ABB 2TFH100556R1001 MCB - Icu 100 kA, 690V/500V
Part Number: 2TFH100556R1001
Quick Summary
2TFH100556R1001 is a high‑reliability moulded case circuit breaker for industrial motor control and power distribution. Operators often face downtime and mis‑selection when protection devices don’t balance fast fault clearing with long‑term reliability. This model carries CE conformity with IEC 60947‑2, a DoC and RoHS/REACH compliance, aligning with global regulatory expectations. As part of ABB SACE Tmax XT, it fits compact spaces while delivering robust short‑circuit protection; ideal for OEMs and panel builders seeking fast, compliant installation.
Product Information
Extended Description
2TFH100556R1001 ABB: XT1H160 TMD63/630 PMP 3P
Environmental Product Declaration - EPD
NoDecNee
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
Environmental Information
Breakers - Packaging disposal information
Customs Tariff Number
85362000
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Version
P
Current Type
AC/DC
Electrical Durability
8000 cycle | 120 cycles per hour
Mechanical Durability
25000 cycle | 240 cycles per hour
Number of Poles
3P
Power Loss
at Rated Operating Conditions per Pole 6.0 W
Rated Current (In)
63 A
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
800 V
Rated Operational Voltage
690 V AC | 500 V DC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 75 kA | (230 V AC) 75 kA | (240 V AC) 75 kA | (380 V AC) 52.5 kA | (415 V AC) 37.5 kA | (440 V AC) 32.5 kA | (500 V AC) 25 kA | (525 V AC) 17.5 kA | (690 V AC) 5 kA | (250 V DC) 2 Poles in Series 52.5 kA | (500 V DC) 3 Poles in Series 52.5 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 100 kA | (230 V AC) 100 kA | (240 V AC) 100 kA | (380 V AC) 70 kA | (415 V AC) 70 kA | (440 V AC) 65 kA | (500 V AC) 50 kA | (525 V AC) 35 kA | (690 V AC) 10 kA | (250 V DC) 2 Poles in Series 70 kA | (500 V DC) 3 Poles in Series 70 kA
Rated Uninterrupted Current (Iu)
160 A
Release
TMD
Release Type
TM
Remarks
ATLAS
Short-Circuit Performance Level
H
Standards
IEC60947-2 | GB/T 14028.2
Sub-type
XT1
Terminal Connection Type
Plug-In Circuit-Breakers
Data Sheet, Technical Information
SACE Tmax XT IEC Low voltage molded case circuit-breakers Catalog | SACE Tmax XT IEC TECHNICAL CHARACTERISTICS Low voltage molded case circuit-breakers
Declaration of Conformity - CE
EC Declaration of Conformity Tmax XT1
Instructions and Manuals
Installation instructions XT1
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
Feature: 3P, 63 A rating and high Icu up to 100 kA. Business Impact: Enhanced protection with minimal downtime during fault events, improving line reliability and reducing rework. Application: Suitable for motor control circuits and low‑voltage distribution in conveyors and machinery. Feature: 690 V AC / 500 V DC operational range and 800 V insulation. Business Impact: Supports diverse power architectures, enabling safe retrofits and future expansions. Application: Office and manufacturing panels requiring versatile voltage compatibility. Feature: Plug‑In circuit‑breaker terminal connection. Business Impact: Faster installation and simpler maintenance swaps, lowering commissioning time. Application: Retrofit projects and modular panel builds with quick replacements. Feature: RoHS/REACH compliance and EPD alignment (NoDecNee) with CE DoC. Business Impact: Regulatory certainty and sustainable sourcing reduce compliance risk. Application: Global deployments with strict environmental and supplier requirements. Feature: SACE Tmax XT family alignment and 25,000 mechanical cycles durability. Business Impact: Long‑term reliability lowers maintenance costs and extends asset life. Application: Continuous operation environments with demanding duty cycles. Feature: Rated impulse withstand and short‑circuit performance (Ics/Icu). Business Impact: Superior fault tolerance for critical loads, reducing unplanned outages. Application: Heavy industry machines and process lines where uptime matters.
Get a Quick Quote for a ABB 2TFH100556R1001
Chat with us on WhatsApp - fast responses guaranteed
Need to speak with someone? We'll call you back within 2 hours during business hours
Interested in ABB 2TFH100556R1001?
Enquire Now
FAQs
Install the 3P plug‑in circuit breaker in standard low‑voltage panels designed for SACE Tmax XT components. Ensure correct wiring with plug‑in terminals, verify rated voltage and current match the application, and secure the device to maintain reliability under vibration and ambient heat. Using ABB installation instructions XT1 provides the best results.
The device is rated for 63 A with rated operational voltage of 690 V AC and 500 V DC, insulation voltage of 800 V, and short‑circuit withstand capabilities up to Ics = 75 kA (at various voltages) and Icu up to 100 kA. It supports AC/DC current types and provides a power loss of about 6.0 W per pole.
Yes. The product aligns with CE declarations of conformity and RoHS/REACH compliance for ABB SACE Tmax XT circuit breakers. This ensures regulatory compliance across the EU and many export markets, supporting environmental and safety standards in industrial installations.
Ideal for motor protection and short‑circuit protection in low‑voltage panels, machine control, conveyors, and general purpose industrial power distribution. Its 3P configuration and high Icu rating make it suitable for demanding loads with fast fault clearing, improving uptime and protecting downstream equipment.
With a tested 25,000 mechanical durability cycles and low per‑pole power loss, it reduces operating costs over time and minimizes spare part complexity. The plug‑in design simplifies inspections and replacements, helping maintenance teams schedule proactive service and shorten downtime during commissioning or upgrades.