ABB 2TFH100587R1001 Automatic Circuit Breaker - IEC60947-2

Part Number: 2TFH100587R1001
Manufacturer
ABB
Part number
2TFH100587R1001

Quick Summary

ABB 2TFH100587R1001 is a 3P molded case circuit breaker for reliable low-voltage protection in industrial panels. Engineers often contend with nuisance tripping and coordination with upstream devices during maintenance. This unit complies with IEC60947-2 and GB/T 14028.2, carries CE conformity, and includes RoHS/REACH declarations to support global installations. With a rated current of 50 A and 8 kV impulse withstand, it delivers robust protection while minimizing energy loss. Designed to integrate with the SACE Tmax XT family, it offers familiar installation, streamlined spare-part compatibility, and improved lifecycle cost for industrial automation projects.

Product Information

Extended Description

2TFH100587R1001 ABB: XT1S160 TMD50/500 PMP 3P
Environmental Product Declaration - EPD
NoDecNee
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
Environmental Information
Breakers - Packaging disposal information
Customs Tariff Number
85362000
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Version
P
Current Type
AC/DC
Electrical Durability
8000 cycle | 120 cycles per hour
Mechanical Durability
25000 cycle | 240 cycles per hour
Number of Poles
3P
Power Loss
at Rated Operating Conditions per Pole 5.0 W
Rated Current (In)
50 A
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
800 V
Rated Operational Voltage
690 V AC | 500 V DC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 63.75 kA | (230 V AC) 63.75 kA | (240 V AC) 63.75 kA | (380 V AC) 50 kA | (415 V AC) 37.5 kA | (440 V AC) 25 kA | (500 V AC) 18 kA | (525 V AC) 17.5 kA | (690 V AC) 5 kA | (250 V DC) 2 Poles in Series 50 kA | (500 V DC) 3 Poles in Series 50 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 85 kA | (230 V AC) 85 kA | (240 V AC) 85 kA | (380 V AC) 50 kA | (415 V AC) 50 kA | (440 V AC) 50 kA | (500 V AC) 36 kA | (525 V AC) 35 kA | (690 V AC) 8 kA | (250 V DC) 2 Poles in Series 50 kA | (500 V DC) 3 Poles in Series 50 kA
Rated Uninterrupted Current (Iu)
160 A
Release
TMD
Release Type
TM
Remarks
ATLAS
Short-Circuit Performance Level
S
Standards
IEC60947-2 | GB/T 14028.2
Sub-type
XT1
Terminal Connection Type
Plug-In Circuit-Breakers
Data Sheet, Technical Information
SACE Tmax XT IEC Low voltage molded case circuit-breakers Catalog | SACE Tmax XT IEC TECHNICAL CHARACTERISTICS Low voltage molded case circuit-breakers
Declaration of Conformity - CE
EC Declaration of Conformity Tmax XT1
Instructions and Manuals
Installation instructions XT1
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
Three-pole Plug-In design speeds installation and minimizes wiring errors, translating to shorter commissioning times and lower labor costs in panel builds. In practice, technicians can swap breakers without heavy tooling, keeping critical lines energized less during replacements. Application: control panels, motor starter assemblies, and distribution boards in manufacturing lines. A 50 A rated current provides precise protection for common industrial loads, improving upstream coordination and reducing nuisance trips in feeders and MCCs. Application: motor-control centers and distribution panels serving conveyors and robotics. High short-circuit performance with Ics up to 63.75 kA and Icu up to 85 kA ensures fast interruption, reducing arc flash risk and equipment damage in power-station-like environments. Application: switchgear and plant-wide distribution. Electrical durability supports up to 8000 cycles (120 cycles per hour), offering long-term reliability in continuous operation environments. Power loss is 5.0 W per pole, helping manage panel heat and improve enclosure cooling efficiency. RoHS/REACH compliance, along with CMRT and CE declarations, mitigates supply-chain and regulatory risk while enabling global shipments.

Get a Quick Quote for a ABB 2TFH100587R1001

Chat with us on WhatsApp - fast responses guaranteed

Need to speak with someone? We'll call you back within 2 hours during business hours

Interested in ABB 2TFH100587R1001? Enquire Now

FAQs

Use the 3P Plug-In circuit-breaker format to mount quickly in compatible Tmax XT panels. Verify the panel cut-out, secure busbar connections, and follow the torque specifications for terminal screws. Ensure the installation footprint aligns with XT1 series dimensions and that wiring complies with local code and safety practices to minimize commissioning time.
The device is rated for 50 A In, with Ui of 800 V and Ue of 690 V AC / 500 V DC. It withstands impulses up to 8 kV (Uimp) and provides Ics up to 63.75 kA and Icu up to 85 kA at specified voltages, supporting robust protection across typical industrial distribution scenarios.
Yes. The 3P XT1 molded case design fits MCCs and feeder panels, offering reliable protection for motor circuits with moderate loads. Its 50 A rating, fast break capabilities, and compatibility with Tmax XT families support coordinated protection, while the CER/REACH/CMRT declarations simplify global deployment.
The breaker meets IEC60947-2 and GB/T 14028.2 standards, carries CE conformity, and includes RoHS/REACH declarations. CMRT is provided for conflict minerals reporting, and WEEE categorization supports proper end-of-life disposal, helping you comply with regulatory and sustainability demands in global projects.
Durability is rated at up to 8000 electrical cycles (120 cycles per hour), with 5.0 W power loss per pole to keep heat within design limits. This reduces downtime, improves energy efficiency, and simplifies spare-part management, delivering lower total cost of ownership in high-duty manufacturing environments.