ABB 2TFH100617R1001 Moulded Case Circuit Breaker - Ics 100 kA
Part Number: 2TFH100617R1001
Quick Summary
ABB 2TFH100617R1001 Moulded Case Circuit Breaker is designed to protect industrial electrical networks by interrupting fault currents in automation and power-distribution panels. Engineers often face the challenge of choosing devices that deliver fast protection without complicating installation or increasing maintenance cost. This unit aligns with IEC60947-2 and CE conformity, plus RoHS and REACH declarations, helping you meet regulatory demands with confidence. Featuring three poles, 160 A nominal current and 690 V AC operating voltage, it integrates with ABB SACE Tmax XT systems and supports plug-in installation for quick changes in dynamic production environments, delivering reliable thermal performance and long-term operation.
Product Information
Extended Description
2TFH100617R1001 ABB: XT2H160 Ekip LSI R160 PMP 3P
Environmental Product Declaration - EPD
NoDecNee
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
SCIP
e5048c63-70bd-4a49-bfbc-6c9bc82ac106 China (CN)
Environmental Information
Breakers - Packaging disposal information
Customs Tariff Number
85362000
Product Net Width
90.0 mm
Product Net Height
130 mm
Product Net Depth / Length
82.5 mm
Product Net Weight
2.54 kg
Package Level 1 Width
195 mm
Package Level 1 Height
225 mm
Package Level 1 Depth / Length
195 mm
Package Level 1 Gross Weight
2.64 kg
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Version
P
Current Type
AC
Electrical Durability
8000 cycle | 120 cycles per hour
Mechanical Durability
25000 cycle | 240 cycles per hour
Number of Poles
3P
Power Loss
at Rated Operating Conditions per Pole 13.4 W
Rated Current (In)
160 A
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
690 V AC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 100 kA | (230 V AC) 100 kA | (240 V AC) 100 kA | (380 V AC) 70 kA | (415 V AC) 70 kA | (440 V AC) 65 kA | (500 V AC) 50 kA | (525 V AC) 30 kA | (690 V AC) 15 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 100 kA | (230 V AC) 100 kA | (240 V AC) 100 kA | (380 V AC) 70 kA | (415 V AC) 70 kA | (440 V AC) 65 kA | (500 V AC) 50 kA | (525 V AC) 30 kA | (690 V AC) 15 kA
Rated Uninterrupted Current (Iu)
160 A
Release
Ekip LSI
Release Type
EL
Remarks
ATLAS
Short-Circuit Performance Level
H
Standards
IEC60947-2 | GB/T 14028.2
Sub-type
XT2
Terminal Connection Type
Plug-In Circuit-Breakers
Data Sheet, Technical Information
SACE Tmax XT IEC Low voltage molded case circuit-breakers Catalog | SACE Tmax XT IEC TECHNICAL CHARACTERISTICS Low voltage molded case circuit-breakers
Declaration of Conformity - CE
EC Declaration of Conformity Tmax XT2
Instructions and Manuals
Installation Instructions XT2 | Ekip C Dip LSI, Ekip C Dip LSIG and LIG XT2-XT4
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
Three-pole design with 160 A rated current and 690 V AC operating voltage provides robust protection for feeders and automation cabinets, reducing nuisance trips and enabling compact panel layouts. This supports streamlined wiring and cost-effective installations in manufacturing lines and process plants. High short-circuit and withstand ratings translate to dependable protection across 220–240 V and higher voltage configurations, enabling safer machinery control and minimized downtime in automotive, packaging, and general industrial settings. The Ekip LSI release and plug-in terminal connection simplify assembly and field servicing, allowing rapid replacements and reduced maintenance labor in mission-critical panels. Power loss of 13.4 W per pole lowers heat generation, improving panel reliability and reducing cooling requirements in crowded electrical enclosures. Compliance with RoHS, REACH, CMRT, and SCIP ensures regulatory peace of mind for global supply chains, while the XT2 family compatibility supports scalable, modular protection across legacy and modern installations.
Get a Quick Quote for a ABB 2TFH100617R1001
Chat with us on WhatsApp - fast responses guaranteed
Need to speak with someone? We'll call you back within 2 hours during business hours
Interested in ABB 2TFH100617R1001?
Enquire Now
FAQs
The 2TFH100617R1001 uses a plug-in circuit-breaker configuration designed for three-pole assemblies, enabling quick installation and straightforward replacement in ABB SACE Tmax XT panel systems. Its compact footprint (90 mm width, 130 mm height, 82.5 mm depth) and 2.54 kg weight support ergonomic mounting in standard enclosures, while maintaining secure terminal connections for reliable electrical performance in automation cabinets.
This unit is rated for 160 A operating current with a rated operating voltage of 690 V AC and rated insulation voltage of 1000 V. It provides short-circuit protection with a service breaking capacity up to 100 kA at lower voltages and up to 15 kA at 690 V, ensuring robust protection across common distribution and machine-control circuits in industrial environments.
Yes. The three-pole design, 160 A rating, and 690 V AC capability make it well-suited for motor feeders and control panels in automation applications. Its XT2 release and SACE Tmax XT lineage provide reliable selective protection for motors and drives, while its compact form factor supports efficient layout in machine enclosures and panel assemblies.
The breaker complies with IEC60947-2 and is CE marked. It also references RoHS information and REACH declarations, alongside CMRT and SCIP data, supporting responsible sourcing and regulatory compliance across global manufacturing operations and supply chains.
Electrical durability is rated at 8000 cycles and mechanical durability at 25000 cycles, with a fixed power loss of 13.4 W per pole under rated conditions. This combination reduces thermal stress and energy consumption, contributing to longer service life, lower cooling loads in panels, and lower total cost of ownership through fewer unplanned outages and easier field servicing with plug-in replacements.