ABB 2TFH100497R1001 Moulded Case Circuit Breaker - IEC60947-2
Part Number: 2TFH100497R1001
Quick Summary
ABB 2TFH100497R1001 Moulded Case Circuit Breaker protects low-voltage systems in industrial panels. Engineers often struggle with nuisance trips and limited replacement options when selecting MCCBs for XT1 environments. This device meets IEC60947-2 and GB/T 14028.2 standards, and carries CE declarations, reinforcing global compliance for multinational facilities. With RoHS and REACH declarations, compact footprint, and a 125 A rating at 690 VAC (and 500 V DC), it supports safer, cost-effective panel design and easier lifecycle management. Its front terminal connection for copper cables simplifies installation in tight switchgear enclosures, helping reduce commissioning time and service interventions.
Product Information
Extended Description
2TFH100497R1001 ABB: XT1N160 TMD125/1250 FFC 4P+RC Inst
Environmental Product Declaration - EPD
NoDecNee
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
Environmental Information
Breakers - Packaging disposal information
Customs Tariff Number
85362000
Product Net Width
101.6 mm
Product Net Height
130 mm
Product Net Depth / Length
70 mm
Product Net Weight
2.7 kg
Package Level 1 Width
242 mm
Package Level 1 Height
165 mm
Package Level 1 Depth / Length
20.5 mm
Package Level 1 Gross Weight
2.8 kg
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Version
F
Current Type
AC
Electrical Durability
8000 cycle | 120 cycles per hour
Mechanical Durability
25000 cycle | 240 cycles per hour
Number of Poles
4P
Power Loss
at Rated Operating Conditions per Pole 10.7 W
Rated Current (In)
125 A
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
800 V
Rated Operational Voltage
690 V AC | 500 V DC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 50 kA | (230 V AC) 50 kA | (240 V AC) 50 kA | (380 V AC) 36 kA | (415 V AC) 36 kA | (440 V AC) 18 kA | (500 V AC) 15 kA | (525 V AC) 11 kA | (690 V AC) 5 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 65 kA | (230 V AC) 65 kA | (240 V AC) 65 kA | (380 V AC) 36 kA | (415 V AC) 36 kA | (440 V AC) 36 kA | (500 V AC) 30 kA | (525 V AC) 22 kA | (690 V AC) 6 kA
Rated Uninterrupted Current (Iu)
160 A
Release
TMD
Release Type
TM
Remarks
ATLAS
Short-Circuit Performance Level
N
Standards
IEC60947-2 | GB/T 14028.2
Sub-type
XT1
Terminal Connection Type
Front for Copper Cables
Data Sheet, Technical Information
SACE Tmax XT IEC Low voltage molded case circuit-breakers Catalog | SACE Tmax XT IEC TECHNICAL CHARACTERISTICS Low voltage molded case circuit-breakers
Declaration of Conformity - CE
EC Declaration of Conformity Tmax XT1
Instructions and Manuals
Installation instructions XT1
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
Feature: Four-pole XT1 configuration with a 125 A rated current and dual voltage capability (690 VAC / 500 V DC) enables protection across AC and DC feeders in mixed installations, reducing component count and space requirements. Business Impact: Streamlined panel design and lower total cost of ownership through unified protection for diverse loads. Application: Suitable for distribution boards and motor control centers in industrial facilities. Feature: High short-circuit ratings with 8 kV rated impulse withstand voltage and up to 65 kA ultimate breaking capacity at relevant voltages improve fault withstand and selective tripping. Business Impact: Enhanced safety margins and reduced collateral damage during faults, improving uptime in critical lines. Application: Environments with heavy motor loads and demanding startup surges. Feature: Robust durability specs—electrical durability up to 8000 cycles and mechanical durability up to 25000 cycles—support long service life in high-use installations. Business Impact: Lower maintenance costs and fewer replacements in busy switchgear, boosting asset reliability. Application: Frequent switching applications in manufacturing lines. Feature: Front-terminal connection for copper cables simplifies installation, spares space, and speeds replacement or retrofits. Business Impact: Faster commissioning, safer terminations, and easier field servicing. Application: Retrofit projects and panel upgrades in constrained enclosures. Feature: Compliance and lifecycle declarations—RoHS, REACH, CMRT; CE declaration; standard references IEC60947-2 and GB/T 14028.2—ensure regulatory alignment and traceability. Business Impact: Faster audits, lower risk of noncompliance penalties, and better supplier collaboration. Application: Global deployments in regulated markets with strict environmental requirements.
Get a Quick Quote for a ABB 2TFH100497R1001
Chat with us on WhatsApp - fast responses guaranteed
Need to speak with someone? We'll call you back within 2 hours during business hours
Interested in ABB 2TFH100497R1001?
Enquire Now
FAQs
The ABB 2TFH100497R1001 uses front-terminal connections designed for copper conductors. Begin by ensuring the panel is de-energized, select appropriate conductor cross-section per rating, strip insulation per terminal specification, and insert into the front terminals. Tighten to manufacturer torque, verify clearances, and perform insulation testing. This approach simplifies retrofits and reduces commissioning time in confined switchgear spaces.
Key specs include rated current I n of 125 A, rated operational voltage Uo of 690 VAC / 500 V DC, rated impulse withstand voltage Uimp of 8 kV, insulation voltage Ui of 800 V, and short-circuit ratings with Ics up to 50 kA (at lower voltages) and Icu up to 65 kA (for selected voltages). It is a 4P XT1 device with front copper terminals.
Yes. The device is a 4P XT1 Moulded Case Circuit Breaker rated for 690 VAC operation, with high short-circuit breaking capacity, dependable durability, and front-terminal wiring ideal for MCC applications. Its compact footprint and RoHS/REACH compliance support safe, reliable integration into motor control centers and panel boards.
It complies with IEC60947-2 and GB/T 14028.2 standards, carries CE declarations, and provides RoHS and REACH declarations. CMRT is available for conflict minerals reporting. These certifications aid regulatory compliance, supplier due diligence, and responsible sourcing in global deployments.
With electrical durability rated at 8000 cycles and mechanical durability at 25000 cycles, the device supports longer service life and fewer replacements. Coupled with 125 A rating and high Ics/Icu ratings, this can reduce downtime and maintenance costs, delivering a favorable total cost of ownership in busy production lines.