ABB 2TFH100051R1001 Moulded Case Circuit Breaker - IEC60947-2

Part Number: 2TFH100051R1001
Manufacturer
ABB
Part number
2TFH100051R1001

Quick Summary

ABB 2TFH100051R1001 is a moulded case circuit breaker providing reliable overcurrent protection in LV distribution panels. Where space is tight and maintenance must be predictable, engineers need compact, easy-to-install protection with clear specs and dependable performance. It meets IEC60947-2 safety standards, carries CE conformity, and complies with RoHS and CMRT reporting, ensuring regulatory alignment across global plants. Built for the SACE Tmax XT family, the unit supports straightforward installation, predictable lifecycle costs, and compatibility with front-terminal copper cables, delivering value for panel builders and OEMs.

Product Information

Extended Description

2TFH100051R1001 ABB: XT1C160 TMD160/1600 FFC 3P
Environmental Product Declaration - EPD
NoDecNee
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
Environmental Information
Breakers - Packaging disposal information
Customs Tariff Number
85362000
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Version
F
Current Type
AC/DC
Electrical Durability
8000 cycle | 120 cycles per hour
Mechanical Durability
25000 cycle | 240 cycles per hour
Number of Poles
3P
Power Loss
at Rated Operating Conditions per Pole 15 W
Rated Current (In)
160 A
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
800 V
Rated Operational Voltage
690 V AC | 500 V DC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 40 kA | (230 V AC) 40 kA | (240 V AC) 40 kA | (380 V AC) 25 kA | (415 V AC) 25 kA | (440 V AC) 12.5 kA | (500 V AC) 9 kA | (525 V AC) 8 kA | (690 V AC) 4 kA | (250 V DC) 2 Poles in Series 25 kA | (500 V DC) 3 Poles in Series 25 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 40 kA | (230 V AC) 40 kA | (240 V AC) 40 kA | (380 V AC) 25 kA | (415 V AC) 25 kA | (440 V AC) 25 kA | (500 V AC) 18 kA | (525 V AC) 8 kA | (690 V AC) 4 kA | (250 V DC) 2 Poles in Series 25 kA | (500 V DC) 3 Poles in Series 25 kA
Rated Uninterrupted Current (Iu)
160 A
Release
TMD
Release Type
TM
Short-Circuit Performance Level
C
Standards
IEC60947-2 | GB/T 14028.2
Sub-type
XT1
Terminal Connection Type
Front for Copper Cables
Data Sheet, Technical Information
SACE Tmax XT IEC Low voltage molded case circuit-breakers Catalog | SACE Tmax XT IEC TECHNICAL CHARACTERISTICS Low voltage molded case circuit-breakers
Declaration of Conformity - CE
EC Declaration of Conformity Tmax XT1
Instructions and Manuals
Installation instructions XT1
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
Feature 1: 3P 160 A protection with 690 V AC / 500 V DC operation → Business impact: robust protection for main feeders reduces nuisance trips and unplanned downtime in LV switchgear; Application: industrial automation panels and machine-building electrical distributions. Feature 2: Front for Copper Cables terminal connection → Business impact: faster wiring, reduced assembly time, and cleaner panel layouts; Application: OEM panel builds and retrofit projects. Feature 3: High fault current capability, Ics up to 40 kA and Icu up to 40 kA → Business impact: enhanced safety margins for high-short-circuit environments; Application: drives, motors, and process lines in heavy industry. Feature 4: Uimp 8 kV withstand and Ui 800 V insulation → Business impact: improved electrical resilience and long-term reliability in varying installation conditions; Application: industrial power distribution near electrical noise and transients. Feature 5: Compliance and documentation (IEC60947-2, CE, RoHS, CMRT) → Business impact: simplified regulatory approval and supply-chain responsibility; Application: global manufacturing sites with strict compliance requirements. Feature 6: Mechanical and electrical durability (8000 electrical cycles, 25000 mechanical cycles) → Business impact: extended service life and lower maintenance costs; Application: frequent switching applications in automation lines. Feature 7: Power loss of 15 W per pole → Business impact: energy-conscious protection reducing running costs; Application: energy-efficient LV switchboards and critical panels.

Get a Quick Quote for a ABB 2TFH100051R1001

Chat with us on WhatsApp - fast responses guaranteed

Need to speak with someone? We'll call you back within 2 hours during business hours

Interested in ABB 2TFH100051R1001? Enquire Now

FAQs

Yes. The device uses a front-terminal connection designed for copper cables, simplifying wiring and enabling faster assembly in control panels and switchgear. This configuration minimizes wiring errors and improves overall panel aesthetics, helping installers meet tight project timelines without sacrificing reliability.
The MCCB is rated at 160 A (I_n) with rated insulation voltage U_i of 800 V, rated impulse withstand voltage U_imp of 8 kV, and a rated short-circuit breaking capacity I_cs up to 40 kA. The rated ultimate short-circuit capacity I_cu is also up to 40 kA for applicable voltage configurations, making it suitable for demanding LV applications.
Yes. It supports rated operational voltage up to 690 V AC (and 500 V DC), aligns with IEC60947-2, and is designed for LV switchgear and machine-building environments. Its 3P configuration and high fault-current ratings provide robust protection in industrial drives, motors, and automation panels.
This MCCB carries CE conformity and IEC60947-2 safety standard alignment, with RoHS and CMRT documentation. These certifications support regulatory compliance across regions, facilitate customer audits, and help streamline procurement for multinational manufacturing sites seeking traceable material and environmental responsibility.
The unit delivers 8000 electrical cycles and 25000 mechanical cycles, indicating long-term switching reliability. With a modest 15 W power loss per pole, energy efficiency improves operating costs. Together, these factors reduce downtime, extend service life, and lower maintenance expenses for high-usage automation lines.