | 500 V DC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 25 kA | (230 V AC) 25 kA | (240 V AC) 25 kA | (380 V AC) 18 kA | (415 V AC) 18 kA | (440 V AC) 11.5 kA | (500 V AC) 8 kA | (525 V AC) 6 kA | (690 V AC) 3 kA | (250 V DC) 2 Poles in Series 18 kA | (500 V DC) 3 Poles in Series 18 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 25 kA | (230 V AC) 25 kA | (240 V AC) 25 kA | (380 V AC) 18 kA | (415 V AC) 18 kA | (440 V AC) 15 kA | (500 V AC) 8 kA | (525 V AC) 6 kA | (690 V AC) 3 kA | (250 V DC) 2 Poles in Series 18 kA | (500 V DC) 3 Poles in Series 18 kA
Rated Uninterrupted Current (Iu)
160 A
Release
TMD
Release Type
TM
Short-Circuit Performance Level
B
Standards
IEC60947-2 | GB/T 14028.2
Sub-type
XT1
Terminal Connection Type
Front for Copper Cables
Data Sheet, Technical Information
SACE Tmax XT IEC Low voltage molded case circuit-breakers Catalog | SACE Tmax XT IEC TECHNICAL CHARACTERISTICS Low voltage molded case circuit-breakers
Declaration of Conformity - CE
EC Declaration of Conformity Tmax XT1
Instructions and Manuals
Installation instructions XT1
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
ABB 2TFH100032R1001 delivers measurable value across protection, installation, and compliance. Feature: 125 A rated current with 690 V AC / 500 V DC operating voltage; Business impact: supports safe, scalable protection for large motor loads and mixed-voltage panels, reducing downtime and replacement costs; Application: motor control centers and plant switchgear. Feature: 4P construction with front for copper cables; Business impact: simplifies wiring, speeds up panel assembly, and minimizes tunneling inside enclosures; Application: compact industrial control panels. Feature: Short-circuit capability up to 25 kA (Ics) and 25 kA (Icu) across voltages; Business impact: robust protection against devastating faults, improving equipment longevity; Application: critical power distribution and drives. Feature: 800 V rated insulation and 8 kV impulse withstand; Business impact: higher electrical durability in harsh environments, lowering maintenance intervals; Application: harsh industrial environments and high-energy systems. Feature: TM release with TMD specifications and RoHS/REACH/CMRT certifications; Business impact: regulatory compliance, safer procurement, and easier supplier audits; Application: global sourcing for complex infrastructure projects. Feature: RoHS/REACH declarations and WEEE compliance; Business impact: supports sustainable procurement and regulatory compliance in multiple regions; Application: international manufacturing and export. Feature: 85362000 tariff classification and SACE Tmax XT main type; Business impact: streamlines customs clearance and product lifecycle planning; Application: global supply chains and compliance reporting.

Get a Quick Quote for a ABB 2TFH100032R1001

Chat with us on WhatsApp - fast responses guaranteed

Need to speak with someone? We'll call you back within 2 hours during business hours

Interested in ABB 2TFH100032R1001? Enquire Now

FAQs

This four-pole MCCB uses front for copper cable terminals and conforms to IEC 60947-2, making it compatible with most standard LV panels and switchgear. Its compact 4P footprint simplifies retrofits, and the front-terminal design reduces wiring complexity during installation, shortening commissioning time.
Key specs include 125 A rated current, 690 V AC / 500 V DC rated voltage, Icu and Ics of 25 kA, 800 V insulation voltage, and 8 kV impulse withstand voltage. It also offers 4P protection, 10.7 W per pole power loss, and a rated service short-circuit capacity across multiple voltages, ensuring robust protection.
Yes. The 2TFH100032R1001 is designed for motor control environments, offering fast, predictable tripping with TM/TMD release characteristics and high short-circuit breaking capacity suitable for drive applications, reducing motor damage and unplanned downtime.
The device conforms to IEC 60947-2 and GB/T 14028.2, with CE declarations, RoHS and REACH compliance, CMRT reporting, and WEEE categorization. These certifications support regulatory reporting, environmental responsibility, and global procurement requirements.
The 2TFH100032R1001 offers robust electrical and mechanical durability (up to 8,000 electrical and 25,000 mechanical cycles) which reduces maintenance intervals and replacement costs. Its reliability, easy installation, and regulatory compliance contribute to lower total cost of ownership in industrial power systems.