ABB XT2H160 Moulded Case Circuit Breaker - R160 3P IEC60947-2
Part Number: 2TFH100623R1001
Quick Summary
ABB XT2H160 molded case circuit breaker protects three‑phase power feeds in industrial automation. Engineers often struggle with protecting feeders while minimizing nuisance trips and panel footprint. This device aligns with IEC60947-2 and GB/T 14028.2, with RoHS and REACH compliance and a CE declaration, delivering regulatory peace of mind. By combining a 160 A rating, 690 V AC capability, and LSIG release, it supports reliable protection, easier maintenance, and smoother installation across diverse industrial environments.
Product Information
Extended Description
2TFH100623R1001 ABB: XT2H160 Ekip LSIG R160 PMP 3P
Country of Origin
China (CN)
Lead Time
30 day
Made To Order
No
Warranty Return
Product under warranty must be returned
Product Sales Status
Inactive
Quote Only
No
Environmental Product Declaration - EPD
NoDecNee
REACH Declaration
REACh Declaration ABB Sace circuit breakers
RoHS Information
RoHS Declaration ABB Sace circuit breakers
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Conflict Minerals Reporting Template (CMRT)
CMRT - Conflict Minerals Reporting Template
SCIP
f6382727-7e24-42a6-9dd6-0bb30622eab5 China (CN)
Environmental Information
Breakers - Packaging disposal information
Customs Tariff Number
85362000
Product Net Width
90.0 mm
Product Net Height
130 mm
Product Net Depth / Length
82.5 mm
Product Net Weight
2.54 kg
Package Level 1 Width
195 mm
Package Level 1 Height
225 mm
Package Level 1 Depth / Length
195 mm
Package Level 1 Gross Weight
2.64 kg
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Version
P
Current Type
AC
Electrical Durability
8000 cycle | 120 cycles per hour
Mechanical Durability
25000 cycle | 240 cycles per hour
Number of Poles
3P
Power Loss
at Rated Operating Conditions per Pole 13.4 W
Rated Current (In)
160 A
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
690 V AC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 100 kA | (230 V AC) 100 kA | (240 V AC) 100 kA | (380 V AC) 70 kA | (415 V AC) 70 kA | (440 V AC) 65 kA | (500 V AC) 50 kA | (525 V AC) 30 kA | (690 V AC) 15 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(220 V AC) 100 kA | (230 V AC) 100 kA | (240 V AC) 100 kA | (380 V AC) 70 kA | (415 V AC) 70 kA | (440 V AC) 65 kA | (500 V AC) 50 kA | (525 V AC) 30 kA | (690 V AC) 15 kA
Rated Uninterrupted Current (Iu)
160 A
Release
Ekip LSIG
Release Type
EL
Remarks
ATLAS
Short-Circuit Performance Level
H
Standards
IEC60947-2 | GB/T 14028.2
Sub-type
XT2
Terminal Connection Type
Plug-In Circuit-Breakers
Data Sheet, Technical Information
SACE Tmax XT IEC Low voltage molded case circuit-breakers Catalog | SACE Tmax XT IEC TECHNICAL CHARACTERISTICS Low voltage molded case circuit-breakers
Declaration of Conformity - CE
EC Declaration of Conformity Tmax XT2
Instructions and Manuals
Installation Instructions XT2 | Ekip C Dip LSI, Ekip C Dip LSIG and LIG XT2-XT4
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
The XT2H160 combines a rugged three-pole design with a 160 A rated current, enabling precise protection for three‑phase power distribution in industrial facilities. This translates to fewer unexpected outages and lower downtime costs, particularly in packaging lines and machining cells where steady power is critical. It also supports plug‑in circuit‑breaker installation, which reduces commissioning time and simplifies panel upgrade projects, cutting on-site labor and improving changeover efficiency. With an 8 kV impulse withstand and a strong short‑circuit performance (Ics and Icu values noted in the datasheet), the device minimizes arc energy exposure and protects downstream equipment. Durability specifications—electrical 8000 cycles and mechanical 25000 cycles—mean longer service life in high‑duty settings. RoHS REACH compliance and CE declarations help ensure global market access and risk reduction for compliance teams. Together with 690 V AC operation and 1000 V insulation rating, the XT2H160 supports versatile integration into modern low‑voltage systems while keeping energy losses manageable (13.4 W per pole).
Get a Quick Quote for a ABB 2TFH100623R1001
Chat with us on WhatsApp - fast responses guaranteed
Need to speak with someone? We'll call you back within 2 hours during business hours
Interested in ABB 2TFH100623R1001?
Enquire Now
FAQs
For 3‑phase 690 V systems, ensure the panel supports plug‑in circuit breakers and that the mounting footprint matches the XT2H160. Verify the rated current (160 A), voltage rating (690 V AC), and available space for a 3P unit. Use the supplied installation instructions, observe torque values for terminal connections, and confirm compatibility with SACE Tmax XT family accessories to ensure reliable signaling and quick replacement if needed.
The XT2H160 provides a 160 A rated current, 690 V AC rated operational voltage, and 1000 V rated insulation voltage. It offers an 8 kV rated impulse withstand and short‑circuit ratings (Ics and Icu) across multiple voltages, ensuring robust protection against faults. These ratings translate to reliable interruption of fault currents, reduced equipment damage, and safer startup/shutdown sequences in mixed industrial loads.
Yes, the unit is designed for high‑duty environments with electrical durability of 8000 cycles and mechanical durability of 25000 cycles, making it suitable for frequent motor start/stop sequences typical in packaging lines. Its 3P configuration and 690 V operating range support motor feeders and conveyor drives, while the LSIG release provides selective tripping aligned with typical motor protection schemes.
The XT2H160 adheres to IEC 60947‑2 and GB/T 14028.2, with RoHS and REACH compliance to meet environmental and regulatory expectations. It carries a CE declaration of conformity and a CMRT statement for responsible sourcing. These certifications support safe operation, regulatory compliance, and global market access across diverse industries.
Lead time is specified at 30 days from order to dispatch, reflecting availability for standard configurations. Warranty terms indicate products under warranty must be returned if defects occur, so maintain proper warranty tickets and documentation. With its long durability and reliable trip characteristics, the XT2H160 can reduce maintenance intervals and downtime when integrated into preventive maintenance plans.