ABB 2TFH100524R1001 MCCB - IEC60947-2 690V AC/DC 25kA

Part Number: 2TFH100524R1001
Manufacturer
ABB
Part number
2TFH100524R1001

Quick Summary

ABB 2TFH100524R1001 MCCB provides reliable overcurrent protection for 690V distribution in industrial automation panels. In demanding environments, nuisance trips, complex wiring, and long commissioning times can stall critical projects. This device is compliant with IEC 60947-2 and CE conformity, RoHS and CMRT declarations, delivering regulatory certainty across multi-region installations. Designed for plug-in installation in 4-pole Tmax XT configurations, it delivers consistent protection with low power loss (2.0 W per pole), robust short-circuit ratings, and easy replacement in legacy ABB Control gear. By combining clear documentation, RoHS/REACH compliance, and straightforward maintenance, the MCCB helps machine builders and panel builders reduce downtime and total cost of ownership while supporting scalable automation strategies.

Product Information

Extended Description

2TFH100524R1001 ABB: XT1B160 TMD20/450 PMP 4P
Environmental Product Declaration - EPD
NoDecNee
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
Environmental Information
Breakers - Packaging disposal information
Customs Tariff Number
85362000
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Version
P
Current Type
AC/DC
Electrical Durability
8000 cycle | 120 cycles per hour
Mechanical Durability
25000 cycle | 240 cycles per hour
Number of Poles
4P
Power Loss
at Rated Operating Conditions per Pole 2.0 W
Rated Current (In)
20 A
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
800 V
Rated Operational Voltage
690 V AC | 500 V DC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 25 kA | (230 V AC) 25 kA | (240 V AC) 25 kA | (380 V AC) 18 kA | (415 V AC) 18 kA | (440 V AC) 11.5 kA | (500 V AC) 8 kA | (525 V AC) 6 kA | (690 V AC) 3 kA | (250 V DC) 2 Poles in Series 18 kA | (500 V DC) 3 Poles in Series 18 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 25 kA | (230 V AC) 25 kA | (240 V AC) 25 kA | (380 V AC) 18 kA | (415 V AC) 18 kA | (440 V AC) 15 kA | (500 V AC) 8 kA | (525 V AC) 6 kA | (690 V AC) 3 kA | (250 V DC) 2 Poles in Series 18 kA | (500 V DC) 3 Poles in Series 18 kA
Rated Uninterrupted Current (Iu)
160 A
Release
TMD
Release Type
TM
Short-Circuit Performance Level
B
Standards
IEC60947-2 | GB/T 14028.2
Sub-type
XT1
Terminal Connection Type
Plug-In Circuit-Breakers
Data Sheet, Technical Information
SACE Tmax XT IEC Low voltage molded case circuit-breakers Catalog | SACE Tmax XT IEC TECHNICAL CHARACTERISTICS Low voltage molded case circuit-breakers
Declaration of Conformity - CE
EC Declaration of Conformity Tmax XT1
Instructions and Manuals
Installation instructions XT1
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
Feature → Business Impact → Application: 4P plug-in design enables fast installation and compact panel layouts, reducing wiring errors, commissioning time, and install risk in main distribution blocks. Feature → Business Impact → Application: High fault tolerance with Icu 25 kA and In 20 A at up to 690 V AC / 500 V DC provides superior protection for motors, drives, and transformers, lowering unplanned downtime in automated lines. Feature → Business Impact → Application: Low power loss of 2.0 W per pole reduces heat, cooling load, and energy costs in large switchgear and control panels. Feature → Business Impact → Application: Comprehensive RoHS, REACH, CMRT declarations simplify regulatory approvals and supply-chain management for global deployments. Feature → Business Impact → Application: SACE Tmax XT compatibility with plug-in connections and IEC 60947-2 standards streamlines procurement for OEMs and accelerates upgrades in machine builders and panel integrators.

Get a Quick Quote for a ABB 2TFH100524R1001

Chat with us on WhatsApp - fast responses guaranteed

Need to speak with someone? We'll call you back within 2 hours during business hours

Interested in ABB 2TFH100524R1001? Enquire Now

FAQs

This MCCB belongs to the SACE Tmax XT family and is designed for 4P plug-in installation in distribution panels that support IEC 60947-2. It fits ABB and compatible switchboards that accept plug-in MCCBs and 690 V class systems. Check the XT installation guidelines for correct mounting and clearance.
Use the 4P plug-in connection described in Installation XT1 instructions. Ensure proper alignment with busbars, secure terminal connections to the rated torque, and verify insulation and clearance. The XT1 installation guide provides step-by-step guidance and safety precautions to minimize commissioning time.
Rated current is 20 A with a rated operational voltage of 690 V AC / 500 V DC and rated insulation voltage of 800 V. It supports Ics and Icu up to 25 kA, Uimp 8 kV, and power loss of 2.0 W per pole. These ratings suit critical load protection in automation panels.
Yes. The product carries RoHS and REACH declarations for ABB Sace circuit breakers and includes CMRT reporting. It complies with EU directives (RoHS 2011/65/EU and amendment 2015/863) and provides documentation to support multi-region compliance.
The device offers low heat generation (2.0 W per pole) and high durability (electrical 8000 cycles, mechanical 25000 cycles), reducing cooling needs and downtime. The RoHS/CMRT documentation simplifies logistics, while its 25 kA breaking capacity protects critical loads, contributing to lower total cost of ownership over panel lifetimes.