ABB 2TFH100547R1001 Moulded Case Breaker - IEC60947-2
Part Number: 2TFH100547R1001
Quick Summary
ABB Tmax XT molded case breaker provides reliable overcurrent protection for low‑voltage switchgear applications. Engineers often struggle with protection setting coordination and long lead times for spare parts, delaying critical projects. This device is IEC60947-2 compliant, CE declared, and RoHS/REACH certified, supporting global regulatory alignment and sustainable procurement. As a SACE Tmax XT 4P automatic circuit breaker, it reduces downtime and maintenance costs while delivering dependable protection for 690 V AC and 500 V DC systems. It is well suited for modernization projects, campus automation, and critical process lines in manufacturing, water treatment, and data center infrastructure. This combination of performance and regulatory compliance helps procurement teams simplify sourcing and shorten project timelines.
Product Information
Extended Description
2TFH100547R1001 ABB: XT1C160 TMD40/450 PMP 4P
Environmental Product Declaration - EPD
NoDecNee
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
Environmental Information
Breakers - Packaging disposal information
Customs Tariff Number
85362000
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Version
P
Current Type
AC/DC
Electrical Durability
8000 cycle | 120 cycles per hour
Mechanical Durability
25000 cycle | 240 cycles per hour
Number of Poles
4P
Power Loss
at Rated Operating Conditions per Pole 4.6 W
Rated Current (In)
40 A
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
800 V
Rated Operational Voltage
690 V AC | 500 V DC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 40 kA | (230 V AC) 40 kA | (240 V AC) 40 kA | (380 V AC) 25 kA | (415 V AC) 25 kA | (440 V AC) 12.5 kA | (500 V AC) 9 kA | (525 V AC) 8 kA | (690 V AC) 4 kA | (250 V DC) 2 Poles in Series 25 kA | (500 V DC) 3 Poles in Series 25 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 40 kA | (230 V AC) 40 kA | (240 V AC) 40 kA | (380 V AC) 25 kA | (415 V AC) 25 kA | (440 V AC) 25 kA | (500 V AC) 18 kA | (525 V AC) 8 kA | (690 V AC) 4 kA | (250 V DC) 2 Poles in Series 25 kA | (500 V DC) 3 Poles in Series 25 kA
Rated Uninterrupted Current (Iu)
160 A
Release
TMD
Release Type
TM
Short-Circuit Performance Level
C
Standards
IEC60947-2 | GB/T 14028.2
Sub-type
XT1
Terminal Connection Type
Plug-In Circuit-Breakers
Data Sheet, Technical Information
SACE Tmax XT IEC Low voltage molded case circuit-breakers Catalog | SACE Tmax XT IEC TECHNICAL CHARACTERISTICS Low voltage molded case circuit-breakers
Declaration of Conformity - CE
EC Declaration of Conformity Tmax XT1
Instructions and Manuals
Installation instructions XT1
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
Feature: Four-pole XT1 design delivers 40 A rated current with plug-in connections for quick panel installation. Business impact: minimizes wiring complexity and commissioning time while ensuring reliable 4P protection across phases. Application: suitable for MCCs, distribution boards, and machine control panels in manufacturing automation where compact, modular protection is essential. Feature: High fault-current resilience with Ics and Icu up to 40 kA across common voltages, plus 690 V AC / 500 V DC operation and 800 V insulation. Business impact: enhances safety, reduces the risk of equipment damage during short circuits, and supports tighter protection coordination. Application: critical power feeders, data centers, and process lines requiring robust fault clearing. Feature: TM/TMD release with Short-Circuit Performance Level C complements selective tripping and fast response. Business impact: improves coordination and reduces unwanted outages while maintaining protective margins. Application: motor feeders and automated lines that demand precise trip curves and reliable performance under surge conditions. Feature: Long-life durability and efficiency with 8000 electrical cycles, 25000 mechanical cycles, and 4.6 W power loss per pole. Business impact: lowers maintenance costs, extends service life, and reduces heat generation in panels. Application: continuous operation in harsh industrial environments where uptime is critical. Feature: Regulatory and environmental data including RoHS/REACH declarations, CMRT, EPD NoDecNee, WEEE 5, and tariff code 85362000. Business impact: simplifies global sourcing and regulatory compliance across multinational sites.
Get a Quick Quote for a ABB 2TFH100547R1001
Chat with us on WhatsApp - fast responses guaranteed
Need to speak with someone? We'll call you back within 2 hours during business hours
Interested in ABB 2TFH100547R1001?
Enquire Now
FAQs
This 4P moulded case breaker is designed for plug-in SACE Tmax XT panels and is compatible with ABB Tmax XT assemblies. It installs quickly in standard 35 mm DIN rails with plug-in circuit-breaker terminals, reducing commissioning time. In retrofit scenarios, it supports rapid swap-outs without re-wiring, helping maintain production uptime and minimizing downtime during upgrades.
The breaker offers In of 40 A, rated operational voltage of 690 V AC / 500 V DC, Ui of 800 V, and Uimp of 8 kV. It provides Ics and Icu up to 40 kA across listed voltages, with a Short-Circuit Performance Level of C. These specs support strong fault protection and predictable trip behavior in demanding installations.
Yes. The 4P design, TM/TMD release, and 690 V/500 V ratings make it well-suited for motor feeders and machine control circuits within MCCs and automation panels. It supports selective coordination when used with other Tmax XT devices, helping prevent cascaded outages while protecting motors and drives.
The product adheres to IEC60947-2 with CE Declarations of Conformity, RoHS and REACH declarations, CMRT, and WEEE category 5. Additional information includes environmental packaging data and a comprehensive data sheet to facilitate regulatory reviews and cross-border sourcing for multinational projects.
With 8000 electrical cycles and 25000 mechanical cycles, plus 4.6 W per pole power loss, the Tmax XT 4P MCCB delivers long service life and energy efficiency. These durability metrics reduce maintenance interventions and spare-part needs, while the plug-in design minimizes replacement time during servicing, lowering overall downtime and operating costs.