ABB 2TFH100048R1001 Moulded Case Circuit Breaker-IEC60947-2

Part Number: 2TFH100048R1001
Manufacturer
ABB
Part number
2TFH100048R1001

Quick Summary

ABB 2TFH100048R1001 Moulded Case Circuit Breaker is a high-performance protective device for industrial electrical panels. This unit helps prevent costly downtime by delivering accurate overcurrent protection and fast fault isolation in complex automation environments. It is certified to IEC60947-2 and CE, with RoHS and REACH declarations supporting safe, compliant operation. For OEMs and panel builders, reliable protection reduces downstream outages and simplifies commissioning. The solution integrates with SACE Tmax XT line expectations, offering compatible mounting, wiring, and sequence control to optimize installation efficiency. By combining robust durability with clear documentation, it supports maintenance planning, spare-part planning, and overall lifecycle cost reduction.

Product Information

Extended Description

2TFH100048R1001 ABB: XT1C160 TMD125/1250 FEF 3P
Environmental Product Declaration - EPD
NoDecNee
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
Environmental Information
Breakers - Packaging disposal information
Customs Tariff Number
85362000
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Version
F
Current Type
AC/DC
Electrical Durability
8000 cycle | 120 cycles per hour
Mechanical Durability
25000 cycle | 240 cycles per hour
Number of Poles
3P
Power Loss
at Rated Operating Conditions per Pole 10.7 W
Rated Current (In)
125 A
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
800 V
Rated Operational Voltage
690 V AC | 500 V DC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 40 kA | (230 V AC) 40 kA | (240 V AC) 40 kA | (380 V AC) 25 kA | (415 V AC) 25 kA | (440 V AC) 12.5 kA | (500 V AC) 9 kA | (525 V AC) 8 kA | (690 V AC) 4 kA | (250 V DC) 2 Poles in Series 25 kA | (500 V DC) 3 Poles in Series 25 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 40 kA | (230 V AC) 40 kA | (240 V AC) 40 kA | (380 V AC) 25 kA | (415 V AC) 25 kA | (440 V AC) 25 kA | (500 V AC) 18 kA | (525 V AC) 8 kA | (690 V AC) 4 kA | (250 V DC) 2 Poles in Series 25 kA | (500 V DC) 3 Poles in Series 25 kA
Rated Uninterrupted Current (Iu)
160 A
Release
TMD
Release Type
TM
Remarks
ATLAS
Short-Circuit Performance Level
C
Standards
IEC60947-2 | GB/T 14028.2
Sub-type
XT1
Terminal Connection Type
Front Extended
Data Sheet, Technical Information
SACE Tmax XT IEC Low voltage molded case circuit-breakers Catalog | SACE Tmax XT IEC TECHNICAL CHARACTERISTICS Low voltage molded case circuit-breakers
Declaration of Conformity - CE
EC Declaration of Conformity Tmax XT1
Instructions and Manuals
Installation instructions XT1
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
Feature: 125 A rated current with 40 kA short-circuit capacity → Business Impact: Enables safe interruption of faults in distribution panels, reducing equipment damage and downtime → Application: Ideal for three-phase MCCB protection in 690 VAC industrial feeders and automation panels. Feature: Wide voltage range with 690 VAC / 500 V DC and 800 V insulation → Business Impact: Supports mixed-control architectures and reliable protection across AC and DC domains → Application: Suitable for motor drives, conveyors, and control panels within manufacturing lines. Feature: Front Extended terminal connections and 3P design → Business Impact: Simplifies wiring, improves connection reliability, and speeds panel assembly → Application: Panel builders and retrofit projects in new or existing installations. Feature: IEC60947-2, CE, RoHS and REACH compliance → Business Impact: Reduces regulatory risk and accelerates procurement across regions → Application: Global manufacturing sites requiring certified electrical protection. Feature: Long life cycles with 8000 electrical and 25000 mechanical cycles → Business Impact: Lowers maintenance costs and extends service intervals → Application: High-use feeders and machine protection roles in continuous operation environments.

Get a Quick Quote for a ABB 2TFH100048R1001

Chat with us on WhatsApp - fast responses guaranteed

Need to speak with someone? We'll call you back within 2 hours during business hours

Interested in ABB 2TFH100048R1001? Enquire Now

FAQs

Use the Front Extended 3P terminals for secure wiring and mounting in a standard low-voltage MCCB cabinet. Follow the installation guidance from the XT1 manuals, ensure correct phase sequence, and torque each terminal to the specified value. The unit is designed to integrate smoothly with SACE Tmax XT assemblies for straightforward retrofit or new installations.
Verify rated current of 125 A, Ics/Icu of 40 kA, rated voltage of 690 VAC / 500 V DC, and rated insulation voltage of 800 V. The device is a 3P moulded case circuit breaker with a release set to TMD/TM, suitable for high-efficiency interruption across varied industrial loads and networks.
Yes. The 3P XT1 device provides robust short-circuit interruption (40 kA) and compatible voltage ratings, making it well-suited for motor feeders and protection in 690 V systems. Its selective tripping and durable design help prevent motor damage during faults while maintaining process continuity.
The breaker complies with IEC 60947-2 and GB/T 14028.2, and carries CE conformity, RoHS, and REACH declarations. A WEEE category designation (5. Small Equipment) is listed for disposal guidelines, supporting global compliance and responsible sourcing.
With electrical durability rated at 8000 cycles and mechanical durability at 25000 cycles, the device reduces replacement frequency and maintenance costs. Long service life, combined with clear labeling and documentation, improves uptime, reduces spare-part requirements, and lowers total cost of ownership in high-use industrial environments.